35 MILES STREET

DAMARISCOTTA, ME null

No Description Available

Tag No.: K0027

K-27 Not Met.
While surveying the facility with the hospital engineer this inspector observed that the fire barrier/smoke compartment doors had an 3/8 inch vertical gap between the doors first floor section.

No Description Available

Tag No.: K0029

K-29 Not Met.
While surveying the facility with the hospital engineer this inspector observed that there were 3 penetrations in the ceiling floor assembly in the medical air compressor room.

Inspector also observed that the required fire rated door to the soild utility room in the Emergency Dept did not positively latch as required

No Description Available

Tag No.: K0130

K-130 Not Met . Other deficiencies observed in hospital and offsite buildings as listed below.

1. Helium tank in the MRI access area was not properly secured.
2. There is was no approved smoke detector present in the vicinity of the doctors sleeping room ( NFPA 72).

3. General surgery office had an exposed electrical wire in equipment room
4. Orthopedic office has non approved deadbolt lock on exit door.
5.79 Schooner street office did have have approved oxygen warning signs where oxygen was being stored.

No Description Available

Tag No.: K0147

K-147 Not Met.
While surveying the facility with the hospital engineer this inspector observed that non approved electrical taps were being used in patient care areas fro medical equipment( Corridors).
NFPA 70, NFPA 99.