HospitalInspections.org

Bringing transparency to federal inspections

116 WEST THIGPEN AVENUE

LAKELAND, GA 31635

No Description Available

Tag No.: K0011

Based on observation and interview with facility staff , the facility failed to maintain 1 of 2 two hour barriers that separate nonconforming buildings from the hospital. In the event of a fire all 25 residents may be affected.

Findings Include:

On 01-16-2013 at approximately 11:45 a.m. observation revealed sheathing missing from the 2 hour barrier at the administration office.

Staff member M confirmed the findings at the time of discovery.

No Description Available

Tag No.: K0056

Based on observation and interview with facility staff the facility failed to ensure sprinkler piping is not used to support items in the attic. In the event of sprinkler failure all 25 residents may be affected.

Findings Include:

On 01-16-2013 at approximately 12:00 p.m. observation revealed low voltage cables are supported by the sprinkler piping in the attic.

Staff member M confirmed the findings at the time of discovery.