HospitalInspections.org

Bringing transparency to federal inspections

1140 N STATE STREET

SAINT IGNACE, MI 49781

No Description Available

Tag No.: K0011

Based on observation it was determined that the facility did not maintain the required minimum 2-hour fire resistance rating of the separation wall to the adjacent non-conforming building in accordance with the LSC, sections 1.1.4.1, 19.1.1.4.2. This deficient practice could affect all occupants in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly fire separation.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:10 PM observed that building construction type and wall construction separation documents were not available for review to verify proper separation between any required areas in the facility, including proper separation between floors.

No Description Available

Tag No.: K0011

Based on observation it was determined that the facility did not maintain the required minimum 2-hour fire resistance rating of the separation wall to the adjacent non-conforming building in accordance with the LSC, sections 18.1.1.4.1, 18.1.1.4.2. This deficient practice could affect all occupants of the facility in the event of a fire where the products of combustion are allowed to transmit through the 2-hour separation wall.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:30 AM observed that at the Shell Space east wall near the north door there was a communications conduit that did not contain any fire stopping material.
- At approximately 10:31 PM observed that at the Shell Space north wall there was a communications conduit that did not contain any fire stopping material.
- At approximately 11:15 AM observed that above the barrier doors across from Medical Records there was a large diameter conduit that was not properly sealed due to fire caulking falling out of the conduit.
- At approximately 11:15 AM observed that above the barrier doors across from Medical Records there was a gray wire causing a penetration in the wall, and the penetration contained no fire stopping material.
- At approximately 11:40 AM observed that in the 2 hr fire barrier near Patient Room 201 there were two communication sleeves that did not contain any fire stopping material.
- At approximately 11:42 AM observed that in the north 2 hr wall near the elevator lobby there was a conduit that contained no fire stopping material around or inside the conduit.
- At approximately 11:45 AM observed that in the 2 hr fire barrier above the 1st floor barrier doors near Room 1027 there were four 3 inch communication sleeves that did not contain any fire stopping material.

No Description Available

Tag No.: K0012

Based on observation it was determined that the facility does not meet the construction type in accordance with the LSC, sections 19.1.6.2, 19.1.6.3, 19.1.6.4, 19.3.5.1, 4.6.6, 4.6.7, 4.6.9, 4.6.10. This deficient practice could affect all occupants of the facility in the event of a fire which is allowed to more rapidly develop due to improper construction type and height.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:10 PM observed that building construction type documents were not available for review at the time of inspection to verify proper construction type and height.

No Description Available

Tag No.: K0014

Based on observation and review of records the facility failed to provide approved interior finish materials in accordance with the LSC sections 19.3.3.1, 19.3.3.2. This deficient practice could affect all occupants within the smoke compartment in the event of a fire which is allowed to more rapidly develop due to improper interior finishes.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 04:30 PM observed that interior finish documents were not available for review.

No Description Available

Tag No.: K0015

Based on observation and review of records the facility failed to provide minimum interior finish materials in accordance with the LSC sections 19.3.3.1, 19.3.3.2. This deficient practice could affect all occupants within the smoke compartment in the event of a fire which is allowed to more rapidly develop due to improper interior finishes.


Findings include:

On 07/07/10, the following observations were made:

- At approximately 04:30 PM observed that interior finish documents were not available for review at the time of inspection.

No Description Available

Tag No.: K0018

Based on observation the facility failed to provide corridor doors that would close and resist the passage of smoke in accordance with the LSC section 18.3.6.3.6. This deficient practice could affect all occupants of the smoke compartment in the event of a fire in one of the rooms with improperly installed or maintained corridor doors.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:45 AM observed that Patient Room R211 does not close to a positive latch.

No Description Available

Tag No.: K0020

Based on observation the facility failed to provide 1-hour fire resistive separation for the vertical openings in accordance with the LSC section 19.3.1.1. This deficient practice could affect all occupants in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly fire separation.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that construction type of stairways could not be verified at the time of inspection.

No Description Available

Tag No.: K0023

Based on observation and review of records the facility failed to provide smoke compartments in accordance with the LSC sections 19.3.7.1, 19.3.7.2. This deficient practice could affect all occupants of the facility in the event of a fire where a sufficient number of smoke compartments may not be available to provide refuge to protect them from the products of combustion.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that locations of any smoke barriers could not be verified at the time of inspection.

No Description Available

Tag No.: K0024

Based on observation and review of records the facility failed to provide smoke compartments in accordance with the LSC section 19.3.7.1. This deficient practice could affect all occupants of the facility in the event of a fire where smoke compartment size and travel distance are too great which may result in ineffective protection from the products of combustion.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that locations of any smoke barriers could not be verified at the time of inspection.

No Description Available

Tag No.: K0025

Based on observation and review of records the facility failed to provide smoke barriers that would provide at least a one half hour fire resistance rating in accordance with the LSC sections 19.3.7.3, 19.3.7.5, 19.1.6.3, 19.1.6.4. This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly located smoke barrier walls.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that locations of any smoke barriers could not be verified at the time of inspection.

No Description Available

Tag No.: K0025

Based on observation the facility failed to provide smoke barriers that would provide at least a one hour fire resistance rating in accordance with the LSC sections 18.3.7.3, 18.3.7.5, 18.1.6.3. This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly sealed penetrations.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 11:20 AM observed that on the 2nd floor above the smoke barrier doors located near Patient Room 212 there was a green colored strut that was penetrating the wall and sealed with drywall tape & mud instead of fire stopping material.
- At approximately 11:22 AM observed that above the smoke barrier doors located near Patient Room 212 there were water pipes that were sealed with drywall tape and mud instead of fire stopping material.

No Description Available

Tag No.: K0026

Based on observation and review of records the facility failed to provide smoke compartments in accordance with the LSC section 19.3.7.4. This deficient practice could affect all occupants of the facility in the event of a fire where adequate space is not provided to accomodate occupants to protect them from the products of combustion.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that locations of any smoke barriers could not be verified at the time of inspection.

No Description Available

Tag No.: K0027

Based on observation and review of records the facility failed to provide for the smoke barrier doors to be self-closing or automatic closing in accordance with the LSC section 19.2.2.2.6. This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly maintained doors.
Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that location of smoke barrier walls could not be verified at the time of inspection, resulting in not being able to verify location of door openings in smoke barriers.

No Description Available

Tag No.: K0027

Based on observation the facility failed to provide for the smoke barrier doors to be self-closing or automatic closing in accordance with the LSC section 18.3.7.5, 18.3.7.6, 18.3.7.8. This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly maintained doors.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:41 AM observed that on the 2nd floor the smoke barrier doors located near Patient Room 212 did not come to a complete close.
- At approximately 10:50 PM observed that on the 2nd floor the smoke barrier doors located near Patient Room 203 did not come to a complete close.
- At approximately 11:50 observed that the smoke barrier doors near Janitor Closet #1027 when closed had a gap of approximately 1/2 inch.

No Description Available

Tag No.: K0028

Based on observation and review of records the facility failed to provide smoke barriers in accordance with the LSC sections 19.3.7.5, 19.3.7.7. This deficient practice could affect all occupants in smoke compartments in the event of a fire where the exiting from the smoke compartment is delayed due to improperly sized doors.

Findings include:

- At approximately 03:20 PM observed that location of smoke barrier walls could not be verified at the time of inspection, resulting in not being able to verify location of door openings in smoke barriers.

No Description Available

Tag No.: K0029

Based on observation the facility failed to provide for the protection of hazardous areas in accordance with the LSC section 18.3.2.1. This deficient practice could affect an undetermined number of occupants in the event of a fire within the hazardous area enclosure where the products of combustion are allowed to spread to the means of egress due to improperly installed or maintained hazardous room enclosures.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:40 AM observed that on the 2nd floor Clean Linen Room 2165 door does not auto close to a positive latch.
- At approximately 11:30 AM observed that on the 2nd floor above the ceiling at Storage Room 2152 there was a penetration to the right side of the duct work caused by drywall being improperly cut and not sealed.
- At approximately 11:30 AM observed that on the 2nd floor above the ceiling at Storage Room 2152 there was a penetration to the left side of the duct work caused by a fire alarm conduit that was not sealed with a fire rated material.
- At approximately 11:47 AM observed that on the 1st floor the Equipment Storage Room 1329 door was held in the open position with a bungee cord.
- At approximately 12:18 PM observed that on the 1st floor Soiled Utility Room 1323 door would not auto close to a positive latch.

No Description Available

Tag No.: K0029

Based on observation the facility failed to provide for the protection of hazardous areas in accordance with the LSC section 19.3.2.1. This deficient practice could affect all occupants of the facility in the event of a fire within the hazardous area enclosure where the products of combustion are allowed to spread to the means of egress due to improperly installed or maintained hazardous area separation.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:15 PM observed there was a rolling door separating the Ambulance Bay/Storage Area from the ER Area. This door operation is not activated by smoke detection as required.
- At approximately 03:25 PM observed that the Janitor's Closet door would not close to a positive latch due to the latching mechanism being secured with tape.
- At approximately 03:27 PM observed that the Lab door was being held in the open position by a foot operated device.
- At approximately 03:28 PM observed that the Soiled Linen Room door does not auto close to a positive latch.
- At approximately 03:30 PM observed that the 2nd floor telephone room had 2 pipe chases in the floor that were filled with an insulation type material that was not fire rated.
- At approximately 3:30 PM observed that the 2nd floor telephone room had 4 conduit chases in the ceiling that were filled with an insulation type material that was not fire rated.
- At approximately 03:40 PM observed that the Contractor's Room door was not equipped with a self-closing device.

No Description Available

Tag No.: K0033

Based on observation the facility failed to provide the required one-hour fire resistance rating for the exit components in accordance with the LSC section 8.2.5.2, 19.3.11. This deficient practice could affect all occupants of the facility in the event of a fire where the products of combustion are allowed to transmit throughout the building due to improperly latching door.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:35 PM observed that on the 2nd floor the North Stairwell door did not close to a positive latch.

No Description Available

Tag No.: K0034

Based on observation the facility failed to provide approved means of egress in accordance with the LSC section 18.2.2.4. This deficient practice could affect all building occupants in the event of an emergency where the rapid evacuation of the facility is necessary, but is delayed due to improperly maintained means of egress.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:50 AM observed that the South Stairwell contained an exhaust duct, domestic water lines, and medical gas lines that were passing through the stairwell and do not serve the stairwell.

No Description Available

Tag No.: K0034

Based on observation the facility failed to provide approved means of egress in accordance with the LSC section 19.2.2.3, 19.2.2.4. This deficient practice could affect all building occupants in the event of an emergency where the rapid evacuation of the facility is necessary, but is delayed due to improperly maintained means of egress.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:35 PM observed that there was combustible storage in the South Stairwell.

No Description Available

Tag No.: K0038

Based on observation the facility failed to provide approved exit access in accordance with the LSC section 19.2.1. This deficient practice could affect all building occupants in the event of an emergency where the rapid evacuation of the facility is necessary, but is delayed due to improperly maintained means of egress.


Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:36 PM observed that the 2nd floor North Stairwell exterior exit does not provide a hard path to the public way.

No Description Available

Tag No.: K0047

Based on observation the facility failed to provide exit and directional signs in accordance with the LSC section 18.2.10.1. This deficient practice could affect all building occupants in the event of an emergency where the rapid evacuation of the facility is necessary, but is delayed due to improperly located/maintained marking of the means of egress.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 12:30 PM observed that there was an "Exit" sign leading occupants into the Ambulance Bay, a hazardous area.
- At approximately 12:43 PM observed that the monthly "Exit" sign maintenance records were not available for review at the time of inspection.

No Description Available

Tag No.: K0048

Based on observation and review of records the facility failed to provide an approved written emergency plan in accordance with the LSC section 18.7.1.1. This deficient practice could potentially affect all occupants of the facility in the event of a fire which requires containment of the fire and/or the rapid evacuation of the building, and the containment and/or evacuation is delayed due to an improper emergency plan.
.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:50 AM observed that the Fire Emergency Plan located at the Acute Care Nurses Station had not been revised for the new facility.

No Description Available

Tag No.: K0050

Based on review of records the facility failed to provide written documentation regarding fire drills in accordance with the LSC section 19.7.1.2. This deficient practice could potentially affect all occupants of the facility if staff are not properly trained in approved emergency procedures.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 04:00 PM observed that fire drill records were not available for review at the time of inspection.

No Description Available

Tag No.: K0052

Based on observation the facility failed to provide a fire alarm system in accordance with the LSC section 9.6.1.4. This deficient practice could affect all building occupants in the event of a delay in occupant notification due to improperly maintained fire alarm system components.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:40 PM observed that in the Contractor's Room there was a fire alarm system strobe device not attached to wall and was hanging by its wiring.

No Description Available

Tag No.: K0052

Based on observation the facility failed to provide a fire alarm system in accordance with the LSC section 9.6.1.4. This deficient practice could affect all occupants of the affected smoke compartment in the event of a delay in occupant notification due to improperly maintained fire alarm system components.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 11:55 AM observed that in CT Room 1407 Restroom the fire alarm visual notification device was covered by a dust cover.

No Description Available

Tag No.: K0054

Based on observation the facility failed to provide and/or maintain smoke detection devices in accordance with the LSC section 9.6.1.3. This deficient practice could affect all building occupants in the event of a delay in occupant notification due to improperly maintained smoke detectors.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 12:18 PM observed that in Soiled Utility Room 1323 there was a smoke detector that was covered with a dust cover.

No Description Available

Tag No.: K0054

Based on observation the facility failed to provide and/or maintain smoke detection devices in accordance with the LSC section 9.6.1.3. This deficient practice could affect all building occupants in the event of a delay in occupant notification due to improperly spaced fire alarm system components.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:37 PM observed that at the 2nd floor Elevator Lobby there was a ceiling mounted smoke detector installed within 3 feet of a HVAC opening.

No Description Available

Tag No.: K0056

Based on observation and review of records the facility failed to provide and/or maintain a sprinkler system in accordance with the LSC section 18.3.5. This deficient practice could affect all building occupants in the event of a delay in occupant notification due to improperly maintained fire sprinkler system components.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:30 AM observed that the 2nd floor Shell Space ceiling tile was not intact, resulting in the sprinkler heads being greater than 12 inches below the ceiling.
- At approximately 12:40 PM observed by review of records that the sprinkler system gauges and control valves inspection records were not available for review at the time of inspection.

No Description Available

Tag No.: K0056

Based on observation the facility failed to provide and/or maintain a sprinkler system in accordance with the LSC section 19.3.5, NFPA 13 Section 5-7.4.1. This deficient practice could affect all building occupants in the event of a fire where the early suppression of the fire does not occur due to the improperly installed fire sprinkler system.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:40 PM observed that in the Contractor's room the sprinkler heads were installed greater than 6 inches from the ceiling.

No Description Available

Tag No.: K0064

Based on observation and review of records the facility failed to provide fire extinguishers in accordance with the LSC section 18.3.5.6. This deficient practice could affect all building occupants in the event of a fire which cannot be controlled due to improper maintenance of the portable fire extinguishers.

Finding include:

On 07/07/10, the following observations were made:

- At approximately 12:25 PM observed that monthly maintenance records for the Ambulance Bay portable fire extinguisher were not available for review at the time of inspection.
- At approximately 12:32 PM observed that monthly maintenance records for the Physical Therapy portable fire extinguisher was not available for review at the time of inspection.

No Description Available

Tag No.: K0064

Based on observation and review of records the facility failed to provide fire extinguishers in accordance with the LSC section 19.3.5.6. This deficient practice could affect all building occupants in the event of a fire where the early suppression of the fire does not occur due to improperly maintained fire extinguishers.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:10 PM observed that portable fire extinguisher monthly inspection records were not available for review at the time of inspection.
- At approximately 03:20 PM observed that the ER Storage fire extinguisher service tag indicated that the most recent annual service was conducted in June/2008.

No Description Available

Tag No.: K0074

Based on observation and review of records the facility failed to provide furnishing flammability documentation in accordance with provisions of the LSC section 10.3.1 and NFPA 13, Standards for the Installation of Sprinkler Systems. Newly introduced upholstered furniture within health care occupancies meets the criteria specified when tested in accordance with the methods cited in 10.3.2 (2) and 10.3.3. 19.7.5.1, NFPA 13

Newly introduced mattresses meet the criteria specified when tested in accordance with the method cited in 10.3.2 (3) , 10.3.4. 19.7.5.3

This deficient practice could affect all occupants within the facility in the event of a fire which is allowed to more rapidly develop due to improper flammable character of furnishings.


Findings include:

- At approximately 03:45 PM observed that the furnishing flammability documents were not available for review at the time of inspection.

No Description Available

Tag No.: K0076

Based on observation the facility failed to provide protection of medical gasses in accordance with NFPA 99. This deficient practice could affect all occupants of the facility in the event of a fire where the improperly stored oxygen contributes to the rate of fire growth.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:22 PM observed that in ER Storage there were unsecured oxygen cylinders.

No Description Available

Tag No.: K0076

Based on observation the facility failed to provide protection of medical gasses in accordance with NFPA 99. This deficient practice could affect all occupants of the affected smoke compartments in the event of a fire where the improperly stored oxygen contributes to the rate of fire growth.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 11:00 AM observed that in Clean Supply Room 2114 there were portable oxygen cylinders stored within 5 feet of combustible storage.
- At approximately 11:00 AM observed that in Clean Supply Room 2114 there were portable oxygen cylinders stored and not separated by full and empty.
- At approximately 11:00 AM observed that in Clean Supply Room 2114 there was an unsecured portable oxygen bottle.
- At approximately 11:08 AM observed that in Storage Room 2175 there were unsecured portable oxygen cylinders.

No Description Available

Tag No.: K0104

Based on observation and review of records the facility failed to provide smoke dampers in accordance with the LSC section 8.3.5. . This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly maintained duct penetrations.

Findings include:

- At approximately 03:20 PM observed that location of smoke barrier walls could not be verified at the time of inspection, resulting in not being able to verify necessity of duct penetration protection.

No Description Available

Tag No.: K0147

Based on observation the facility failed to maintain the electrical system in accordance with the LSC section 9.1.2. This deficient practice could affect all occupants of the facility in the event of a failure of the electrical equipment, or the exposure to hazardous electrical currents due to improper protection.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:25 PM observed that in the Radiology Storage area there was exposed electrical wiring above the ceiling.

LIFE SAFETY CODE STANDARD

Tag No.: K0011

Based on observation it was determined that the facility did not maintain the required minimum 2-hour fire resistance rating of the separation wall to the adjacent non-conforming building in accordance with the LSC, sections 1.1.4.1, 19.1.1.4.2. This deficient practice could affect all occupants in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly fire separation.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:10 PM observed that building construction type and wall construction separation documents were not available for review to verify proper separation between any required areas in the facility, including proper separation between floors.

LIFE SAFETY CODE STANDARD

Tag No.: K0011

Based on observation it was determined that the facility did not maintain the required minimum 2-hour fire resistance rating of the separation wall to the adjacent non-conforming building in accordance with the LSC, sections 18.1.1.4.1, 18.1.1.4.2. This deficient practice could affect all occupants of the facility in the event of a fire where the products of combustion are allowed to transmit through the 2-hour separation wall.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:30 AM observed that at the Shell Space east wall near the north door there was a communications conduit that did not contain any fire stopping material.
- At approximately 10:31 PM observed that at the Shell Space north wall there was a communications conduit that did not contain any fire stopping material.
- At approximately 11:15 AM observed that above the barrier doors across from Medical Records there was a large diameter conduit that was not properly sealed due to fire caulking falling out of the conduit.
- At approximately 11:15 AM observed that above the barrier doors across from Medical Records there was a gray wire causing a penetration in the wall, and the penetration contained no fire stopping material.
- At approximately 11:40 AM observed that in the 2 hr fire barrier near Patient Room 201 there were two communication sleeves that did not contain any fire stopping material.
- At approximately 11:42 AM observed that in the north 2 hr wall near the elevator lobby there was a conduit that contained no fire stopping material around or inside the conduit.
- At approximately 11:45 AM observed that in the 2 hr fire barrier above the 1st floor barrier doors near Room 1027 there were four 3 inch communication sleeves that did not contain any fire stopping material.

LIFE SAFETY CODE STANDARD

Tag No.: K0012

Based on observation it was determined that the facility does not meet the construction type in accordance with the LSC, sections 19.1.6.2, 19.1.6.3, 19.1.6.4, 19.3.5.1, 4.6.6, 4.6.7, 4.6.9, 4.6.10. This deficient practice could affect all occupants of the facility in the event of a fire which is allowed to more rapidly develop due to improper construction type and height.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:10 PM observed that building construction type documents were not available for review at the time of inspection to verify proper construction type and height.

LIFE SAFETY CODE STANDARD

Tag No.: K0014

Based on observation and review of records the facility failed to provide approved interior finish materials in accordance with the LSC sections 19.3.3.1, 19.3.3.2. This deficient practice could affect all occupants within the smoke compartment in the event of a fire which is allowed to more rapidly develop due to improper interior finishes.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 04:30 PM observed that interior finish documents were not available for review.

LIFE SAFETY CODE STANDARD

Tag No.: K0015

Based on observation and review of records the facility failed to provide minimum interior finish materials in accordance with the LSC sections 19.3.3.1, 19.3.3.2. This deficient practice could affect all occupants within the smoke compartment in the event of a fire which is allowed to more rapidly develop due to improper interior finishes.


Findings include:

On 07/07/10, the following observations were made:

- At approximately 04:30 PM observed that interior finish documents were not available for review at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observation the facility failed to provide corridor doors that would close and resist the passage of smoke in accordance with the LSC section 18.3.6.3.6. This deficient practice could affect all occupants of the smoke compartment in the event of a fire in one of the rooms with improperly installed or maintained corridor doors.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:45 AM observed that Patient Room R211 does not close to a positive latch.

LIFE SAFETY CODE STANDARD

Tag No.: K0020

Based on observation the facility failed to provide 1-hour fire resistive separation for the vertical openings in accordance with the LSC section 19.3.1.1. This deficient practice could affect all occupants in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly fire separation.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that construction type of stairways could not be verified at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0023

Based on observation and review of records the facility failed to provide smoke compartments in accordance with the LSC sections 19.3.7.1, 19.3.7.2. This deficient practice could affect all occupants of the facility in the event of a fire where a sufficient number of smoke compartments may not be available to provide refuge to protect them from the products of combustion.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that locations of any smoke barriers could not be verified at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0024

Based on observation and review of records the facility failed to provide smoke compartments in accordance with the LSC section 19.3.7.1. This deficient practice could affect all occupants of the facility in the event of a fire where smoke compartment size and travel distance are too great which may result in ineffective protection from the products of combustion.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that locations of any smoke barriers could not be verified at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0025

Based on observation and review of records the facility failed to provide smoke barriers that would provide at least a one half hour fire resistance rating in accordance with the LSC sections 19.3.7.3, 19.3.7.5, 19.1.6.3, 19.1.6.4. This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly located smoke barrier walls.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that locations of any smoke barriers could not be verified at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0025

Based on observation the facility failed to provide smoke barriers that would provide at least a one hour fire resistance rating in accordance with the LSC sections 18.3.7.3, 18.3.7.5, 18.1.6.3. This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly sealed penetrations.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 11:20 AM observed that on the 2nd floor above the smoke barrier doors located near Patient Room 212 there was a green colored strut that was penetrating the wall and sealed with drywall tape & mud instead of fire stopping material.
- At approximately 11:22 AM observed that above the smoke barrier doors located near Patient Room 212 there were water pipes that were sealed with drywall tape and mud instead of fire stopping material.

LIFE SAFETY CODE STANDARD

Tag No.: K0026

Based on observation and review of records the facility failed to provide smoke compartments in accordance with the LSC section 19.3.7.4. This deficient practice could affect all occupants of the facility in the event of a fire where adequate space is not provided to accomodate occupants to protect them from the products of combustion.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that locations of any smoke barriers could not be verified at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0027

Based on observation and review of records the facility failed to provide for the smoke barrier doors to be self-closing or automatic closing in accordance with the LSC section 19.2.2.2.6. This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly maintained doors.
Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:20 PM observed that location of smoke barrier walls could not be verified at the time of inspection, resulting in not being able to verify location of door openings in smoke barriers.

LIFE SAFETY CODE STANDARD

Tag No.: K0027

Based on observation the facility failed to provide for the smoke barrier doors to be self-closing or automatic closing in accordance with the LSC section 18.3.7.5, 18.3.7.6, 18.3.7.8. This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly maintained doors.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:41 AM observed that on the 2nd floor the smoke barrier doors located near Patient Room 212 did not come to a complete close.
- At approximately 10:50 PM observed that on the 2nd floor the smoke barrier doors located near Patient Room 203 did not come to a complete close.
- At approximately 11:50 observed that the smoke barrier doors near Janitor Closet #1027 when closed had a gap of approximately 1/2 inch.

LIFE SAFETY CODE STANDARD

Tag No.: K0028

Based on observation and review of records the facility failed to provide smoke barriers in accordance with the LSC sections 19.3.7.5, 19.3.7.7. This deficient practice could affect all occupants in smoke compartments in the event of a fire where the exiting from the smoke compartment is delayed due to improperly sized doors.

Findings include:

- At approximately 03:20 PM observed that location of smoke barrier walls could not be verified at the time of inspection, resulting in not being able to verify location of door openings in smoke barriers.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on observation the facility failed to provide for the protection of hazardous areas in accordance with the LSC section 18.3.2.1. This deficient practice could affect an undetermined number of occupants in the event of a fire within the hazardous area enclosure where the products of combustion are allowed to spread to the means of egress due to improperly installed or maintained hazardous room enclosures.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:40 AM observed that on the 2nd floor Clean Linen Room 2165 door does not auto close to a positive latch.
- At approximately 11:30 AM observed that on the 2nd floor above the ceiling at Storage Room 2152 there was a penetration to the right side of the duct work caused by drywall being improperly cut and not sealed.
- At approximately 11:30 AM observed that on the 2nd floor above the ceiling at Storage Room 2152 there was a penetration to the left side of the duct work caused by a fire alarm conduit that was not sealed with a fire rated material.
- At approximately 11:47 AM observed that on the 1st floor the Equipment Storage Room 1329 door was held in the open position with a bungee cord.
- At approximately 12:18 PM observed that on the 1st floor Soiled Utility Room 1323 door would not auto close to a positive latch.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on observation the facility failed to provide for the protection of hazardous areas in accordance with the LSC section 19.3.2.1. This deficient practice could affect all occupants of the facility in the event of a fire within the hazardous area enclosure where the products of combustion are allowed to spread to the means of egress due to improperly installed or maintained hazardous area separation.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:15 PM observed there was a rolling door separating the Ambulance Bay/Storage Area from the ER Area. This door operation is not activated by smoke detection as required.
- At approximately 03:25 PM observed that the Janitor's Closet door would not close to a positive latch due to the latching mechanism being secured with tape.
- At approximately 03:27 PM observed that the Lab door was being held in the open position by a foot operated device.
- At approximately 03:28 PM observed that the Soiled Linen Room door does not auto close to a positive latch.
- At approximately 03:30 PM observed that the 2nd floor telephone room had 2 pipe chases in the floor that were filled with an insulation type material that was not fire rated.
- At approximately 3:30 PM observed that the 2nd floor telephone room had 4 conduit chases in the ceiling that were filled with an insulation type material that was not fire rated.
- At approximately 03:40 PM observed that the Contractor's Room door was not equipped with a self-closing device.

LIFE SAFETY CODE STANDARD

Tag No.: K0033

Based on observation the facility failed to provide the required one-hour fire resistance rating for the exit components in accordance with the LSC section 8.2.5.2, 19.3.11. This deficient practice could affect all occupants of the facility in the event of a fire where the products of combustion are allowed to transmit throughout the building due to improperly latching door.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:35 PM observed that on the 2nd floor the North Stairwell door did not close to a positive latch.

LIFE SAFETY CODE STANDARD

Tag No.: K0034

Based on observation the facility failed to provide approved means of egress in accordance with the LSC section 18.2.2.4. This deficient practice could affect all building occupants in the event of an emergency where the rapid evacuation of the facility is necessary, but is delayed due to improperly maintained means of egress.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:50 AM observed that the South Stairwell contained an exhaust duct, domestic water lines, and medical gas lines that were passing through the stairwell and do not serve the stairwell.

LIFE SAFETY CODE STANDARD

Tag No.: K0034

Based on observation the facility failed to provide approved means of egress in accordance with the LSC section 19.2.2.3, 19.2.2.4. This deficient practice could affect all building occupants in the event of an emergency where the rapid evacuation of the facility is necessary, but is delayed due to improperly maintained means of egress.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:35 PM observed that there was combustible storage in the South Stairwell.

LIFE SAFETY CODE STANDARD

Tag No.: K0038

Based on observation the facility failed to provide approved exit access in accordance with the LSC section 19.2.1. This deficient practice could affect all building occupants in the event of an emergency where the rapid evacuation of the facility is necessary, but is delayed due to improperly maintained means of egress.


Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:36 PM observed that the 2nd floor North Stairwell exterior exit does not provide a hard path to the public way.

LIFE SAFETY CODE STANDARD

Tag No.: K0047

Based on observation the facility failed to provide exit and directional signs in accordance with the LSC section 18.2.10.1. This deficient practice could affect all building occupants in the event of an emergency where the rapid evacuation of the facility is necessary, but is delayed due to improperly located/maintained marking of the means of egress.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 12:30 PM observed that there was an "Exit" sign leading occupants into the Ambulance Bay, a hazardous area.
- At approximately 12:43 PM observed that the monthly "Exit" sign maintenance records were not available for review at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0048

Based on observation and review of records the facility failed to provide an approved written emergency plan in accordance with the LSC section 18.7.1.1. This deficient practice could potentially affect all occupants of the facility in the event of a fire which requires containment of the fire and/or the rapid evacuation of the building, and the containment and/or evacuation is delayed due to an improper emergency plan.
.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:50 AM observed that the Fire Emergency Plan located at the Acute Care Nurses Station had not been revised for the new facility.

LIFE SAFETY CODE STANDARD

Tag No.: K0050

Based on review of records the facility failed to provide written documentation regarding fire drills in accordance with the LSC section 19.7.1.2. This deficient practice could potentially affect all occupants of the facility if staff are not properly trained in approved emergency procedures.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 04:00 PM observed that fire drill records were not available for review at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0052

Based on observation the facility failed to provide a fire alarm system in accordance with the LSC section 9.6.1.4. This deficient practice could affect all building occupants in the event of a delay in occupant notification due to improperly maintained fire alarm system components.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:40 PM observed that in the Contractor's Room there was a fire alarm system strobe device not attached to wall and was hanging by its wiring.

LIFE SAFETY CODE STANDARD

Tag No.: K0052

Based on observation the facility failed to provide a fire alarm system in accordance with the LSC section 9.6.1.4. This deficient practice could affect all occupants of the affected smoke compartment in the event of a delay in occupant notification due to improperly maintained fire alarm system components.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 11:55 AM observed that in CT Room 1407 Restroom the fire alarm visual notification device was covered by a dust cover.

LIFE SAFETY CODE STANDARD

Tag No.: K0054

Based on observation the facility failed to provide and/or maintain smoke detection devices in accordance with the LSC section 9.6.1.3. This deficient practice could affect all building occupants in the event of a delay in occupant notification due to improperly maintained smoke detectors.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 12:18 PM observed that in Soiled Utility Room 1323 there was a smoke detector that was covered with a dust cover.

LIFE SAFETY CODE STANDARD

Tag No.: K0054

Based on observation the facility failed to provide and/or maintain smoke detection devices in accordance with the LSC section 9.6.1.3. This deficient practice could affect all building occupants in the event of a delay in occupant notification due to improperly spaced fire alarm system components.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:37 PM observed that at the 2nd floor Elevator Lobby there was a ceiling mounted smoke detector installed within 3 feet of a HVAC opening.

LIFE SAFETY CODE STANDARD

Tag No.: K0056

Based on observation and review of records the facility failed to provide and/or maintain a sprinkler system in accordance with the LSC section 18.3.5. This deficient practice could affect all building occupants in the event of a delay in occupant notification due to improperly maintained fire sprinkler system components.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 10:30 AM observed that the 2nd floor Shell Space ceiling tile was not intact, resulting in the sprinkler heads being greater than 12 inches below the ceiling.
- At approximately 12:40 PM observed by review of records that the sprinkler system gauges and control valves inspection records were not available for review at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0056

Based on observation the facility failed to provide and/or maintain a sprinkler system in accordance with the LSC section 19.3.5, NFPA 13 Section 5-7.4.1. This deficient practice could affect all building occupants in the event of a fire where the early suppression of the fire does not occur due to the improperly installed fire sprinkler system.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:40 PM observed that in the Contractor's room the sprinkler heads were installed greater than 6 inches from the ceiling.

LIFE SAFETY CODE STANDARD

Tag No.: K0064

Based on observation and review of records the facility failed to provide fire extinguishers in accordance with the LSC section 18.3.5.6. This deficient practice could affect all building occupants in the event of a fire which cannot be controlled due to improper maintenance of the portable fire extinguishers.

Finding include:

On 07/07/10, the following observations were made:

- At approximately 12:25 PM observed that monthly maintenance records for the Ambulance Bay portable fire extinguisher were not available for review at the time of inspection.
- At approximately 12:32 PM observed that monthly maintenance records for the Physical Therapy portable fire extinguisher was not available for review at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0064

Based on observation and review of records the facility failed to provide fire extinguishers in accordance with the LSC section 19.3.5.6. This deficient practice could affect all building occupants in the event of a fire where the early suppression of the fire does not occur due to improperly maintained fire extinguishers.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:10 PM observed that portable fire extinguisher monthly inspection records were not available for review at the time of inspection.
- At approximately 03:20 PM observed that the ER Storage fire extinguisher service tag indicated that the most recent annual service was conducted in June/2008.

LIFE SAFETY CODE STANDARD

Tag No.: K0074

Based on observation and review of records the facility failed to provide furnishing flammability documentation in accordance with provisions of the LSC section 10.3.1 and NFPA 13, Standards for the Installation of Sprinkler Systems. Newly introduced upholstered furniture within health care occupancies meets the criteria specified when tested in accordance with the methods cited in 10.3.2 (2) and 10.3.3. 19.7.5.1, NFPA 13

Newly introduced mattresses meet the criteria specified when tested in accordance with the method cited in 10.3.2 (3) , 10.3.4. 19.7.5.3

This deficient practice could affect all occupants within the facility in the event of a fire which is allowed to more rapidly develop due to improper flammable character of furnishings.


Findings include:

- At approximately 03:45 PM observed that the furnishing flammability documents were not available for review at the time of inspection.

LIFE SAFETY CODE STANDARD

Tag No.: K0076

Based on observation the facility failed to provide protection of medical gasses in accordance with NFPA 99. This deficient practice could affect all occupants of the facility in the event of a fire where the improperly stored oxygen contributes to the rate of fire growth.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:22 PM observed that in ER Storage there were unsecured oxygen cylinders.

LIFE SAFETY CODE STANDARD

Tag No.: K0076

Based on observation the facility failed to provide protection of medical gasses in accordance with NFPA 99. This deficient practice could affect all occupants of the affected smoke compartments in the event of a fire where the improperly stored oxygen contributes to the rate of fire growth.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 11:00 AM observed that in Clean Supply Room 2114 there were portable oxygen cylinders stored within 5 feet of combustible storage.
- At approximately 11:00 AM observed that in Clean Supply Room 2114 there were portable oxygen cylinders stored and not separated by full and empty.
- At approximately 11:00 AM observed that in Clean Supply Room 2114 there was an unsecured portable oxygen bottle.
- At approximately 11:08 AM observed that in Storage Room 2175 there were unsecured portable oxygen cylinders.

LIFE SAFETY CODE STANDARD

Tag No.: K0104

Based on observation and review of records the facility failed to provide smoke dampers in accordance with the LSC section 8.3.5. . This deficient practice could affect all occupants in adjacent smoke compartments in the event of a fire where the products of combustion are allowed to transmit throughout the affected smoke compartments due to improperly maintained duct penetrations.

Findings include:

- At approximately 03:20 PM observed that location of smoke barrier walls could not be verified at the time of inspection, resulting in not being able to verify necessity of duct penetration protection.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation the facility failed to maintain the electrical system in accordance with the LSC section 9.1.2. This deficient practice could affect all occupants of the facility in the event of a failure of the electrical equipment, or the exposure to hazardous electrical currents due to improper protection.

Findings include:

On 07/07/10, the following observations were made:

- At approximately 03:25 PM observed that in the Radiology Storage area there was exposed electrical wiring above the ceiling.