601 HAMILTON AVE

TRENTON, NJ 08629

No Description Available

Tag No.: K0038

Based on observation, it was determined that, the facility failed to have exits that are readily accessible at all times.

Findings include:

1. On 4/6/10, at 10:30 AM, in the presence of Staff #3, the exit door to the courtyard adjacent to the P7 elevator did not immediately open.

No Description Available

Tag No.: K0039

Based on observation, it was determined that, the facility failed to provide exit corridors of 4 feet width(clear and unobstructed).

Findings include:

1. On 4/6/10, at 11:30 AM, in the presence of Staff #3, in the 2nd floor corridor between 2B and Old Main units, the exit way width was restricted to 2'-6" by stretchers, wheelchairs, and boxes.

No Description Available

Tag No.: K0046

Based on observation, it was determined that, the facility failed to provide emergency lighting.

Findings include:

1. On 4/6/10, at 10:00 AM, in the presence of Staff #3, the battery powered light in the in the 2nd generator room could not light.

No Description Available

Tag No.: K0047

Based on observation, it was determined that, the facility failed to display exit lights with continuous illumination.

Findings include:

1. On 4/6/10, at 10:15 AM, in the presence of Staff #3, in the chapel, the 2 exit lights did not light.

No Description Available

Tag No.: K0106

Based on observation, it was determined that, the facility failed to provide a Type 1 Essential Electrical System in accordance with NFPA 99.

Findings include:

1. On 4/6/10, at 10:40 AM, in the presence of Staff #3, the generator in the 1st generator room was a natural gas fired unit which did not have a fuel source on site.

No Description Available

Tag No.: K0135

Based on observation, it was determined that, the facility failed to store flammable liquids in approved containers.

Findings include:

1. On 4/6/10, at 10:35 AM, in the presence of Staff #3, in the 1st generator room, there were 23 gallons of flammable xylene that were not stored in a fire rated cabinet.