Tag No.: K0147

Based on record review and staff interview it was determined the facility failed to ensure periodic testing and maintenance of the facility's 3 transfer switches.

Findings:

On 12/20/16, 15:00, the inspection and maintenance reports for the facility's 3 transfer switches was requested and not provided.

The CEO acknowleged the transfer switch inspections were not available.
_____

Based on observation and staff interview it was determined the facility failed to ensure the following equipment was inspected and maintained within the operating suite.

Findings:

On 12/20/16 at 10:24 a.m., an inspection label on a power strip located in the operating room indicated it was last inspected on January 2015 and due Feb. 2015. A power strip located in the endoscopic procedure room had an inspection label that indicated the next inspection was due in 2015.

The CEO acknowledged the out of date inspections for the power strips in the operating room and endo procedure room.


At 10:43 a.m., an certificate of inspection from the department of labor indicated the sterilizer located in the surgical suite was last inspected on March 1, 2014 and due on Jan 31, 2015.

The CEO acknowledged the missing annual inspection for the surgical suite sterilizer.