HospitalInspections.org

Bringing transparency to federal inspections

200 NORTH ELM STREET

ONAMIA, MN 56359

No Description Available

Tag No.: K0017

Based on observations, the facility had several penetrations in the corridors that are not in compliance with NFPA Life Safety Code 101 (00) Sections 19.3.6.2 and 8.2.4.4.1 in resisting the passage of smoke. This deficient practice could affect the exiting of all residents, staff and visitors. In the event of a fire in this space, smoke and fire could spread into the corridor making it untenable.

Findings include:

During the facility tour on 6-5-13 between 8:00-10:00 AM, it was observed that the facility had several penetrations in the corridor walls above the ceiling tiles in the following locations:

A. The central supply corridor
B. The corridor of the patient rooms
C. The corridor by the employee dining room.

This deficient practice was verified by the Facility Director of Faciilities (GV) and the time of exit.

LIFE SAFETY CODE STANDARD

Tag No.: K0017

Based on observations, the facility had several penetrations in the corridors that are not in compliance with NFPA Life Safety Code 101 (00) Sections 19.3.6.2 and 8.2.4.4.1 in resisting the passage of smoke. This deficient practice could affect the exiting of all residents, staff and visitors. In the event of a fire in this space, smoke and fire could spread into the corridor making it untenable.

Findings include:

During the facility tour on 6-5-13 between 8:00-10:00 AM, it was observed that the facility had several penetrations in the corridor walls above the ceiling tiles in the following locations:

A. The central supply corridor
B. The corridor of the patient rooms
C. The corridor by the employee dining room.

This deficient practice was verified by the Facility Director of Faciilities (GV) and the time of exit.