Tag No.: K0014

Based on observation of the surveyor on June 28 th, 2011:

The traction room has older peg/particle board on the wall with no documentation of the interior finish. The room is open to the exit corridor.


The maintenance director was present during the observation.

No Description Available

Tag No.: K0056

Based on observation of the surveyor on June 28 th, 2011

The kitchen storage room has rack storage of large cans that are within 18 inches of the sprinkler head. (the can was removed immediately)


The maintenance director was present during this observation.

No Description Available

Tag No.: K0147

Based on observation of the surveyor on June 28 th, 2011

There were several empty computer boxes with in 36 inches of the electrical panel in the IO room located in basement (boxes were removed immediately)

The maintenance director was present during this observation.