Bringing transparency to federal inspections
Tag No.: K0069
Based on observations during the tour of the facility on the morning of 10/23/2015, with Director of Maintenance; the facility failed to provide proper distance between open flames and deep fry at kitchen. NFPA 96: 12.1.2.4 ..... All deep fat fryers shall be installed with at least a 16 inch space between the fryer and surface flames from adjacent cooking equipment.
Tag No.: K0145
Based on review of records during the survey of facility on 10/23/2015, with Director of Maintenance, the facility failed to provide documentation of the testing of grounding system at inpatient care areas. The electrical grounding of duplex outlets in general patient care areas shall be tested annually and critical care areas tested semi-annually. The facility must initiate a file on site to retain these records.
Receptacle testing in patient care areas shall be tested as follows:
Physical integrity of each receptacle. (Visual)
Continuity of the grounding of each receptacle. (Test)
Correct polarity of hot and neutral connections in each receptacle. (Test)
The retention force of the grounding blade shall be not less than 4 oz. (test)