1505 8TH ST

WICHITA FALLS, TX 76301

Building Services - Other

Tag No.: K0500

Based on observation the facility failed to provide adequate information for final filters and filter frame inspection and replacement. facility advised to keep log of such information.

Electrical Equipment - Other

Tag No.: K0919

Based on observation the facility failed to provide required task lighting for the exterior generator per NFPA 99 2012

6.4.2.2.3.2 The life safety branch shall supply power for lighting, receptacles, and equipment as follows:
(1)?Illumination of means of egress in accordance with NFPA 101, Life Safety Code
(2)Exit signs and exit directional signs in accordance with NFPA 101, Life Safety Code
(3)*Hospital communications systems, where used for issuing instruction during emergency conditions
(4)Generator set location as follows:
(a)Task illumination
(b)Battery charger for emergency battery-powered lighting unit(s)
(c)Select receptacles at the generator set location and essential electrical system transfer switch locations