HospitalInspections.org

Bringing transparency to federal inspections

7777 FOREST LANE

DALLAS, TX 75230

Means of Egress - General

Tag No.: K0211

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:


A) There were missing signage "No Exit "on the door exit out to the roof garden at the 2nd level. This is not in accordance with NFPA 101, 2003, 7.10.8.3.1 and 7.10.8.3.2. - No Exit. Any door, passage, or stairway that is neither an exit nor a way of exit access and that is located or arranged so that it is likely to be mistaken for an exit shall be identified by a sign that reads as follows: NO EXIT. Such sign shall have the word NO in letters 2 in. high with a stroke width of 3/8 in. and the word EXIT in letters 1 in. high, with the word EXIT below the word NO .

Egress Doors

Tag No.: K0222

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:


A) Some double egress corridor doors were not released for free egress from the magnetic lock device upon activate the fire alarm system. Please verify all other mag lock of the entire facility are released for free egress upon the fire alarm activation.

Doors with Self-Closing Devices

Tag No.: K0223

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:

A) Some double egress corridor doors were not released from the magnetic hold open device upon activate the fire alarm system. Please verify all other mag hold of the entire facility are released for free egress upon the fire alarm activation.

Protection - Other

Tag No.: K0300

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:

A) Some of the smoke barrier partition or fire partition were not smoke or fire caulked.

Fire Alarm System - Initiation

Tag No.: K0342

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:

A) Some of the fire dampers or smoke dampers access panels were not labeled.


B) There was not a fire/smoke damper provided at the 2 hours fire separation at one end of the connecting bridge located at the heart& spine hospital.

Smoke Detection

Tag No.: K0347

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:

A) Some of the fire dampers or smoke dampers access panels were not labeled.

Building Services - Other

Tag No.: K0500

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:

A) If there is temperature and humidity variation will be adopted, please provide a letter indication that the hospital governing boy will adopt the CMS waiver Ref: S&C: 13-25-LSC & ASC.

Fundamentals - Building System Categories

Tag No.: K0901

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:

A) Please provide risk assessment in accordance with NFPA 99, 2012.

Electrical Systems - Other

Tag No.: K0911

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:


(A) There was a missing receptacle powered from life safety branch and a battery back-up light fixture at some of the automatic transfer switch location.


(B) The label for FACP indicated as MSI -14 and there was no corresponded panel schedule existed. Please verify the FACP is powered from the life safety branch or correct the panel schedule on the life safety branch.


(C) Some of the electrical directory was not updated in accordance to the new or modified receptacles.


(D) Some emergency panels were not distinctively marked so that they are readily identifiable as a component of the essential electrical system.


(E) Please verify that there is a bonding wire provided between the normal and essential branch-circuits panelboards. Please reference NFPA 70, 2002: 517-14. - Panelboard bonding requires the equipment grounding terminal buses of the normal and essential branch-circuits panelboards serving the same individual patient vicinity be bonded together with an insulated continuous copper conductor not smaller than # 10 AWG.


(F) There was not an electrical panel and circuit number labeling on the face of the FACP


(G) There were flexible utilized from emergency life safety electrical panel (DPCPLA). This wiring system shall be a nonflexible metal raceway.


(H) Some medication room light fixtures were not powered from the generator emergency panel and correctly was powered from the normal power.

Electrical Systems - Wet Procedure Locations

Tag No.: K0913

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:


A) Please provide which OR rooms are wet procedure location.

Electrical Systems Wet Procedure Locations: Operating rooms are considered wet procedure locations, unless otherwise determined by a risk assessment conducted by the facility governing body. Operating rooms defined as wet locations are protected by either isolated power or ground-fault circuit interrupters. A written record of the risk assessment is maintained and available for inspection. NFPA 99 - 6.3.2.2.8.4, 6.3.2.2.8.7, 6.4.4.2.

Gas Equipment - Cylinder and Container Storag

Tag No.: K0923

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:

A) There was no isolator provided between med gas copper pipes and the galvanized steel support at medical city hospital central plant.


B) The electrical device (fire pull) were located below 5'0" A.F.F. at the medical gas room. Please relocate it above 5'-0" A.F.F.

Features of Fire Protection - Fire Loss Preve

Tag No.: K0933

The inspector observed, while accompanied by the CEO, COO, CMO, CFO, Senior Vice President and CNE, Vice President of Clinical Excellence and Regulatory Compliance, Vice President of Clinical Excellence and Regulatory Compliance 2, Vice President of Operation, Manager of Facility Safety, Director of on 10/16/2019 that there were the following issues:


A) The policy and logs of the feature of fire protection - fire loss prevention in operating rooms was not available. Please provide updated policy for the fire loss prevention in operating room in accordance with NFPA 99, 2012, 15.13