Bringing transparency to federal inspections
Tag No.: K0200
Door Inspections:
Fire-rated door assemblies and certain other doors in the means of egress shall be tested annually or per an accepted performance-based evaluation schedule approved by the AHJ per NFPA 80, 2010, Ch. 5.2. A written record of the inspections and testing shall be signed and kept for inspection by the AHJ. NFPA101, 7.2.1.15.
Based on observation the facility failed to maintain properly all the doors along the means of egress.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that fire rated doors along the means of egress were inspected annually however, there was no record of repairs performed on the doors identified as defective during the inspections.
Tag No.: K0281
Illumination of Means of Egress.
7.8.1.4* Required illumination shall be arranged so that the failure of any single lighting unit does not result in an illumination level of less than 0.2 ft-candle (2.2 lux) in any designated area.
Based on observation the facility failed to provide adequate illumination at exit landing.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that in the exit landing were missing two points of lights.
Tag No.: K0374
Based on observation the facility failed to provide adequate smoke barrier doors.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that there were many double egress doors without astragal. Provide astragals on these doors for optimal smoke infiltration protection.
Tag No.: K0500
Final filters and Frames:
Final filters and filter frames should be visually inspected for pressure drop and for bypass monthly. Filters should be replaced based on pressure drop or maintenance schedule with filters that provide the efficiencies specified. (ASHRAE 170, Informative Appendix A, Operations and Maintenance Procedures.) A log of filter replacements should be maintained for each air handler.
Based on observation the facility failed to provide adequate monthly pressure drop records.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that there was no record or logs of each air handler showing dates when the final filters, pre-filters have been replaced with the pressure differential across the filter before and after replacement where differential pressure monitors are required.
Tag No.: K0902
Medical gas tank farm -Signage - NFPA 99, 2012
8.3 Tanks must have permanent signage that states:
OXYGEN
NO SMOKING
NO OPEN FLAMES
8.4 Access to tanks should be controlled or locked.
NFPA, 99: 2012: 5.1.3.3.2*- Locations for central supply systems and the storage of positive-pressure gases shall meet the following requirements:
(1) They shall be constructed with access to move cylinders, equipment, and so forth, in and out of the
location on hand trucks complying with 11.4.3.1.1.
(2) They shall be secured with lockable doors or gates or otherwise secured.
(3) If outdoors, they shall be provided with an enclosure (wall or fencing) constructed of noncombustible
materials with a minimum of two entries/exits.
Based on observation the facility failed to provide adequate signage for gas storages outside and provide a procedure to ensure that the second exit is always open when somebody is the tank farm.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that the facility failed to provide adequate signage for gas storages outside and provide a procedure to ensure that the second exit is always open when somebody is the tank farm for safety reasons.
Light Switch Location:
Locations for central supply systems and the storage of medical gases shall meet the following requirements: (5) Be compliant with NFPA 70, National Electrical Code, for ordinary locations, with electrical devices located at or above 5 feet above finished floor to avoid physical damage - NFPA 99, 2002, 5.1.3.3.2(5).
Based on observation the facility failed to provide adequate safety features in the medical gas storage room.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that the facility failed to provide adequate safety measures in the medical gas storage room by installing an electrical light switch below the height of 5ft in the medical gas storage room.
Medical Bulk Storage clearance
"The minimum distance from any bulk oxygen system to any public sidewalk or parked vehicle shall be 10 ft." - NFPA 50, 2001, 2.2.12.
"The minimum distance from any bulk oxygen system to any line of adjoining property that can be built upon shall be 5 ft." - NFPA 50, 2001, 2.2.13.
"The minimum distance from any bulk oxygen system to any opening in walls of adjacent structures shall be 10 ft." - NFPA 50, 2001, 2.2.3
Based on observation, the facility failed to provide adequate clearance between the sidewalk or road bulk gas storage area.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that the facility failed to provide adequate clearance between the sidewalk or vehicular roadway and the bulk medical gas storage area.
Tag No.: K0907
Based on observation the facility failed to provide a risk assessment for the medical gas system.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that the facility had not done a risk assessment to determine the procedures and schedule for testing the medical gas system.
Tag No.: K0911
Essential Electrical System Segregation (Life Safety):
"The essential electrical system shall be divided into the following three branches: (1) Life safety, (2) Critical, (3) Equipment." NFPA 99, 2012, 6.4.2.2.1.1.
6.4.2.2.3 Life Safety Branch.
6.4.2.2.3.1 The life safety branch shall be limited to circuits essential to life safety.
6.4.2.2.3.2 "The life safety branch shall supply power for lighting, receptacles, and equipment as follows:
(1) Illumination of means of egress in accordance with 101, Life Safety Code,
(2) Exit signs and exit directional signs in accordance with NFPA 101, Life Safety Code,
(3) Hospital communications systems, where used for issuing instruction during emergency conditions,
(4) Generator set locations as follows:
(a) Task illumination,
(b) Battery charger for emergency battery-powered lighting unit(s),
(c) Select receptacles at the generator set location and essential electrical system transfer switch locations,
(5) Elevator cab lighting, control, communications, and signal systems,
(6) Electrically powered doors used for building egress,
(7) Fire alarms and auxiliary functions of fire alarm combination systems complying with NFPA 72, National Fire Alarm and Signaling Code."
6.4.2.2.3.3 "Alarm and alerting systems (other than fire alarm systems) shall be connected to the life safety branch or critical branch."
6.4.2.2.3.4 "Loads dedicated to a specific generator, including the fuel transfer pump(s), ventilation fans, electrically operated louvers, controls, cooling system, and other generator accessories essential for generator operation, shall be connected to the life safety branch or the output terminals of the generator with overcurrent protective devices."
6.4.2.2.3.5 "No functions other than those in 6.4.2.2.3.2, 6.4.2.2.3.3, and 6.4.2.2.3.4 shall be connected to the life safety branch, except as specifically permitted in 6.4.2.2.3."
Based on observation the facility had incorrect circuits connected in the essential electrical system.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that were no select receptacle at Generator and ATS locations. Provide these receptacles and ensure that they are powered from the Life Safety branch/panel.
Generator EPOS or Kill Switch:
"All installations shall have a remote manual stop station of a type to prevent inadvertent or unintentional operation located outside the room housing the prime mover, where so installed, or elsewhere on the premises where the prime mover is located outside the building" - NFPA 110, 2010.
Based on observation the facility had incorrectly installed the Generator kill switch in a locked location.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that there was not generator kill switch installed outside the generator enclosure.
Tag No.: K0913
Based on observation the facility failed to provide adequate risk assessment for all the operating rooms.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that risk assessments were not performed by the governing body to determine if the Operating rooms were wet or dry locations. If determined to be wet, they must be protected by line isolation monitors or GFCIs.
Tag No.: K0914
Based on observation the facility failed to provide adequate maintenance and testing of Essential Electrical System.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that there were the following issues:
1. That additional testing was not being performed correctly in terms of referencing each receptacle to the different tests performed on the particular receptacle in the patient care area at intervals defined by documented performance data on all the patient care receptacles. The testing record shall be such that each area and receptacles tested must be identified.
2. Records of where, type of repairs performed and date of electrical maintenance and required tests performed in all the patient care areas.
Tag No.: K0918
Based on observation the facility failed to provide adequate maintenance and testing of Essential Electrical System.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that there were the following issues:
1. The monthly load tests were not being done consistently monthly -at approximately 30 days apart.
2. The main and feeder circuit breakers were not being inspected annually and there was no program for periodically exercising the
components.
3. There were no records of maintenance and testing maintained.
Tag No.: K0924
Based on observation the facility failed to provide adequate medical gas equipment testing.
The inspector observed, while accompanied by the Facilities Director, Market Facilities Compliance Officer and Associate Vice President (AVP) Regulatory during the hours of the inspection from 3:00 pm to 7:00 pm on 9/20/2022 that the facility had no scheduled maintenance program for medical gas equipment.