Bringing transparency to federal inspections
Tag No.: K0015
Based on observation and document review, the facility failed to establish all wall coverings' interior finish flame spread rating to establish compliance.
Findings include:
Administrative and Outpatient Clinic (West Charleston) - Rooms #6, #26, #28, and #41 had wood paneling. The facility did not have flame spread documentation to establish the flame spread rating values and compliance for the wood paneling.
Tag No.: K0018
Based on observation, the facility failed to ensure that all corridor doors were free from impediments to closure.
Findings include:
The following corridor doors had impediments to closure making them incapable of resisting the transfer of smoke:
- Section E - Room #E170 corridor door was held open with chair.
Tag No.: K0022
Based on observation, the facility failed to ensure that all egress markings were properly installed.
Findings include:
Section C - In the office suite area, the egress marking did not have the chevron tab removed to properly direct occupants to the exit.
Tag No.: K0029
Based on observation, the facility failed to maintain the required fire-barrier rating for hazardous rooms.
Findings include:
- Section E - The E Unit's soiled holding room's corridor door was only 20-minute fire-rated (must be 45-minute rated).
- Section G - The G Unit's soiled holding room's corridor door was only 20-minute fire-rated (must be 45-minute rated).
Tag No.: K0038
39.2.1.1 All means of egress shall be in accordance with Chapter 7 and this chapter.
7.2.1.5.1 Doors shall be arranged to be opened readily from the egress side whenever the building is occupied. Locks, if provided, shall not require the use of a key, tool or special knowledge or effort for operation from the egress side.
Exception No. 1: This requirement shall not apply where otherwise provided in Chapters 18 through 23.
Exception No. 2: Exterior doors shall be permitted to have key-operated locks from the egress side provided that the following criteria have been met:
(a) Permission to use this exceptions provided in Chapters 12 through 42 for the specific occupancy.
(b) On or adjacent to the door, there is readily visible, durable sign in letters not less than 1 inch high on a contrasting background that reads as follows: THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED.
(c) The locking devise is the type that is readily distinguishable as locked.
(d) A key is immediately available to any occupant inside the building when it is locked.
Exception No. 2 shall be permitted to be revoked by the authority having jurisdiction for cause.
Exception No. 3: Where permitted in Chapters 12 through 42, key operations shall be permitted, provided that the key cannot be removed when the door is locked from the side from which egress is to be made.
Based on observation and staff interview, the facility failed to ensure key locked exterior egress doors conformed to the code.
Findings include:
East Las Vegas Clinic (Outpatient Building) - The north lobby's exterior exit door and the south lobby's exterior exit door were key-locked. The three accompanying facility staff members indicated that they did not have keys for either of these exterior exit doors. No signage was posted, no key was immediately available for egress, and no permission was granted in the existing business chapter of the Life Safety Code.
Note: The building has multiple tenants.
Tag No.: K0050
39.7.2 Extinguisher Training. Designated employees of business occupancies shall be periodically instructed in the use of portable fire extinguishers.
Based on document review, the facility failed to establish that staff had been trained on portable fire extinguisher use.
Findings include:
The facility did not have documentation to demonstrate that any outpatient staff had been trained on the use of portable fire extinguishers.
Tag No.: K0056
Based on observation, the facility failed to ensure that fire sprinkler protective coverage was installed in all required locations.
Findings include:
Building 3 - The elevator machine room was not equipped with a fire sprinkler coverage.
Tag No.: K0062
Based on observation, the facility failed to maintain the fire sprinkler system.
Findings include:
The following problems were identified for the support and outpatient buildings:
Downtown Las Vegas Clinic (Outpatient Building) - The fire department connection was found unprotected. The bifurcated connection was missing both of its protective covers/end caps.
Tag No.: K0074
Based on observation and document review, the facility failed to establish that draperies within the facility conformed to NFPA 701.
Findings include:
- Section A: The Gymnasium Office had black draperies hanging over the viewing panel to the Gymnasium. The facility did not have documentation for review to establish that the draperies had been tested and met NFPA 701 standard for fire retardancy.
- Section B: The Supply Office had 42 inch long draperies strung along two walls of the room use to cover supplies on shelving. The facility did not have documentation for review to establish that the draperies had been tested and met NFPA 701 standard for fire retardancy.
Tag No.: K0075
Based on observation, the facility failed to ensure that waste containers were limited to no more than 32-gallons or placed in an adequately fire-barrier protected (hazardous) room with fire sprinkler protection.
Findings include:
- Section C - In the Nourishment Room was a 44-gallon waste container.
- Section C - In the corridor near Room #126 was a 44-gallon waste container.
Tag No.: K0104
Based on observation, the facility failed to ensure openings between smoke compartments were protected.
Findings include:
Section D - Room #D166 had two unprotected conduit openings.
Tag No.: K0144
NFPA 99, Section 3-4.4.1.1 Maintenance and Testing of Alternative Power Source and Transfer Switches.
(b)1. Test Criteria. Generator sets shall be tested twelve (12) times a year with testing intervals between not less than 20 days or exceeding 40 days. Generator sets serving emergency and equipment systems shall be in accordance with NFPA 110, Standards for Emergency and Standby Power Systems.
NFPA 110, Chapter 8 Routine Maintenance and Operational Testing
8.1* General.
8.1.1 The routine maintenance and operational testing program shall be based on all of the following:
(1) Manufacturer's recommendations
(2) Instruction manuals
(3) Minimum requirements of this chapter
(4) The authority having jurisdiction
8.1.2 Consideration shall be given to temporarily providing a portable or alternate source whenever the emergency generator is out of service.
8.2* Manuals, Special Tools, and Spare Parts.
8.2.1 At least two sets of instruction manuals for all major components of the EPSS shall be supplied by the manufacturer(s) of the EPSS and shall contain the following:
(1) A detailed explanation of the operation of the system
(2) Instructions for routine maintenance
(3) Detailed instructions for repair of the EPS and other major components of the EPSS
(4) An illustrated parts list and part numbers
(5) Illustrated and schematic drawings of electrical wiring systems, including operating and safety devices, control panels, instrumentation, and annunciators
8.2.2 For Level 1 systems, instruction manuals shall be kept in a secure, convenient location, one set near the equipment, and the other set in a separate location.
8.2.3 Special tools and testing devices necessary for routine maintenance shall be available for use when needed.
8.2.4 Replacement for parts identified by experience as high mortality items shall be maintained in a secure location(s) on the premises.
8.2.4.1 Consideration shall be given to stocking spare parts as recommended by the manufacturer.
8.3 Maintenance and Operational Testing.
8.3.1* The EPSS shall be maintained to ensure to a reasonable degree that the system is capable of supplying service within the time specified for the type and for the time duration specified for the class.
8.3.2 A routine maintenance and operational testing program shall be initiated immediately after the EPSS has passed acceptance tests or after completion of repairs that impact the operational reliability of the system.
8.3.2.1 The operational test shall be initiated at an automatic transfer switch and shall include testing of each EPSS component on which maintenance or repair has been performed, including the transfer of each automatic and manual transfer switch to the alternate power source, for a period of not less than 30 minutes under operating temperature.
8.3.3 A written schedule for routine maintenance and operational testing of the EPSS shall be established.
8.3.4 A written record of the EPSS inspections, tests, exercising, operation, and repairs shall be maintained on the premises.
8.3.4.1 The written record shall include the following:
(1) The date of the maintenance report
(2) Identification of the servicing personnel
(3) Notation of any unsatisfactory condition and the corrective action taken, including parts replaced
(4) Testing of any repair for the time as recommended by the manufacturer
8.3.5* Transfer switches shall be subjected to a maintenance program that includes all of the following operations:
(1) Checking of connections
(2) Inspection or testing for evidence of overheating and excessive contact erosion
(3) Removal of dust and dirt
(4) Replacement of contacts when required
8.3.6* Storage batteries, including electrolyte levels, used in connection with Level 1 and Level 2 systems shall be inspected weekly and shall be maintained in full compliance with manufacturer's specifications.
8.3.6.1 Maintenance of lead-acid batteries shall include the monthly checking and recording of electrolyte specific gravity.
8.3.6.2 Defective batteries shall be replaced immediately upon discovery of defects.
8.4 Operational Inspection and Testing.
8.4.1* Level 1 and Level 2 EPSSs, including all appurtenant components, shall be inspected weekly and exercised under load at least monthly.
8.4.1.1 If the generator set is used for standby power or for peak load shaving, such use shall be recorded and shall be permitted to be substituted for scheduled operations and testing of the generator set, providing the same record as required by 8.3.4.
8.4.2* Generator sets in Level 1 and Level 2 service shall be exercised at least once monthly, for a minimum of 30 minutes, using one of the following methods:
(1) Under operating temperature conditions and at not less than 30 percent of the EPS nameplate kW rating
(2) Loading that maintains the minimum exhaust gas temperatures as recommended by the manufacturer
8.4.2.1 The date and time of day for required testing shall be decided by the owner, based on facility operations.
8.4.2.2 Equivalent loads used for testing shall be automatically replaced with the emergency loads in case of failure of the primary source.
8.4.2.3* Diesel-powered EPS installations that do not meet the requirements of 8.4.2 shall be exercised monthly with the available EPSS load and exercised annually with supplemental loads at 25 percent of nameplate rating for 30 minutes, followed by 50 percent of nameplate rating for 30 minutes, followed by 75 percent of nameplate rating for 60 minutes, for a total of 2 continuous hours.
8.4.3 Load tests of generator sets shall include complete cold starts.
8.4.4 Time delays shall be set as follows:
(1) Time delay on start:
a. 1 second minimum
b. 0.5 second minimum for gas turbine units
(2) Time delay on transfer to emergency: no minimum required
(3) Time delay on restoration to normal: 5 minutes minimum
(4) Time delay on shutdown: 5 minutes minimum
8.4.5 Level 1 and Level 2 transfer switches shall be operated monthly.
8.4.5.1 The monthly test of a transfer switch shall consist of electrically operating the transfer switch from the standard position to the alternate position and then a return to the standard position.
8.4.6* EPSS circuit breakers for Level 1 system usage, including main and feed breakers between the EPS and the transfer switch load terminals, shall be exercised annually with the EPS in the " off " position.
8.4.6.1 Medium- and high-voltage circuit breakers for Level 1 system usage shall be exercised every 6 months and shall be tested under simulated overload conditions every 2 years.
8.4.7 The routine maintenance and operational testing program shall be overseen by a properly instructed individual.
8.4.8* The EPSS shall be tested for the duration of its assigned class (see Section 4.2), or for a duration agreed to by the authority having jurisdiction for at least 4 hours, at least once within every 36-48 months.
8.4.8.1 The load shall be the EPSS system load running at the time of the test. The test shall be initiated by opening all switches or breakers supplying normal power to the EPSS.
8.4.8.2 A power interruption to non-EPSS loads shall not be required.
Based on interview and document review, the facility failed to establish that weekly generator inspections had occurred over the past 12-months.
Findings include:
The facility did not have documented evidence that the generator (Olympian) had been inspected weekly (Section 8.4.1 above). Maintenance Staff indicated that the generator was set to a timer and ran weekly, however they did not routinely inspect the generators weekly.
Tag No.: K0147
NFPA 101
Chapter 18-5.1.1 Utilities shall comply with the provisions of Section 9-1
Chapter 9-1.2 Electrical wiring and equipment installed shall be in accordance with NFPA 70, National Electric Code.
Exception: Existing installations may be continued in service subject to approval by the authority having jurisdiction.
NFPA 70
EXTENSION CORDS:
NFPA 70, Section 400-8 Unless specifically permitted in Section 400-7, flexible cords and cables shall not be used for the following:
(a) As a substitute for fixed wiring of a structure
NFPA 70, Section 305-4(h) Protection from Accidental Damage. Flexible cords and cables shall be protected from accidental damage. Sharp corners and projections shall be avoided. Where passing through doorways or other pinch points, protections shall be provided to avoid damage.
Based on observation, the facility failed to ensure that the electrical installations within the building conformed to NFPA 70, National Electrical Code.
Findings include:
The below listed locations had the following electrical problems:
-Section C - Office #C164 was using a power strip as permanent wiring for a refrigerator.