Tag No.: K0130
Letters indicating preferred customer status in case of emergency situation for water and fuel source. When designated by the emergency management plan to provide continuous service in a disaster or emergency, health care facilities shall establish contingency plans for the continuity of essential building systems, as applicable: (2) water; and, (5) fuel sources. NFPA 99, 12.3.3.2 Continuity of Essential Building Systems
This STANDARD is not met as evidence by: Based on observations during the review of required maintenance logs, on the afternoon of 12/18/2013, the facility failed to supply a letter indicating preferred customer status for fuel.
Tag No.: K0145
Emergency system receptacles shall be identified and shall also indicate the panelboard and circuit number supplying them. NFPA 70: 517-19
This STANDARD is not being met, as evidenced by: Based on observation during the Survey on the morning of 12/18/2013, with the hospital's plant operations/facility team, numerous emergency system electrical receptacles in patient care areas did not have non-removable labels identifying the electrical panelboard and circuit number supplying them.