Means of Egress - General

Tag No.: K0211

Based on observation, interview and record review, facility staff failed to inspect, test and maintain the fire egress doors in accordance with the 2010 Editions of NFPA 80 (Standard for Fire Doors and Other Opening Protectives) and NFPA 105 (Standard for Fire Doors and Other Opening Protectives). Facility staff failed to conduct an annual inspection of the fire egress doors. The facility census was five.

1. Review of the facility's inspection, testing and maintenance records for the 2018 year showed the records did not contain documentation of an annual inspection of the fire egress doors during the 12-month period.

During an interview on 2/26/19 at 1:21 P.M., the Maintenance Supervisor said he did not know of the requirement to conduct annual inspections of the egress doors.


Review of NFPA 101, 2012 Edition showed the following:
-7.1.10.2.1 showed no furnishings, decorations, or other objects shall obstruct exits or their access thereto, egress therefrom, or visibility thereof.
-19.2.2.2.1 Doors complying with 7.2.1 shall be permitted.
-7.2.1.15.1* Where required by Chapters 11 through 43, the following door assemblies shall be inspected and tested not less than annually in accordance with 7.2.1.15.2 through 7.2.1.15.8:
(1) Door leaves equipped with panic hardware or fire exit hardware in accordance with 7.2.1.7;
(2) Door assemblies in exit enclosures;
(3) Electrically controlled egress doors;
(4) Door assemblies with special locking arrangements subject to 7.2.1.6.
-7.2.1.15.2 Fire-rated door assemblies shall be inspected and tested in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives. Smoke door assemblies shall be inspected and tested in accordance with NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives.
-7.2.1.15.3 The inspection and testing interval for fire-rated and nonrated door assemblies shall be permitted to exceed 12 months under a written performance-based program in accordance with 5.2.2 of NFPA 80, Standard for Fire Doors and Other Opening Protectives.
-7.2.1.15.4 A written record of the inspections and testing shall be signed and kept for inspection by the authority having jurisdiction.

Fire Alarm - Control Functions

Tag No.: K0344

Based on observation and facility staff interview, the facility failed to secure the fire alarm control panels against unauthorized use. The facility census was five.

1. Observation on 2/26/19, during the facility tour, showed a key in the fire alarm control panel at the nurses' station.

Observation on 2/26/19, during the facility tour, showed a key in the fire alarm panel in the breakroom/conference room area.

During an interview on 2/26/19 at 11:57 A.M., the Maintenance Supervisor said that fire alarm control panels are accessible to unauthorized people.

NFPA 72, National Fire Alarm and Signaling Code, 2010 Edition, Section 10.11.5.2 states: " The means shall be key operated or located within a locked cabinet, or arranged to provide equivalent protection against unauthorized use.

Fire Alarm System - Testing and Maintenance

Tag No.: K0345

Based on staff interview and record review facility staff failed to test the fire alarm system per the National Fire Protection Association (NFPA) requirements. The facility census was five.

1. Record review on 2/26/19 of the facility records did not show an annual fire alarm inspection.

During an interview on 2/26/19 at 12:57 P.M., the Maintenance Supervisor said that the facility does not conduct annual fire alarm inspections.

* See NFPA 72, National Fire Alarm and Signaling Code, 2010 edition, table 14.3.1 for testing requirements.

Smoke Detection

Tag No.: K0347

Based on observation and facility staff interview, facility staff failed to ensure areas open to the corridor contain smoke detection per NFPA 72, National Fire Alarm and Signaling Code. The facility census was five.

Observations on 2/26/19, during the facility tour, showed the vending machine room open to the designated exit corridor. Observation showed the room did not have smoke detector coverage.

During an interview on 2/26/19 at 11:47 A.M., the Maintenance Supervisor confirmed the observation.

19.3.4.1 General. Health care occupancies shall be provided
with a fire alarm system in accordance with Section 9.6.

Refer to NFPA 72, National Fire Alarm and Signaling Code, 2010 edition, sections 17.6.3 Location and Spacing and 17.6.3.3.1 Spacing for additional information.

Sprinkler System - Maintenance and Testing

Tag No.: K0353

Based on staff interview and record review, facility staff failed to inspect the wet sprinkler systems per NFPA 25, Standard for the Inspection, Testing, and maintenance of Water-Based Fire Protection Systems, 2011 edition. The facility census was five.

Record review on 2/26/19 did not show the following inspections:

-no monthly pressure checks for the wet sprinkler sprinkler system;

-annual inspection for the wet sprinkler system for any year;

-No quarterly inspections;

-5 year internal pipe inspections & gauge replacements/calibrations for the wet, antifreeze or dry deluge sprinkler systems

During an interview on 2/26/19 at 1:00 P.M., the Maintenance Director said the sprinkler inspections were missed.

Refer to NFPA 25, Standard for the Inspection, Testing, and maintenance of Water-Based Fire Protection Systems, 2011 edition, Chapters 5, 13 and 14 for additional information.

Fundamentals - Building System Categories

Tag No.: K0901

Based on record review and facility staff interview, the facility failed to ensure that all building systems had been assigned a risk assessment category and documented. The census was five.

1. Review of the facility documents for fire safety, building system tests, and policies showed no assessment of the which systems were critical for patient safety.

2. During an interview on 2/26/19 at 1:19 PM, the Maintenance Supervisor said the facility did not have categorical risk assessments for building systems.

Electrical Systems - Essential Electric Syste

Tag No.: K0918

Based on observation, staff interview and record review facility staff failed to conduct an annual load bank test on the emergency generator. Facility staff failed to run the emergency generator under load for 30 minutes monthly. Facility staff failed to provide an emergency stop switch away from the generator set location. The facility census was five.

1. Record review on 2/26/19 did not show records of the following:

-annual testing with the available building electrical load at a minimum of 30% of the generator nameplate rating or load bank records,

- monthly 30 minute under load tests

During an interview on 2/26/19 at 1:07 P.M., the Maintenance Supervisor said that he is not sure if the emergency generator pulls 30% of the generator nameplate rating. The Maintenance Supervisor said that facility staff does not run the generator for 30 minutes monthly.

2. Observation on 2/26/19, during the facility tour, showed the emergency generator's emergency stop switch located on the generator set.

During an interview on 2/26/19 at 11:35 A.M., the Maintenance Supervisor confirmed the observation.


NFPA 110, Standard for Emergency and Standby Power Systems, 2010 edition states:

5.6.5.6* All installations shall have a remote manual stop station
of a type to prevent inadvertent or unintentional operation located
outside the room housing the prime mover, where so installed,
or elsewhere on the premises where the prime mover is
located outside the building.

5.6.5.6.1 The remote manual stop station shall be labeled.

8.4.2* Diesel generator sets in service shall be exercised at
least once monthly, for a minimum of 30 minutes, using one
of the following methods:
(1) Loading that maintains the minimum exhaust gas temperatures
as recommended by the manufacturer
(2) Under operating temperature conditions and at not less
than 30 percent of the EPS nameplate kW rating

8.4.2.1 The date and time of day for required testing shall be
decided by the owner, based on facility operations.

8.4.2.2 Equivalent loads used for testing shall be automatically
replaced with the emergency loads in case of failure of
the primary source.

8.4.2.3 Diesel-powered EPS installations that do not meet the
requirements of 8.4.2 shall be exercised monthly with the available
EPSS load and shall be exercised annually with supplemental
loads at not less than 50 percent of the EPS nameplate kW
rating for 30 continuous minutes and at not less than 75 percent
of the EPS nameplate kWrating for 1 continuous hour for a total
test duration of not less than 1.5 continuous hours.

8.3 Maintenance and Operational Testing.

8.3.1* The EPSS shall be maintained to ensure to a reasonable
degree that the system is capable of supplying service within the
time specified for the type and for the time duration specified for
the class.

8.3.2 A routine maintenance and operational testing program
shall be initiated immediately after the EPSS has passed
acceptance tests or after completion of repairs that impact the
operational reliability of the system.

8.3.2.1 The operational test shall be initiated at an ATS and
shall include testing of each EPSS component on which maintenance
or repair has been performed, including the transfer of
each automatic and manual transfer switch to the alternate
power source, for a period of not less than 30 minutes under
operating temperature.

8.3.3 A written schedule for routine maintenance and operational
testing of the EPSS shall be established.

8.3.4 A permanent record of the EPSS inspections, tests, exercising,
operation, and repairs shall be maintained and readily
available.

8.3.4.1 The permanent record shall include the following:
(1) The date of the maintenance report
(2) Identification of the servicing personnel
(3) Notation of any unsatisfactory condition and the corrective
action taken, including parts replaced
(4) Testing of any repair for the time as recommended by the
manufacturer

8.3.5* Transfer switches shall be subjected to a maintenance and
testing program that includes all of the following operations:
(1) Checking of connections
(2) Inspection or testing for evidence of overheating and excessive
contact erosion
(3) Removal of dust and dirt
(4) Replacement of contacts when required

8.3.6 Paralleling gear shall be subject to an inspection, testing,
and maintenance program that includes all of the following
operations:
(1) Checking of connections
(2) Inspection or testing for evidence of overheating and excessive
contact erosion
(3) Removal of dust and dirt
(4) Replacement of contacts when required

8.3.7* Storage batteries, including electrolyte levels or battery
voltage, used in connection with systems shall be inspected
weekly and maintained in full compliance with manufacturer ' s
specifications.

8.3.7.1 Maintenance of lead-acid batteries shall include the
monthly testing and recording of electrolyte specific gravity. Battery
conductance testing shall be permitted in lieu of the testing
of specific gravity when applicable or warranted.

8.3.7.2 Defective batteries shall be replaced immediately
upon discovery of defects.

8.3.8 A fuel quality test shall be performed at least annually
using tests approved by ASTM standards.

8.4 Operational Inspection and Testing.

8.4.1* EPSSs, including all appurtenant components, shall be
inspected weekly and exercised under load at least monthly.

8.4.6 Transfer switches shall be operated monthly.

8.4.6.1 The monthly test of a transfer switch shall consist of
electrically operating the transfer switch from the standard position
to the alternate position and then a return to the standard
position.

7.2.4* Minimizing the possibility of damage resulting from interruptions
of the emergency source shall be a design consideration
for EPSS equipment.

A.7.2.4 When installing the EPSS equipment and related
auxiliaries, environmental considerations should be given,
particularly with regard to the installation of the fuel tanks
and exhaust lines, or the EPS building, or both.
To protect against disruption of power in the facility, it is recommended
that the transfer switch be located as close to the load
as possible. The following are examples of external influences:
(1) Natural conditions
(a) Storms
(b) Floods
(c) Earthquakes
(d) Tornadoes
(e) Hurricanes
(f) Lightning
(g) Ice storms
(h) Wind
(i) Fire
(2) Human-caused conditions
(a) Vandalism
(b) Sabotage
(c) Other similar occurrences
(3) Material and equipment failures
For natural conditions, EPSS design should consider the
"100-year storm" flooding level or the flooding level predicted
by the Sea, Lake, and Overland Surges from Hurricanes