HospitalInspections.org

Bringing transparency to federal inspections

323 SW 10TH ST

MADISON, SD 57042

No Description Available

Tag No.: K0028

Based on observation, measurement, and interview, the provider failed to maintain clear door widths of at least 32 inches in five of five smoke barriers in the patient wings. Findings include:

1. Observation and measurement at 10:00 a.m. on 5/3/11 revealed the cross-corridor smoke barrier doors in the patient wings were only 29 inches wide and did not provide a clear opening width of 32 inches. Interview with the facility manager at the time of the observation revealed those doors were from the original construction.

The building meets the FSES. Please mark an "F" in the completion date column to indicate the provider's intent to correct deficiencies identified in K000.