Tag No.: K0039
Based on observation, it was determined that the facility failed to ensure that a clear and unobstructed width of 4 feet for exit access was provided.
Findings include:
1. On 2/28/11 at 2:05 PM, in the presence of Staff #27, the exitway to Stair #5, in the SICU, was reduced to 24" wide, by four (4) stored beds that were not in use.
Tag No.: K0062
Based on observation, it was determined that the facility failed to ensure that the automatic sprinkler system was maintained.
Findings include:
1. On 2/28/11 at 10:30 AM, in the presence of Staff #27, three (3) boxes of supplies were stored within 18" of the sprinkler in the plumber shop.
Tag No.: K0076
Based on observation, it was determined that the facility failed to protect stored medical gas in accordance with NFPA 99.
Findings include:
1. On 2/28/11 at 11:55 AM, in the presence of Staff #27, fifteen (15) tanks of medical gas were unsecured in the A level tank cage.