HospitalInspections.org

Bringing transparency to federal inspections

200 STADIUM DRIVE

SEYMOUR, TX 76380

No Description Available

Tag No.: K0014

Based on record review on the afternoon of 10/27/2010, documentation was not available to substantiate the new material installed on the lower part of the corridor walls has a Class A, Class B, or Class C interior finish.

No Description Available

Tag No.: K0018

Based on observation during the afternoon of 10/27/2010, the corridor doors to patient sleeping rooms have roller latches. Each roller latch must be replaced with postive latching hardware that engages automatically when the door is closed.

No Description Available

Tag No.: K0038

Based on observation during the aftrnoon of 10/27/2010, The exit access was obstructed by the exercise parallel bars located in the exit corridor near rooms 20 and 21.

No Description Available

Tag No.: K0045

Based on observation during the afternoon of 10/27/2010, all of the light fixtures in the egress corridors could be switched off at the switches located on the corridor walls. A minimum of one foot-candle of illumination must be provided in the egress corridors which cannot be switched off.