Bringing transparency to federal inspections
Tag No.: K0011
Based on observations made on October 12-14, 2010, the facility failed to maintain the 2-hour fire resistance of fire barrier walls and doors in fire walls.
Findings included:
1. Room 1202-C (a locked closet) on the exit corridor in the Maintenance department was observed at 2:00 p.m. on 10/12/10. There was a six inch by twelve inch penetration above the corridor door into the space above the corridor which was not sealed.
2. The electrical subpanel on the north wall of room 1518 was observed at 3:00 p.m. on 10/12/10. The subpanel was not sealed for twelve penetrations through the 2-hour wall between the phone room and the mechanical room.
3. The exit stairwell by the Sterile Processing Department was observed at 10:30 a.m. on 10/13/10. New wiring had been installed in the stairwell for expanded cell phone coverage. The 2-hour wall between the exit corridor and the stairwell had a penetration where the wiring had not been sealed.
4. The room under the Cameron Auditorium was observed at 9:50 a.m. on 10/13/10. There were penetrations through the two hour ceiling in this room exposing wood construction in the interior spaces.
5. The door leading to the tunnels near the south tower was observed at 1:07 p.m. on 10/13/10. The fire wall above the door had two penetrations through it. One was for the sprinkler pipe and the remaining was for a half inch conduit which was not sealed.
18076
6. A 3-hour fire wall had an unsealed penetration around an open ended conduit above the rated double doors, where ER connecting tunnel met the South tower as observed at 1:30 p.m. on 10/13/10.
Tag No.: K0012
Based on observations on October 12-14, 2010, the facility failed to maintain the fire and smoke resistance rating of wall and ceiling assemblies.
Findings included:
1. Room 1202-B (a locked closet) on the exit corridor in the Maintenance department was observed at 1:40 p.m. on 10/12/10.
a) There were three open penetrations in the east wall of this room, and
b) three open penetrations in the west wall of this room.
All were penetrations from where conduits had been removed and the gypsum board had not been properly sealed.
2. Room 1202-A (a locked closet) on the exit corridor in the Maintenance department was observed at 1:55 p.m. on 10/12/10.
a) There were three penetrations in the east wall of this room,
b) There was one penetration in the west wall of this room, and
c) There were two penetrations in the south wall of this room which had not been properly sealed.
3. Room 1805 (a network server room) was observed at 4:00 p.m. on 10/12/10. There were two ceiling tiles missing in this server room.
4. The DuFresne classroom was observed at 4:30 p.m. on 10/12/10. The DaLite screen in this room was installed through a hole in the ceiling tile. There was no sprinkler or smoke detection above the ceiling tile in this room.
5. The Hub room in Medical Records was observed at 7:40 a.m. on 10/13/10. The following deficiencies were found:
a) a ceiling tile was missing, and
b) the wall in this room had a two inch hole.
6. The Audio/Video (AV) storeroom in the Cameron Auditorium was observed at 9:40 a.m. on 10/13/10. The walls and ceiling in this room were not finished and had no rating.
7. The corridor near the Nutrition office was observed at 2:35 p.m. on 10/13/10. One ceiling tile had a two inch penetration at this location.
18076
8. Room 570C had a missing ceiling tile at 4:10 p.m. on 10/12/10 on the 5th floor.
9. Rooms 515A and 515B had several missing ceiling tiles at 4:15 p.m. on 10/12/10 on the 5th floor.
10. Room 393 had two missing ceiling tiles at 3:01 p.m. on 10/12/10 on the 3rd floor.
11. Patient room 10 had a missing ceiling tile at 3:04 p.m. on 10/12/10.
12. The old open heart room had four missing ceiling tiles at 3:06 p.m. on 10/12/10 on the 3rd floor.
13. Elevator #17's lobby ceiling tile had a two inch by four inch hole on the 4th floor (PCU)of the surgical tower.
Tag No.: K0017
Based on observations which were made on October 12-14, 2010, the facility failed to maintain the fire resistive construction of all corridor walls in order that they would be resistant to the passage of smoke. In sprinklered buildings, wall partitions are only required to resist the passage of smoke, 19.3.6.1.
Findings included:
In accordance with Sections 19.3.6.1, 19.3.6.2.1, 19.3.6.5 of NFPA 101, 2000 edition; corridors are separated from use areas by walls constructed with at least ? hour fire resistance rating. In sprinklered buildings, partitions are only required to resist the passage of smoke. In non-sprinklered buildings, walls properly extend above the ceiling. (Corridor walls may terminate at the underside of ceilings where specifically permitted by Code. Charting and clerical stations, waiting areas, dining rooms, and activity spaces may be open to the corridor under certain conditions specified in the Code. Gift shops may be separated from corridors by non-fire rated walls if the gift shop is fully sprinklered.)
The sprinkler chase room 472 on the 4th floor had an unsealed penetration that extended above the room door into exit corridor at 7:41 a.m. on 10/12/10.
Tag No.: K0018
Based on observation made on October 12-14, 2010, the facility failed to ensure that there were no impediments to closing or using a corridor door opening onto the exit corridor system.
Findings included:
Hold-open devices that release when the corridor door is pushed or pulled shall be permitted per Section 19.3.6.3.3 of NFPA 101 LSC, (2000 Edition). However, a hold-open device can not be used on doors in an exit passageway, stairway enclosure, horizontal exit, smoke barrier, fire barrier or hazardous area enclosure unless they conform with Section 7.2.1.8.2 of NFPA 101 LSC, (2000 Edition). Doors cannot be blocked open by furniture, door stops, chocks, wedges, or devices that necessitate manual releasing action to close the door.
The self closure of the Equipment Depot corridor door on the 7th floor had a magnetic hold device that was interfaced with the fire alarm system (opened onto the exit corridor). When exercised, the door closure was inhibited by 4 sets of metal hooks over the door at 1:48 p.m. on 10/12/10. The facility staff removed all but one of the metal hooks and the door would positively latch and close.
Tag No.: K0020
Based on observations made on October 12-14, 2010, the facility failed to assure that vertical openings between floors were sealed and/or enclosed by fire resistive construction.
Findings included:
In accordance with Section 19.3.1.1 of NFPA 101, 2000 Edition, any vertical opening shall be enclosed or protected in accordance with Section 8.2.5 of NFPA 101. Where enclosure is provided, the construction shall have not less than a 1-hour resistance rating.
In accordance with Section 8.3.6.1 of NFPA 101; pipes, conduits, bus ducts, cables, wires, air ducts, pneumatic tubes and ducts, and similar building service equipment that pass through floors and smoke barriers shall be protected/filled with a material that is capable of maintaining the smoke resistance of the smoke barrier.
1. The northwest corner of the Maintenance Shop was observed at 1:35 p.m. on 10/12/10. An electrical box cover was missing on a piece of conduit which extended to the level above.
2. Room 1200 (a mechanical room) in Maintenance was observed at 2:05 p.m. on 10/12/10. A copper pipe above an air-conditioning unit was not sealed as it passed through the ceiling to the level above.
18076
3. An unsealed floor penetration (open end of a two inch conduit) was observed in the north east corner of the Communications room on 8th floor at 12:44 p.m. on 10/12/10.
Tag No.: K0022
Based on observation made on October 12-14, 2010, the facility failed to ensure that all access to exits were properly marked by readily visible signs.
Findings included:
In accordance with Section 7.10.1.2 of the LSC, exits, other than main exterior exit doors that obviously and clearly are identifiable as exits, shall be marked by an approved sign readily visible from any direction of exit access.
1. The DuFresne classroom was observed to be twenty four feet by forty six feet with only one exit to the east, at 4:32 p.m. on 10/12/10. There was another way out of this space to the west but the door did not have an exit sign.
2. The classroom identified as 5-A and 5-B was observed at 4:45 p.m. on 10/12/10. The classroom had an exit sign at the east end of the exit corridor but did not have an exit sign at the west door.
3. The north exit corridor directly behind Registration was observed at 8:20 a.m. on 10/13/10. The exit sign directed one to enter the stairway instead of exiting the outside double doors around the column.
18076
4. The court yard door at the surgery waiting area lacked a NO EXIT sign at 11:32 a.m. on 10/13/10. This enclosed court yard and the secondary door into it leads to a staff meeting lounge on the other side of the court yard.
5. The two exit doors on the west side of the OR core lacked an illuminating exit sign at 10:21 a.m. on 10/13/10.
6. The corridor exit location near the operating room 7 in OR was reviewed. At this juncture, this south stairway was identified as an exit stairway after the smoke barrier doors (interfaced with the fire alarm system). In an emergency event, these double doors would close and the occupants could not see the exit sign on the other side of the doors. There was no exit sign above these smoke barrier doors. Additionally, the exit sign after the smoke barrier doors pointing at the south stairway was not visible to the occupants traveling from the opposite side (north to south).
Tag No.: K0025
Based on observations made on October 12-14, 2010, the facility failed to maintain the fire resistive rating of fire/smoke barrier walls.
Findings included:
In accordance with Section 8.3 of NFPA 101 LSC, 2000 edition; smoke barriers shall be constructed to provide at least a one half hour fire resistance rating. Smoke barriers may terminate at an atrium wall. Windows are protected by fire-rated glazing or by wired glass panels and steel frames. A minimum of two separate compartments are provided on each floor. Dampers are not required in duct penetrations of smoke barriers in fully ducted heating, ventilating, and air conditioning systems in accordance with Sections 19.3.7.3, 19.3.7.5, 19.1.6.3, 19.1.6.4 of NFPA 101, LSC (2000 edition).
1. The smoke barrier wall above the doctor's dictation on the 8th floor had an unsealed penetration around a conduit housing three data cables at 1:15 p.m. on 10/12/10.
2. The smoke barrier wall above the double doors on the West corridor of the 8th floor had an unsealed penetration around fiber communication cables at 1:20 p.m. on 10/12/10.
3. The smoke barrier wall above the double doors on the west corridor of the 7th floor had an unsealed penetration around a conduit housing communication cables at 1:45 p.m. on 10/12/10.
4. The smoke barrier wall above the fire rated double doors near room 369 on the 3rd floor had an unsealed penetration at 2:33 p.m. on 10/12/10. The penetration was unsealed on both sides.
5. The smoke barrier wall above fire rated (90 minute) door at Med-South nurse station on the 3rd floor had an unsealed conduit penetration at 2:36 p.m. on 10/12/10.
6. The smoke barrier wall above the ceiling tiles in cubicle #7 in the old observation area on the 3rd floor had an unsealed penetration around a conduit at 2:38 p.m. on 10/12/10.
7. The smoke barrier wall above the double doors near room 375 outside the old CCU had a penetration around a two inch open ended conduit at 2:53 p.m. on 10/12/10.
8. The smoke barrier wall near room marked 4109 on the 4th floor of the surgical tower had a two inch thick previously sealed penetration that required additional fire rated sealant at 8:50 a.m. on 10/13/10.
Note: All of these penetrations were sealed during the survey after the maintenance department was notified.
Tag No.: K0027
Based on observation and exercising of the doors on October 12-14, 2010, the facility failed to ensure that smoke barrier doors closed tightly to resist the passage of smoke.
Findings included:
1. Elevator lobby doors with fire rating of 90 minutes and with a magnetic hold device were exercised at 8:21 a.m. on 10/13/10 at the north end of the PCU, surgical tower. The doors would not positively latch when released from the magnetic hold device. The doors were exercised several times. The doors were repaired during the course of the survey.
2. The fire rated smoke barrier doors with a magnetic hold device (interfaced with the fire alarm system) near the operating rooms 5 and 6 were blocked by a utility cart in the core of OR. At 10:11 a.m. on 10/13/10, the utility cart was removed by a staff member after being notified, and the doors were released from the magnetic hold device. The doors would not latch positively.
3. The fire rated smoke barrier doors with a magnetic hold device (interfaced with the fire alarm system), located near the operating rooms 6 and 7 in OR, would not positively latch when exercised at 10:15 a.m. on 10/13/10.
4. The fire rated smoke barrier doors with a magnetic hold device (interfaced with the fire alarm system), located near the operating rooms 4 and 5 in OR, would not latch positively when exercised at 10:40 a.m. on 10/13/10.
Tag No.: K0029
Based on observations made on October 12-14, 2010, the facility failed to maintain or establish the fire rated protection for hazardous areas.
Findings included:
In accordance with Section 8.4 of NFPA 101, LSC, 2000 edition; hazardous areas shall be enclosed with a one hour fire-rated barrier, with a 3/4 hour fire-rated door, without windows. Doors to hazardous areas shall be self-closing or automatic closing in accordance with Section 7.2.1.8 and Section 19.3.2.1 of NFPA 101 LSC.
Hazardous areas must be separated from non-hazardous areas with one hour rated wall and ceiling assemblies.
1. The Soiled Laundry room was observed at 10:40 a.m. on 10/13/10. The southeast corner of this room had five conduits which were not sealed, two were pneumatic tubes, two were steam pipes, and the remaining was a smaller conduit.
2. The Boiler room was observed at 11:15 a.m. on 10/13/10.
a) The west wall of the mezzanine in this room had a penetration above the exit door into the second level of the hospital which was an open two inch conduit,
b) The north wall of the boiler room had four penetrations in the brick wall. One was at a brace which extended through the brick wall while one was a loose brick at about the midpoint of the mezzanine. Finally,there were two steam pipes which were not sealed in the northeast corner of the mezzanine.
3. The Chiller room was observed at 11:30 a.m. on 10/13/10. The door between the Chiller room and the Electrical room was not self-closing at the one-hour wall. The door was properly rated for the opening.
4. The enclosed catwalk room above the Electrical room was observed at 11:35 a.m. on 10/13/10. There were two unsealed conduits between the Chiller room and the room above the Electrical room. One was an unsealed two inch conduit and the remaining was a three quarter inch conduit.
5. The north wall of the Chiller room which separates the Chiller room from the Boiler room was observed at 11:45 a.m. on 10/13/10. There were seven penetrations in this wall, six were open conduits, and the remaining was at a brace.
18076
6. The west mechanical room on the 5th floor had an open ended conduit penetrating through the wall by ACH 5-3 at 4:10 p.m. on 10/12/10.
7. Room 391, the mechanical room on the 3rd floor, had an unsealed conduit penetrating through the corridor wall above the room door at 3:02 p.m. on 10/12/10.
Tag No.: K0033
Based on observations made on October 12-14, 2010, all vertical openings such as stair towers are contained with a fire resistant rating.
Findings include:
In accordance with Section 7.1.3.2.1 of NFPA 101, 2000 Edition; where this Code requires an exit to be separated from other parts of the building, the separating construction shall meet the requirements of Section 8.2 and the following.
(a) * The separation shall have not less than a 1-hour fire resistance rating where the exit connects three stories or less.
(b) * The separation shall have not less than a 2-hour fire resistance rating where the exit connects four or more stories. The separation shall be constructed of an assembly of noncombustible or limited-combustible materials and shall be supported by construction having not less than a 2-hour fire resistance rating.
Exception No. 1: In existing non-high-rise buildings, existing exit stair enclosures shall have not less than a 1-hour fire resistance rating.
Exception No. 2: In existing buildings protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7, existing exit stair enclosures shall have not less than a 1-hour fire resistance rating.
1. The second floor level of the northeastern stair tower was observed at 2:01 p.m. on 10/12/10. A horizontal hole was created when piping was removed near room 211/212. The hole was repaired while the surveyor was still in the building.
2. The first floor level of the center stair tower near room 1502C was reviewed on 10/12/10 at 2:10 p.m. Two, three inch holes through the two hour construction of the stair tower were noted. Piping had been removed and the holes left unfilled. The holes were repaired while the surveyor was still in the building.
3. The ground level of the south stair well near room G035 was reviewed on 10/14/10 at 9:15 a.m. There were at least two open penetrations one inch square in size and some unsealed open ended conduits in the 2 hour barrier.
Tag No.: K0038
Based on observations made on October 12-14, 2010, the means of egress was reduced by items stored in the means of egress.
In accordance with Section 7.1.10.1 of NFPA 101, 2000 Edition, means of egress shall be continuously maintained free of all obstructions or impediments to full instant use in the case of fire or other emergency.
Findings include:
1. Outpatient Pediatric Therapy was observed on 10/12/10 at 3:09 p.m. Two exercise mats were found outside the egress door (12533). The mats were water soaked and were taking up approximately 1/3 to 1/4 of the egress path to the public way.
2. The Outpatient Pediatric Therapy corridor, labeled as 1135, was reviewed on 10/12/10. The exit was partially blocked with three items:
a) a gurney,
b) a toddler tricycle, and
c) a chair with wheels.
Note: The tricycle and chair were removed by a member of the staff at the time of survey.
3. The Mother Joseph Room was observed at 8:45 a.m. on 10/13/10. A microphone stand and a cork board (18 inches by 24 inches) were found located in the means of egress from the room near the internal stairs. These items were immediately removed by staff at the time of survey.
Tag No.: K0046
Based on observations and discussions with staff on October 14, 2010, the battery backup emergency lighting systems were not tested as required.
Findings included:
In accordance with NFPA 101 2000 Edition, Section 7.9.3 Periodic Testing of Emergency Lighting Equipment a functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds. An annual test shall be conducted on every required battery-powered emergency lighting system for not less than 11/2 hours. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.
Exception: Self-testing/self-diagnostic, battery-operated emergency lighting equipment that automatically performs a test for not less than 30 seconds and diagnostic routine not less than once every 30 days and indicates failures by a status indicator shall be exempt from the 30-day functional test, provided that a visual inspection is performed at 30-day intervals.
Although emergency lighting is not required in business occupancies such as this facility; NFPA 101, 2000 Edition, states the following in Section 4.6.12.2: "Existing life safety features obvious to the public, if not required by the Code, shall be either maintained or removed."
The battery operated emergency lighting of the facility was reviewed at 9:30 a.m. Staff in the area indicated that the batteries were recently replaced. The facility staff were asked about having the monthly 30 minute test and annual test for the emergency lighting. Upon further investigation, the facility staff could not locate documentation for either the 30 minute or 90 minute test.
Tag No.: K0047
Based on observations made on October 12-14, 2010, exit sign illumination must be maintained and doors that may be considered exits that re-enter the building should contain "No Exit" signs.
Findings include:
1. An exit sign labeled as 12242 was not illuminated in the first floor lab at 2:30 p.m. Attempts to determine if the exit sign self illuminated were not successful.
2. The "Old Lithotripsy Doctor's" office was reviewed at 3:25 p.m. on 10/12/10. The exit light appeared to be illuminated at approximately 1/2 of the exit sign. All letters of the exit sign must be illuminated completely.
In accordance with NFPA 101, 2000 Edition, section 7.10.8.1 No Exit;
any door, passage, or stairway that is neither an exit nor a way of exit access and that is located or arranged so that it is likely to be mistaken for an exit shall be identified by a sign that reads as follows: NO EXIT
Such sign shall have the word NO in letters 2 in. (5 cm) high with a stroke width of 3/8 in. (1 cm) and the word EXIT in letters 1 in. (2.5 cm) high, with the word EXIT below the word NO.
3. The exit near the Lewis & Clark Conference rooms was reviewed on 10/13/10 at 4:25 p.m. The "Old Smoke Room" which can be accessed through the exit vestibule requires that staff re-enter the building to exit. This door to the corridor leading to this room that is inside the vestibule should be labeled as "NO EXIT".
Tag No.: K0051
Based on observations made on 10/13/10, manual fire alarm pull boxes shall be maintained free and clear from obstruction and smoke detectors shall be maintained.
Findings include:
In accordance with NFPA 72, 1999 Edition, Section 2-8.2.1; manual fire alarm boxes shall be located throughout the protected area so that they are unobstructed and accessible.
1. The egress corridor from the Lewis and Clark Conference rooms was reviewed on 10/13/10. A manual fire alarm box was observed to be partially obstructed by a collapsible coat rack. The rack was later moved by staff at the time of survey.
2. The clean side of laundry was reviewed at 9:40 a.m. on 10/13/10. A cart overflowing with bags of laundry in it was blocking access to the manual fire alarm box.
3. The transfer switch room was observed on 10/13/10 at 10:41 a.m. A manual fire alarm box was observed without a cover in the hard lid ceiling.
4. Room G049 was observed on 10/13/10 at 10:57 a.m. The hard lid ceiling installed in the room contained an electrical box for a smoke detector. The smoke detector had been removed and no cover existed on the box.
Tag No.: K0052
Based on observation and staff interview on October 14, 2010, the facility failed to ensure that the location of the dedicated power circuit branch servicing the fire alarm panel was permanently addressed on the alarm panel. Also, the circuit disconnecting means was not identified with a red marking.
Findings included:
In accordance with Section 1-5.2.5.2 of NFPA 72, 1999 edition; the connections to the light and power service for the Fire Alarm Control Panel (FACP) shall be on a dedicated branch circuit(s). The circuit(s) and connections shall be mechanically protected. Circuit disconnecting means shall have a red marking, shall be accessible only to authorized personnel, and shall be identified as FIRE ALARM CIRCUIT CONTROL. The location of the circuit disconnecting means shall be permanently identified at the fire alarm control unit.
The main FACP for the Sletten Cancer Center was observed at 9:00 a.m. on 10/14/10. The FACP panel was labeled as to what electrical panel and breaker controlled it (Panel EG5, Breaker #14), but the circuit disconnecting means was not identified with a red marking.
Tag No.: K0056
Based on observations made on October 12-14, 2010, the facility failed to provide for complete coverage of the building by an approved automatic sprinkler system.
Findings included:
In accordance with Section 19.1.1.3 of the Life Safety Code (LSC), All health care facilities shall be designed, constructed, maintained, and operated to minimize the possibility of a fire emergency requiring the evacuation of occupants. Because the safety of health care occupants cannot be ensured adequately by dependence on evacuation of the building, their protection from fire shall be provided by appropriate arrangement of facilities, adequate staffing, and development of operating and maintenance procedures composed of the following:
(1) Design, construction, and compartmentation
(2) Provision for detection, alarm, and extinguishment
(3) Fire prevention and the planning, training, and drilling programs for the isolation of fire, transfer of occupants to areas of refuge, or evacuation of the building.
1. A closet in Neurodiagnostic Department was observed to be not sprinkled, as observed at 2:30 p.m. on 10/12/10.
2. Elevator #6 by the Neurodiagnostic Department was observed to be hydraulically controlled as observed at 2:35 p.m. on 10/12/10. The elevator pit was not sprinkled.
3. Room 1208-C, under the interior stairway was observed to be not sprinkled at 2:43 p.m. on 10/12/10.
4. The closet on the west wall of Registration/Admissions offices was observed at 8:10 a.m. on 10/13/10. This closet was without sprinkler coverage.
5. The closet enclosing the Automatic Teller Machine (ATM), was found to be non sprinkled as observed at 8:30 a.m. on 10/13/10.
6. The walk-in-cooler labeled C-37 was found to be eight feet by twenty feet and had one sprinkler head which was obstructed by a condenser as observed at 8:45 a.m. on 10/13/10.
7. The Transformer room by the Cameron Auditorium was not sprinkled as observed at 9:45 a.m. on 10/13/10.
8. The tunnels under the ground floor were observed at 1:06 p.m. on 10/13/10. A new section of the tunnel had been opened up by boring through the concrete wall, there were combustible materials in the area and no sprinkler coverage in this eight foot by twelve foot space.
Tag No.: K0062
Based on observation made on October 12-14, 2010, the facility failed to maintain the automatic sprinkler system in accordance with the standards of NFPA 13 and NFPA 25.
Findings included:
In accordance with Section 5-6.6 of NFPA 13 (1999 Edition), the clearance between the deflector of standard pendent and upright spray sprinklers and the top of storage shall be 18 inches or greater.
In accordance with 3-2.7.2 of NFPA 13 (1999 Edition) escutcheon plates used with a recessed or flush-type sprinkler shall be part of a listed sprinkler assembly.
1. Soiled linen storage room 333, on the 3rd floor, had two sprinklers where there an annular space existed between the ceiling tiles and the escutcheon rings as observed at 2:06 p.m. on 10/12/10.
2. The magnetic door hold system components were tied to the sprinkler pipe above room 438 on the 4th floor at 7:30 a.m. on 10/13/10.
3. The sprinkler head in closet 450A (PT reception area closet) was blocked items placed on the top shelf of the closet. As soon as notified, the facility staff removed the items and the top shelf from the closet at 8:07 a.m. on 10/13/10.
4. The sprinkler head in ER room 18 (door marked 117) had a heavy accumulation of dust at 1:55 p.m. on 10/13/10.
5. Several chemical spray bottles were hanging from the sprinkler stand pipe/control valves in room 128, housekeeping in ER at 2:00 p.m. on 10/13/10.
20343
6. Room 1064-B, (a mechanical room), had a sprinkler head recessed into the corridor wall. The room was approximately five feet by five feet. The head was an upright pendant type and should have been a side pendant type for this location.
7. Room 1223 (storeroom for volunteers) had items stored which blocked spray pattern coverage for the room as observed at 2:15 p.m. on 10/12/10.
8. The Morgue walk-in-cooler had one escutcheon ring which was not tight to the ceiling tile as observed at 9:30 a.m. on 10/13/10.
9. The Compactor room had four escutcheon rings missing on the ceiling as observed at 12:40 p.m. on 10/13/10.
10. The South Tower stairwell had one sprinkler head taped over as observed at 12:50 p.m. on 10/13/10.
Tag No.: K0064
Based on observations made on October 12-14, 2010, the facility failed to ensure that portable fire extinguishers were inspected and maintained in accordance with the standards of NFPA 10.
Findings included:
In accordance with 1-6.7 and 1-6.10 of NFPA 10, 1998 Edition, portable extinguishers other than wheeled types shall be securely installed on the hanger or bracket supplied with them or placed in cabinets or wall recesses. In no case shall the clearance between the bottom of the supported extinguisher and the floor be less than 4 inches. Extinguishers weighing less than or equal to 40 lb shall be installed so that the top of the extinguisher is not more than 5 feet above the floor. Those extinguishers with a weight more than 40 lb shall be installed so that the top of the extinguisher is not more than 3 1/2 feet above the floor.
Fire extinguishers shall be hydrostatically tested per 5-2 of NFPA 10, 1998 Edition, at intervals not exceeding those specified in Table 5-2. The hydrostatic retest shall be conducted within the calendar year of the specified test interval. In no case shall an extinguisher be recharged if it is beyond its specified retest date. Dry Chemical extinguishers with mild steel or aluminum shells shall be hydrostatically tested every 12 years. Extinguishers that pass the test shall have the maintenance information recorded on a label securely affixed to the shell showing month and year of the service, the name or initials of the person performing the work and the name of the agency performing the maintenance.
In accordance with Section 4-4.3 of NFPA 10, 1998 Edition; every six years, stored-pressure fire extinguishers that require a hydrostatic test shall be emptied and subjected to the applicable maintenance procedures.
1. A free standing fire extinguisher was observed in the elevator equipment room located on the 5th floor at 4:45 p.m. on 10/12/10.
2. Fire extinguisher 44 located in 4th floor PT was manufactured in 1989. The 1995 date, the first 6-year testing of the device, could not be seen on the extinguisher. The 2001 hydrotesting and 2007 6-year maintenance testings were conducted and the labels were easily seen at 8:05 a.m. on 10/13/10.
20343
3. Air handling room 1088 in Accounting had one portable fire extinguisher which was not on a hanger as observed at 2:10 p.m. on 10/12/10.
4. A 3-A-40-BC portable fire extinguisher in room M-101-A (medical records storeroom) was last hydrotested in July of 2000, and received a six year maintenance test in July of 2007 as observed at 3:25 p.m. on 10/12/10. The six year maintenance should have been conducted in July of 2006 when it expired.
5. A 10-A-60 BC portable fire extinguisher in a wall cabinet in room 1801 received a six year maintenance test in July of 1999, but did not receive a hydotest until July 2006 as observed at 3:28 p.m. on 10/12/10. The hydrotest was due at the end of the sixth year in July of 2005.
6. The portable fire extinguisher (#232) located at GLS 106123, had the hydrotest maintenance sticker directly over the six year maintenance sticker, and one could not track the history for the extinguisher, as observed at 3:55 p.m. on 10/12/10.
Tag No.: K0067
Based on observations made on October 12-14, 2010; the facility failed to maintain the heating, ventilation, and air-conditioning system in accordance with Sections 19.5.2.1, and 9.2.1 of NFPA 101, Life Safety Code (LSC) and NFPA 90A.
Findings included:
In accordance with Section 5-3.1 of NFPA 90A, 1999 Edition; controls related to fan shut down and automatic damper operation shall be tested for compliance with the requirements of this standard.
A fire drill was conducted at 1:30 p.m. on 10/14/10 to check fire and smoke dampers on three floors of the West Campus building. A fire damper in the mechanical room #237 was observed for proper closure. The air handling system failed to shut down properly at this damper location.
Tag No.: K0071
Based on exercise of fire doors protecting gravity linen/trash chutes made on October 12-14, 2010, the facility failed to assure that there is a self-closing door at the discharge opening of the chute in accordance with NFPA 82, 1999 Edition.
In accordance with 3-2.2.9 of NFPA 82 gravity linen/trash chutes shall be protected at the discharge level by an approved automatic-closing or self-closing one-hour fire door suitable for Class B openings.
Findings included:
1. The trash chute room (1213) was observed at 2:20 p.m. on 10/12/10. The sliding door on the chute was not self-closing.
2. The laundry chute in room 1802 was observed at 3:30 p.m. on 10/12/10. The chute door was not self-closing.
3. The trash chute across from Medical Records was observed at 7:50 a.m. on 10/13/10. The chute doors were not self-closing.
4. The laundry chute across from Medical Records was observed at 7:51 a.m. on 10/13/10. The chute doors were not self-closing.
5. The laundry chute by Sterile Processing was observed at 10:20 a.m. on 10/13/10. The chute door was not self-closing, nor was it latched at the time it was observed.
18076
6. The laundry chute door on the south side of ER, with a self closure device (90 minute fire rated), would not positively latch when exercised at 2:11 p.m. on 10/13/10.
Tag No.: K0072
Based on observations made on October 12-14, 2010, the facility failed to ensure that items were not stored or left in the exit corridor system unattended for periods exceeding 30 minutes.
Findings included:
Items not in use in exit corridors (i.e. left unattended for more than 30 minutes), such as linen carts, medication carts, janitorial equipment, chairs, wheelchairs, delivery items and other similar items must be stored properly or removed from the corridor per Centers for Medicare and Medicaid Services Survey and Certification letter 04-41.
The exit corridor next to the Neurodiagnostic Department was observed at 2:22 p.m. on 10/12/10. The cardboard recycling bins were being stored in the exit corridor in this area.
Interview with facility staff regarding the storage in the exit corridor revealed that the bins have always been there.
Tag No.: K0074
Based on observation and interview with maintenance staff made on October 12-14, 2010, the facility failed to provide documentation that curtains in the basement met the Standards of NFPA 13, for flame spread ratings.
Findings included:
In accordance with Section 19.7.5.1 of NFPA 101, 2000 Edition; draperies, curtains, including cubicle curtains, and other loosely hanging fabrics and films serving as furnishings or decorations in health care occupancies shall be in accordance with the provisions of Section 10.3.1 of NFPA 101.
Exception: Curtains at showers.
Room 1225 (Volunteer managers office) was observed at 2:10 p.m. on 10/12/10. There were sheer drapes hanging on the corridor windows to this office. There was no tag attesting that they carried a flame spread rating, nor any documentation that they had been treated with a material which was rated.
Interview with facility staff at a team meeting at 4:45 p.m. on 10/12/10 revealed that possibly the volunteer manager brought the drapes from home and hung them.
Tag No.: K0076
Based on observation made on October 12-14, 2010, the facility failed to ensure that nonflammable gas cylinders were stored in accordance with the standards of NFPA 99.
Findings included:
In accordance with 8-3.1.22.2(h) and 4-3.5.2.1(b27) of NFPA 99 (1999 Edition) freestanding cylinders of nonflammable gases (such as oxygen) shall be properly chained or supported in a cylinder cart or stand or by means of racks or fastenings to protect them from falling over or being knocked down.
In accordance with NFPA 99, Sect. 4-3.1.1.2(a)(4) requires that the electric installation in storage locations or manifold enclosures for nonflammable medical gases shall comply with the standards of NFPA 70, National Electrical Code (NEC), for ordinary locations. Electric wall fixtures, switches, and receptacles shall be installed in fixed locations not less than 152 cm (5 ft) above the floor as a precaution against their physical damage.
1. An "E" size cylinder of oxygen was observed to be unsecured and in upright freestanding position in the ICU near room 5116 on the 5th floor of the surgical tower at 9:25 a.m. on 10/13/10.
2. A carbon dioxide cylinder was observed to be unsecured and in upright freestanding position in the medical gas room, marked 2517, in OR at 10:30 a.m. on 10/13/10. The cylinder was located in front of an electrical outlet approximately 14 inches from the floor.
3. The medical gas storage room door, marked 155B, was impeded by a cylinder rack and could not be closed at 2:13 p.m. on 10/13/10.
Tag No.: K0077
Based on observations made on October 12-14, 2010, the facility did not appropriately label a medical gas shut off valve as to its use.
Findings included:
In accordance with 4-3.5.4.2 of NFPA 99 (1999 Edition) shutoff valves for medical gases shall be labeled to reflect the rooms that are controlled by such valves.
1. The medical gas shutoff valve panel near room #6 in OR lacked labeling to address the rooms that it served at 10:21 a.m. on 10/13/10.
2. The medical gas shutoff valve panel near room #5 in OR lacked labeling to address the rooms that it served at 10:41 a.m. on 10/13/10.
Tag No.: K0145
Based on observations made on October 12 -14, 2010; the facility failed to properly designate the branch functions of each automatic transfer switch.
The findings include:
Type I essential electrical systems are comprised of two separate systems, being the emergency system and the equipment system per section 3-4.2.2.1 of NFPA 99, 1999 edition. The emergency system shall be limited to circuits essential to life safety and critical patient care. These are designated the life safety branch and the critical branch. The number of transfer switches to be used shall be based upon reliability, design, and load considerations. Each branch of the emergency system and each equipment system shall have one or more transfer switches. One transfer switch shall be permitted to serve one or more branches or systems in a facility with a maximum demand on the essential electrical system of 150 kVA (120 kW).
The multiple transfer switches in electrical room G105F were examined at 10:40 a.m. on 10/13/10. Several transfer switches were housed in the room with the following numbers on them: 10-M3-084-0, 10-M3-085-0, 10-M3-086-0, 10-M3-087-0, 10-M3-088-0. There was no designation on any of the transfer switch denoting whether that particular switch served the emergency (life safety and critical functions) branch, the equipment branch or if the systems had been further isolated into separate Life Safety and Critical branches.
Tag No.: K0147
Based on observations made on October 12-14, 2010, the facility failed to maintain the electrical system and/or its components in accordance with the standards of NFPA 70, 1999 Edition or interpretations from the Centers for Medicare and Medicaid Services (CMS).
Findings included:
Extension cords (including power strips) or multiple adaptors used in health care shall be protected against overcurrent conditions by means acceptable to the National Electrical Code or the Authority Having Jurisdiction (CMS), one means of which is by providing power strips or multiple adaptors that have built-in circuit breakers with either 15 or 20 ampere ratings per Article 240-4 of NFPA 70; and Sections 7-5.1.2.6 and 7-6.2.1.5 of NFPA 99; and previous interpretations from CMS. The limited use of circuit breaker protected power strips is acceptable by CMS provided that no major appliances such as air conditioners, refrigerators, microwaves, heating units and oxygen concentrators are connected to a power strip. These items must be directly connected to an appropriate receptacle.
According to NFPA 70 Article 110-26, sufficient working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. Area required is three feet deep in front of equipment and 30 inches wide or the width of the equipment from live parts is required to be maintained if exposed. Distances shall be measured from the live parts if such are exposed or from the enclosure front or opening if such are enclosed.
1. A microwave was plugged into a surge protector in room 843, a staff kitchen as observed at 12:50 p.m. on 10/12/10 on the 8th floor. As soon as notified, the facility staff unplugged and removed the microwave from this location.
2. The electrical panel in room 393 on the 3rd floor was blocked by a clothes rack and furniture. As soon as notified, the facility staff removed the items blocking electrical panel OBL.
3. The Chief Risk Officer's office in Risk Management was observed at 1:35 p.m. on 10/12/10. Surge cords were found in series under one desk.
Note: One surge cord was removed from the location and the deficiency was corrected at the time of the survey process.
4. The Mercy Flight Dispatch room was observed at 1:40 p.m. on 10/12/10. A microwave and a small refrigerator were plugged into a surge cord.
5. The Map room was observed at 1:55 p.m. on 10/12/10. There were two APC units in use with surge cords plugged into them in series.
6. Room 1227 (air handling room) was observed at 2:08 p.m. on 10/12/10. One electrical box was found without its cover.
7. Room 1229 was observed at 2:50 p.m. on 10/12/10. Surge cords were found in series along the east and west walls.
8. Room 1801 was observed at 3:27 p.m. on 10/12/10. Three surge cords were found in series in this room.
9. The Patient Advocate office was observed at 7:35 a.m. on 10/13/10. There were two surge cords in series under a desk.
10. Medical Records break room was observed at 7:45 a.m. on 10/13/10. A microwave oven and refrigerator were plugged into a surge cord.
11. Room 1003 in Patient Registration was observed at 8:00 a.m. on 10/13/10. The Lexmark copier was plugged into an extension cord.
12. The Kitchen Chef's office was observed at 8:50 a.m. on 10/13/10. A surge cord was not flat on the floor or affixed to the wall, but dangling on the weight of the cord.
13. The Chief Clinical Officer's desk in Administration was observed at 9:55 a.m. on 10/13/10. There was an extension cord in use in this area.
18076
14. Breakers marked 40-42 were in on positions in the electrical panel L-OR1 in the operating room #1 at 10:09 a.m. on 10/13/10, however, they were marked as "spare" on the panel directory.
15. The warmer and the blood bank refrigeration units were plugged into a surge protector in the pump room in OR at 10:10 a.m. on 10/13/10.
16. A refrigerator was plugged into a surge protector in Am Admit/OR offices at 11:25 a.m. on 10/13/10.
17. A refrigerator was plugged into a surge protector in the OR staff lounge at 11:34 a.m. on 10/13/10.
18. Two toasters were plugged into an extension cord, then the extension cord was plugged into a surge protector in the OR staff lounge at 11:36 a.m. on 10/13/10.
19. The circuit breaker 41 in electrical panel ER 1C1L was in on position and marked as spare in the panel directory in ER at 1:47 p.m. on 10/13/10.
20. The receptacle with exposed electrical wires in the OR CT support equipment room, 211, had a missing cover at 1:43 p.m. on 10/13/10.
21. A refrigerator was plugged into a surge protector near the south exit of Laboratory on the second floor at 3:30 p.m. on 10/13/10.
22. A receptacle with exposed electrical wires in Pharmacy Informations, 2008, has a missing cover at 3:40 p.m. on 10/13/10.
23. Circuit breakers 6-12 were in the on position in panel L in the robot packaging room in Pharmacy. The panel directory was blank corresponding to these breakers.
Tag No.: K0154
Based on observation and interview with staff on October 12-14, 2010; the facility failed to notify proper authorities when the fire sprinkler system was out of service for more than 4 hours in a 24 hour period.
Findings include:
While touring the facility for life safety code compliance, facility staff indicated that various areas were under construction on the ground level. While in room G106 where construction staging was being done, it was noted that the facility had several ceiling tiles out of place. From discussion with staff, the construction project ran for 8 to 10 hours a day and then security would conduct fire watch on off hours. This fire watch was not report to the authority having jurisdiction at 406-444-4170 as is required.