HospitalInspections.org

Bringing transparency to federal inspections

300 SECOND AVENUE

LONG BRANCH, NJ 07740

No Description Available

Tag No.: K0017

Based on observation, it was determined that the facility failed to ensure that all corridors are separated from use by walls constructed with fire resistance rating.

Findings include:

On 9/30/13 at 10:05 AM, in the presence of Staff #45, it was observed that there was a penetration in the wall between the Wimpheimer Building and the corridor of the BBR Building.

No Description Available

Tag No.: K0018

Based on observation, it was determined that the facility failed to ensure that there were no impediments to the closing of the door.

Findings include:

On 9/30/13 at 10:10 AM, in the presence of Staff #45, it was observed that the smoke door on the Ground Floor North Wing could not close.

No Description Available

Tag No.: K0029

Based on observation, it was determined that the facility failed to ensure that rated construction for the use of the room was provided.

Findings include:

On 10/30/13 at 10:10 AM, in the presence of Staff #45, it was observed that in Room #G306, there were 2 penetrations in the rated wall.

No Description Available

Tag No.: K0047

Based on observation, it was determined that the facility failed to ensure that continuous illumination of exit lights was provided.

Findings include:

On 9/30/13 at 10:50 AM, in the presence of Staff #45, it was observed that the exit light at the Ground Floor Maintenance Building corridor was not lit.

No Description Available

Tag No.: K0052

Based on observation, it was determined that the facility failed to ensure that the fire alarm system was maintained.

Findings include:

1. On 10/30/13 at 11:10 AM, in the presence of Staff #45, it was observed that a construction cap was on the fire alarm detector in Room #G304A.

2. On 10/30/13 at 2:30 PM, in the presence of Staff #45, it was observed that a construction cap was on the fire alarm detector in Room #C579.

No Description Available

Tag No.: K0062

Based on observation, it was determined that the facility failed to ensure that the sprinkler system is maintained in reliable operating condition.

Findings include:

1. On 10/30/13 at 11:20 AM, in the presence of Staff #45, it was observed that in Room #G3165, (5) boxes of supplies were stored within 18" of the sprinkler system.

2. On 10/30/13 at 1:50 PM, in the presence of Staff #45, it was observed that in Room #R417, a basket and files were stored within 18" of the sprinkler system.

No Description Available

Tag No.: K0074

Based on observation, it was determined that the facility failed to ensure that cubical curtains that meet the requirements of NFPA 13, Standards for the Installation of Sprinkler Systems, are provided.

Findings include:

On 10/30/13 at 2:30 PM, in the presence of Staff #45, it was observed that the cubical curtains in Room #C576 through Room #C585 had mesh that was too small for a sprinklered environment.

No Description Available

Tag No.: K0076

Based on observation, it was determined that the facility failed to ensure that medical gas in storage was protected in accordance with NFPA 99 4-3.1.1.1.

Findings include:

Reference: NFPA 99 4-3.1.1.1 states, "Cylinders in service and in storage shall be secured and located to prevent falling or being knocked over."

1. On 9/30/13 at 10:50 AM, in the presence of Staff #45, it was observed that in the main medical gas tank room, six (6) tanks of medical gas were not secured.

2. On 10/30/13 at 2:25 PM, in the presence of Staff #45, it was observed that in the BBR Building, 5th floor corridor, a tank of medical gas was not secured.

LIFE SAFETY CODE STANDARD

Tag No.: K0017

Based on observation, it was determined that the facility failed to ensure that all corridors are separated from use by walls constructed with fire resistance rating.

Findings include:

On 9/30/13 at 10:05 AM, in the presence of Staff #45, it was observed that there was a penetration in the wall between the Wimpheimer Building and the corridor of the BBR Building.

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observation, it was determined that the facility failed to ensure that there were no impediments to the closing of the door.

Findings include:

On 9/30/13 at 10:10 AM, in the presence of Staff #45, it was observed that the smoke door on the Ground Floor North Wing could not close.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on observation, it was determined that the facility failed to ensure that rated construction for the use of the room was provided.

Findings include:

On 10/30/13 at 10:10 AM, in the presence of Staff #45, it was observed that in Room #G306, there were 2 penetrations in the rated wall.

LIFE SAFETY CODE STANDARD

Tag No.: K0047

Based on observation, it was determined that the facility failed to ensure that continuous illumination of exit lights was provided.

Findings include:

On 9/30/13 at 10:50 AM, in the presence of Staff #45, it was observed that the exit light at the Ground Floor Maintenance Building corridor was not lit.

LIFE SAFETY CODE STANDARD

Tag No.: K0052

Based on observation, it was determined that the facility failed to ensure that the fire alarm system was maintained.

Findings include:

1. On 10/30/13 at 11:10 AM, in the presence of Staff #45, it was observed that a construction cap was on the fire alarm detector in Room #G304A.

2. On 10/30/13 at 2:30 PM, in the presence of Staff #45, it was observed that a construction cap was on the fire alarm detector in Room #C579.

LIFE SAFETY CODE STANDARD

Tag No.: K0062

Based on observation, it was determined that the facility failed to ensure that the sprinkler system is maintained in reliable operating condition.

Findings include:

1. On 10/30/13 at 11:20 AM, in the presence of Staff #45, it was observed that in Room #G3165, (5) boxes of supplies were stored within 18" of the sprinkler system.

2. On 10/30/13 at 1:50 PM, in the presence of Staff #45, it was observed that in Room #R417, a basket and files were stored within 18" of the sprinkler system.

LIFE SAFETY CODE STANDARD

Tag No.: K0074

Based on observation, it was determined that the facility failed to ensure that cubical curtains that meet the requirements of NFPA 13, Standards for the Installation of Sprinkler Systems, are provided.

Findings include:

On 10/30/13 at 2:30 PM, in the presence of Staff #45, it was observed that the cubical curtains in Room #C576 through Room #C585 had mesh that was too small for a sprinklered environment.

LIFE SAFETY CODE STANDARD

Tag No.: K0076

Based on observation, it was determined that the facility failed to ensure that medical gas in storage was protected in accordance with NFPA 99 4-3.1.1.1.

Findings include:

Reference: NFPA 99 4-3.1.1.1 states, "Cylinders in service and in storage shall be secured and located to prevent falling or being knocked over."

1. On 9/30/13 at 10:50 AM, in the presence of Staff #45, it was observed that in the main medical gas tank room, six (6) tanks of medical gas were not secured.

2. On 10/30/13 at 2:25 PM, in the presence of Staff #45, it was observed that in the BBR Building, 5th floor corridor, a tank of medical gas was not secured.