HospitalInspections.org

Bringing transparency to federal inspections

510 8TH AVENUE NE

HAZEN, ND 58545

No Description Available

Tag No.: K0062

Testing frequencies for automatic sprinkler systems range from quarterly to annually. Inspection frequencies can be as often as weekly to as long as annually. The frequencies for testing, inspection and maintenance of automatic sprinkler systems are dictated by the requirements as outlined by Table 5-1 of NFPA 25, Standard for the Inspection, Testing and Maintenance of Water-based Fire Protection Systems. NFPA 25 requires the facility to complete, maintain and make available to the authority having jurisdiction copies of records which indicate the procedure performed, by whom, the results and the date. These records are to be retained for the life of the system. The automatic sprinkler system is required to have specified maintenance.

The facility failed to ensure the automatic sprinkler system was continuously maintained in a reliable operating condition as required by NFPA 25, Standard for the Inspection, Testing and Maintenance of Water-based Fire Protection Systems.

Review of sprinkler records could not verify that the quarterly tests of the wet sprinkler system were conducted in the past twelve (12) months.

No Description Available

Tag No.: K0130

Records review indicated the facility failed to provide evidence of maintenance of fire dampers in a reliable operating condition as required by NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. Maintenance of fire dampers is required at least every 6 years. Maintenance of fire dampers includes:

(a) Fusible links shall be removed.
(b) All dampers shall be operated to verify that they close fully.
(c) The latch, if provided, shall be checked.
(d) Moving parts shall be lubricated as necessary.

No Description Available

Tag No.: K0144

Maintenance of emergency generator batteries should include checking and recording the value of the specific gravity. NFPA 110, Section A-6-3.6

The facility failed to ensure the emergency generator was in compliance with NFPA 110, Standard for Emergency and Standby Power Systems.

Record review determined the batteries in the emergency generator were last checked in November of 2012.