No Description Available

Tag No.: K0011

Based on visual observations and interview with facility engineer the facility failed to maintain a fire barrier of at least two-hour between nonconforming building. The deficient practice had the potential to affect 9 floors where the medical office building connect.

Findings:

During the facility tour on 12/1-15/2010, between the hours of 8:30am and 4:30pm, it was observed that there was no fire barrrie separation between the medical office building and hospital the medical office building is a non conforming building that dose not meet healthcare requirements for life safety code. The Life Safety Code 2000 existing, Which this facility is inspected under require a two-hour fire barrier separate the two.

No Description Available

Tag No.: K0027

Based on visual observations the facility failed to maintain barrier doors that self-close and latch in their frames . The deficient practice had the potential to affect 4 of 8 smoke barriers, and approximally 25 patients.

Findings:

During the facility tour on 2/1-15/2010, between the hours of 8:30am and 4:30pm, it was observed that barrier doors on 3rd floor labor and delivery and 2nd floor NICU barrier doors did not have latching hardware on them,which these doors unable of self-closing and latching in their frames.

No Description Available

Tag No.: K0027

Based on visual observations the facility failed to maintain barrier doors that self-close and latch in their frames. The deficient practice had the potential to affect 4 of 8 barriers, and approximately 18 patients.

Findings:

During the facility tour on 2/1-15/2010, between the hours of 8:30am and 4:30pm, it was observed that 1st floor surgery and MRI barrier doors in basement did not have latching hardware, which will not allow these doors to self-close and latch in there frames.

No Description Available

Tag No.: K0067

Based on visual observations the facility failed to maintain heating,ventilating, and air conditioning comply whit this standard. The deficient practice had the potential to affect 10 patients .

Findings:

During the facility tour on 2/1-15/2010, between the hours of 8:00am and 4:30pm , it was observed that the corridor 1st floor in outpatient's clinical rehab /physical therapy being used for return air plenum.

LIFE SAFETY CODE STANDARD

Tag No.: K0011

Based on visual observations and interview with facility engineer the facility failed to maintain a fire barrier of at least two-hour between nonconforming building. The deficient practice had the potential to affect 9 floors where the medical office building connect.

Findings:

During the facility tour on 12/1-15/2010, between the hours of 8:30am and 4:30pm, it was observed that there was no fire barrrie separation between the medical office building and hospital the medical office building is a non conforming building that dose not meet healthcare requirements for life safety code. The Life Safety Code 2000 existing, Which this facility is inspected under require a two-hour fire barrier separate the two.

LIFE SAFETY CODE STANDARD

Tag No.: K0027

Based on visual observations the facility failed to maintain barrier doors that self-close and latch in their frames . The deficient practice had the potential to affect 4 of 8 smoke barriers, and approximally 25 patients.

Findings:

During the facility tour on 2/1-15/2010, between the hours of 8:30am and 4:30pm, it was observed that barrier doors on 3rd floor labor and delivery and 2nd floor NICU barrier doors did not have latching hardware on them,which these doors unable of self-closing and latching in their frames.

LIFE SAFETY CODE STANDARD

Tag No.: K0027

Based on visual observations the facility failed to maintain barrier doors that self-close and latch in their frames. The deficient practice had the potential to affect 4 of 8 barriers, and approximately 18 patients.

Findings:

During the facility tour on 2/1-15/2010, between the hours of 8:30am and 4:30pm, it was observed that 1st floor surgery and MRI barrier doors in basement did not have latching hardware, which will not allow these doors to self-close and latch in there frames.

LIFE SAFETY CODE STANDARD

Tag No.: K0067

Based on visual observations the facility failed to maintain heating,ventilating, and air conditioning comply whit this standard. The deficient practice had the potential to affect 10 patients .

Findings:

During the facility tour on 2/1-15/2010, between the hours of 8:00am and 4:30pm , it was observed that the corridor 1st floor in outpatient's clinical rehab /physical therapy being used for return air plenum.