HospitalInspections.org

Bringing transparency to federal inspections

220 5TH AVE W

TURTLE LAKE, ND 58575

No Description Available

Tag No.: K0011

The facility failed to ensure a complete two-hour fire resistive rated wall assembly between the hospital and the administrative building.

Observation determined the 90-minute fire rated self-closing door at the Activities Storage Closet did not self-close and latch to the door frame.

No Description Available

Tag No.: K0020

The facility failed to provide a one-hour fire resistance rated stair enclosure.

Observation determined the walls of the east stair enclosure stopped at the membrane ceiling and were not extended to the roof deck.

No Description Available

Tag No.: K0062

The facility failed to ensure all areas have proper coverage by the automatic fire sprinkler system.

Observation determined the new Bariatric Room is not adequately protected by the fire sprinkler system. The existing sprinkler system in this room had been dismantled to allow installation of the overhead rail structure.

No Description Available

Tag No.: K0144

The emergency generator must be inspected weekly. NFPA 110, 3-5.4.5

1) Review of records determined documentation of the weekly inspections of the generator did not include the battery fluid.

2) Inspection of the battery revealed the presence of corrosion build-up on the positive post connection.