HospitalInspections.org

Bringing transparency to federal inspections

345 TENTH AVENUE

GRANITE FALLS, MN 56241

Hazardous Areas - Enclosure

Tag No.: K0321

Based on observation and interview, the Facility failed to maintain hazardous areas are protected by a fire barrier having 1-hour fire resistance rating.

Hazardous Areas - Enclosure
2012 EXISTING
Hazardous areas are protected by a fire barrier having 1-hour fire resistance rating (with 3/4-hour fire rated doors) or an automatic fire extinguishing system in accordance with 8.7.1. When the approved automatic fire extinguishing system option is used, the areas shall be separated from other spaces by smoke resisting partitions and doors in accordance with 8.4. Doors shall be self-closing or automatic-closing and permitted to have nonrated or field-applied protective plates that do not exceed 48 inches from the bottom of the door.
Describe the floor and zone locations of hazardous areas that are deficient in REMARKS.
19.3.2.1

Area Automatic Sprinkler Seperation N/A
a. Boiler and Fuel-Fired Heater Rooms
b. Laundries (larger than 100 square feet)
c. Repair, Maintenance, and Paint Shops
d. Soiled Linen Rooms (exceeding 64 gallons)
e. Trash Collection Rooms
(exceeding 64 gallons)
f. Combustible Storage Rooms/Spaces
(over 50 square feet)
g. Laboratories (if classified as Severe
Hazard - see K3220)

Findings include:

On facility tour between 10:00 AM and 1:00 PM on 08/21/2018, observation revealed the door to the Soiled Utility Room near the Nurse's Station was observed open. This door needs to self close and latch.

This deficient practice was verified by the Facility Maintenance Director.

Evacuation and Relocation Plan

Tag No.: K0711

Based on documentation review and interview, the Facility failed to maintain a Evacuation and Relocation Plan according to the 2012 Life Safety Code.

Evacuation and Relocation Plan
There is a written plan for the protection of all patients and for their evacuation in the event of an emergency.
Employees are periodically instructed and kept informed with their duties under the plan, and a copy of the plan is readily available with telephone operator or with security. The plan addresses the basic response required of staff per 18/19.7.2.1.2 and provides for all of the fire safety plan components per 18/19.2.2.
18.7.1.1 through 18.7.1.3, 18.7.2.1.2, 18.7.2.2, 18.7.2.3, 19.7.1.1 through 19.7.1.3, 19.7.2.1.2, 19.7.2.2, 19.7.2.3

FINDINGS INCLUDE:

On facility tour between 10:00 AM and 1:00 PM on 08/21/2018, documentation review revealed the Facility Fire Emergency Plan needs to be updated to include language that staff will call 911 in the event of smoke and/or fire.

This deficient practice was verified by the Facility Maintenance Director.