Bringing transparency to federal inspections
Tag No.: K0025
Based on surveyor observation and staff interview, the facility failed to maintain smoke barriers to resist the passage of smoke. The facility has a capacity of 25 and a census of 4.
Findings include:
Observations and staff interview on 02/18/15 at 10:28 a.m., revealed an approximately 3 foot by 8-inch hole through the smoke barrier above the smoke barrier doors near the Pharmacy.
Administrative Staff A and Maintenance Staff A observed this finding.
Tag No.: K0062
Based on record review and staff interview, the facility failed to maintain the sprinkler system in accordance with National Fire Protection Association (NFPA) 25, 1998 edition. The facility has a capacity of 25 and a census of 4.
Findings include:
Record review and staff interview on 02/18/15 revealed the following deficiencies:
1. At 9:27 a.m. the Midwest sprinkler system inspection report dated 02/21/14 stated, "small storage room in ambulance garage hallway isn't properly covered." The facility had not corrected this deficiency at the time of the inspection.
2. At 10:32 a.m. linens in the Linen Closet near the Meditation Room were located within 18-inches of the sprinkler head.
Administrative Staff A and Maintenance Staff A observed this finding.
Tag No.: K0147
Based on surveyor observation and staff interview, the facility failed to maintain the electrical system in accordance with National Fire Protection Association (NFPA) 70, 1999 edition. The facility has a capacity of 25 and a census of 4.
Findings include:
Observations and staff interview on 02/18/15 at 10:03 a.m., revealed an open electrical junction box located above panel HA-1 in the AHU 6 Room.
Administrative Staff A and Maintenance Staff A observed this finding.