Tag No.: K0017
Based on a tour of the hospital it was observed that lounges and waiting areas which are open to the exit access corridor and which are not located so as to be constantly supervised from a staff location, were not provided with approved automatic smoke detectors, interconnected with the building free alarm system. The hospital does have a plan in place to address this item.
Tag No.: K0027
Based on a tour of the hospital it was observed that a plain glass vision panel with no fire label was found in one of the pair of 90-minute rated cross corridor doors near the third floor cath lab.
Tag No.: K0047
Based on a tour of the hospital it was observed that only one of the exits from the main dining room was identified with an illuminated exit sign. Hospital personnel were installing a second exit sign at the conclusion of the survey.
Tag No.: K0056
Based on a tour of the hospital it was observed that it was noted that the building is fully sprinklered. However, sprinklers were obstructed in several areas by cubicle curtain track or equipment supports in :
A. Various rooms in pediatrics, and
B. The Cath Lab Rooms.
Tag No.: K0056
Based on a tour of the hospital it was observed that it was noted that the building is fully sprinklered. However, sprinklers were obstructed in several areas by cubicle curtain track or equipment supports in the treatment in the Germantown Emergency Center.
Tag No.: K0141
Based on a tour of the hospital it was observed that signs were not provided in areas where oxygen cylinders were stored.
Tag No.: K0017
Based on a tour of the hospital it was observed that lounges and waiting areas which are open to the exit access corridor and which are not located so as to be constantly supervised from a staff location, were not provided with approved automatic smoke detectors, interconnected with the building free alarm system. The hospital does have a plan in place to address this item.
Tag No.: K0027
Based on a tour of the hospital it was observed that a plain glass vision panel with no fire label was found in one of the pair of 90-minute rated cross corridor doors near the third floor cath lab.
Tag No.: K0047
Based on a tour of the hospital it was observed that only one of the exits from the main dining room was identified with an illuminated exit sign. Hospital personnel were installing a second exit sign at the conclusion of the survey.
Tag No.: K0056
Based on a tour of the hospital it was observed that it was noted that the building is fully sprinklered. However, sprinklers were obstructed in several areas by cubicle curtain track or equipment supports in :
A. Various rooms in pediatrics, and
B. The Cath Lab Rooms.
Tag No.: K0056
Based on a tour of the hospital it was observed that it was noted that the building is fully sprinklered. However, sprinklers were obstructed in several areas by cubicle curtain track or equipment supports in the treatment in the Germantown Emergency Center.
Tag No.: K0141
Based on a tour of the hospital it was observed that signs were not provided in areas where oxygen cylinders were stored.