161 RIVER OAKS DRIVE

CANTON, MS 39046

No Description Available

Tag No.: K0011

Based on observation and testing, the facility failed to provide the two hour fire separation between nonconforming building.

Findings Include:

While inspecting the separation wall between the General E.R. waiting room and clinics on 02/23/10 at approximately 11:00 a.m., the surveyor and maintenance director observed the two hour fire separation had a one inch to two inch gap between the wall and the deck above.

This deficient practices have the potential of effecting the entire facility. The maintenance supervisor and the administrator were notified during an exit conference.

LIFE SAFETY CODE STANDARD

Tag No.: K0011

Based on observation and testing, the facility failed to provide the two hour fire separation between nonconforming building.

Findings Include:

While inspecting the separation wall between the General E.R. waiting room and clinics on 02/23/10 at approximately 11:00 a.m., the surveyor and maintenance director observed the two hour fire separation had a one inch to two inch gap between the wall and the deck above.

This deficient practices have the potential of effecting the entire facility. The maintenance supervisor and the administrator were notified during an exit conference.