Tag No.: K0062

Based on observations and records review it was determined the facility failed to maintain the sprinkler system.

The findings included:

1. Observations of the old surgery room area on 11/8/11 at 9:26 AM, revealed a storage rack installed within 18 inches of the sprinkler.

2. Observation of the old dark room on 11/8/11 at 9:40 AM, revealed the sprinkler was painted and corroded.

3. Record review of the sprinkler system annual inspection/test report dated 6/27/11 on 11/8/11 at 10:30 AM,, revealed the sprinkler system had an incorrect tamper and value installed in triage room 126.

4. Record review on 11/8/11 at 10:35 AM, revealed no quarterly inspections were conducted on the sprinkler system during the 1st and 2nd quarters of 2010.

5. Record review on 11/8/11 at 10:37 AM, revealed no annual sprinkler inspection/test was conducted during 2010.

6. Record review on 11/8/11 at 10:40 AM, revealed no quarterly inspections were conducted on the sprinkler system during the 1st and 3rd quarters of 2011.

7. Record review on 11/8/11 at 10:41 AM, revealed the sprinkler system's 5 year obstruction investigation was overdue (Aug 11).

8. Record review on 11/8/11 at 10:42 AM, revealed the sprinklers system's 5 year gage test or replacement was overdue (Aug 11).

These findings were verified by the maintenance supervisor and acknowledged by the administrator during the exit conference on 11/8/1.