Tag No.: K0056
Based upon observation and staff interview, the facility fails to assure that the automatic sprinkler system is installed in accordance with NFPA 13. The deficient practice does not provide complete coverage for all portions of the building, affecting 1 of 4 smoke zones. The facility has a capacity of 25 with a census of 15 at the time of the survey.
Findings include.
During the tour conducted on 03/02/2011, at 2:20 p.m., observation revealed a lack of sprinkler coverage in a portion of the hospital's administrative offices. A dividing wall constructed post installation of the automatic sprinkler system restricts some of the coverage intended for the office area to the materials storage room.
Staff M was present and aware of the findings. Staff M stated that the final location of the wall varied from the original design provided to the sprinkler contractor, resulting in a misplacement of sprinkler heads. The provided architect's code compliance review reflects an accurate location of the wall.