Gas Equipment - Cylinder and Container Storag

Tag No.: K0923

Based on observation and interview, the facility failed to protect medical gas storage as required. Oxygen cylinders were not stored with the required precautions.

Findings include:

1. Observation on 6/24/25 at 1:35 p.m. in the oxygen storage room with Vice president J revealed two full D-size oxygen cylinders were stored upright outside of the oxygen cylinder storage rack. One C-size oxygen cylinder was found housed within a fabric case and was lying on the floor beside the oxygen cylinder storage rack.

Vice president J agreed that the cylinders were stored improperly.

The deficiency affected one of one smoke compartments.