Tag No.: K0341
.
Based on observation and interview, the facility failed to maintain the fire alarm remote annunciator per the requirements of:
2012 NFPA 101, 19.3.4.1, and 9.6.1.3
2010 NFPA 72, 10.16.3*
Findings include:
On 6/27/2018, during a tour of the facility from 12:45 pm to 3:45 pm, the fire alarm remote annunciator was not readily accessible to responding personnel.
.
Tag No.: K0353
.
Based on review of documentation and interview, the facility failed to maintain the automatic sprinkler system per the requirements of:
2012 NFPA 101, 19.3.5.1, 9.7.5, 9.7.7, and 9.7.8
2011 NFPA 25, Table 5.1.1.2
Findings include:
On 6/28/2018, during a tour of the facility from 8:15 am to 10:45 am, the facility failed to provide all of the quarterly automatic sprinkler inspection records for the past 12 months. Only the annual inspection conducted on 03/23/2018 was provided.
A member of the maintenance staff and administrator was present, when this deficiency was identified.
.
Tag No.: K0353
.
Based on review of documentation and interview, the facility failed to maintain the automatic sprinkler system per the requirements of:
2012 NFPA 101, 19.3.5.1, 9.7.5, 9.7.7, and 9.7.8
2011 NFPA 25, Table 5.1.1.2
Findings include:
On 6/28/2018, during a tour of the facility from 8:15 am to 10:45 am, the facility failed to provide all of the quarterly automatic sprinkler inspection records for the past 12 months. Only the annual inspection conducted on 03/23/2018 was provided.
A member of the maintenance staff and administrator was present, when this deficiency was identified.
Tag No.: K0781
.
Based on observation and interview, the facility failed to prohibit portable space heating devices per the requirements of:
2012 NFPA 101, 19.7.8
Findings include:
On 6/27/2017, during a tour of the facility from 12:45 pm to 3:45 pm, the surveyor observed a portable space heating device (unplugged) under a desk in the Physical Therapy Office.
A member of the maintenance staff was present when this deficiency was identified.
.
Tag No.: K0916
.
Based on observation and interview, the facility failed to maintain the generator's remote annunciator per the requirements of:
2012 NFPA 99, 6.4.1.1.17
Findings include:
On 6/27/2018, during a tour of the facility from 12:45 pm to 3:45 pm, the surveyor observed the generator's remote annunciator was not in a location readily observed by operating personnel at a regular work station.
.
Tag No.: K0923
.
Based on observation and interview, the facility failed to maintain the oxygen storage area per the requirements of:
2012 NFPA 99, 11.6.5.3
Findings include:
On 6/27/2017, during a tour of the facility from 12:45 pm to 3:45 pm, the surveyor observed the empty oxygen cylinders were not marked to avoid confusion and delay.
A member of the maintenance staff was present when this deficiency was identified.