Tag No.: E0034
Based on document review and interview, it was determined the facility failed to develop an Emergency Preparedness communication plan including a means for providing information about the facility's occupancy, needs, and ability to provide assistance, to the authority having jurisdiction, the Incident Command Center, or designee, affecting the entire facility.
Findings include
1. Document review on November 6, 2019, at 10:20 a.m., revealed the facility failed to develop an emergency plan including a means for providing information about the facility's occupancy, needs, and ability to provide assistance, to the authority having jurisdiction, an Incident Command Center, or designee.
Interview at the exit conference with the Chief Operating Officer on November 7, 2019, at 11:30 a.m., confirmed the EP plan did not include a communication plan for providing information about their occupancy, in the event of an emergency.
***********************************
Based on document review and interview during an onsite Revisit conducted on November 2, 2020, at 8:15 a.m., revealed the following:
Item 1 Not Complete. The facility failed to develop an emergency plan including a means for providing information about the facility's occupancy, needs, and its ability to provide assistance to the authority having jurisdiction, an Incident Command Center, or designee.
Interview at the exit conference with the Administrator on November 2, 2020, at 11:50 a.m., confirmed the EP plan did not include a communication plan for providing information about their occupancy, in the event of an emergency.
Tag No.: K0100
Based on an observation and interview, it was determined the facility failed to maintain accurate floor plans outlining designated rated partitions, affecting one of six floors.
Findings Include:
1. Document review on November 6, 2019, at 11:50 a.m., revealed the provided floor plans indicated the wall of Storage Room 562 as a two hour rated wall. The wall above the door was stenciled as a one hour wall.
Interview at the exit conference with the Chief Operating Officer on November 7, 2019, at 11:30 a.m., confirmed the provided floor plans did not match the stenciling on the wall.
************************************
Based on document review and interview during an onsite Revisit conducted on November 2, 2020, at 8:15 a.m., revealed the following:
Item 1 Not Complete. The provided floor plans indicated the wall of Storage Room 562 as a two hour fire rated shaft wall. The wall above the door was stenciled as a one hour wall.
Interview at the exit conference with the Administrator on November 2, 2020, at 11:50 a.m.,
confirmed the provided floor plans did not match the stenciling on the wall.
Tag No.: K0311
Based on an observation and interview, it was determined the facility failed to ensure vertical openings between floors maintained a fire resistance rating, affecting two of six floors.
Findings include:
1. Observation on November 7, 2019, at 10:10 a.m., revealed, in Second Floor, Falls 4 electrical room, unsealed penetrations of the ceiling assembly around conduits.
Interview at the exit conference with the Chief Operating Officer on November 7, 2019, at 11:30 a.m., confirmed the unsealed vertical penetrations.
************************************
Based on observation and interview during an onsite Revisit conducted on November 2, 2020, at 8:15 a.m., revealed the following:
Item 1 Not Complete. Inside the Second Floor, Falls 4 electrical room, there were unsealed penetrations in the ceiling assembly.
Interview at the exit conference with the Administrator on November 2, 2020, at 11:50 a.m., confirmed there were unsealed penetrations in the rated ceiling assembly.
Tag No.: K0321
Based on an observation and interview, it was determined the facility failed to maintain hazardous areas, affecting two of six floors.
Findings include:
1. Observation on November 6, 2019, at 11:30 a.m., revealed, in Second Floor elevator lobby, the rated access door to the oxygen supply valves lacked a self-closure.
Interview at the exit conference with the Chief Operating Officer on November 7, 2019, at 11:30 a.m., confirmed the rated door lacked a self-closure.
2. Observation on November 6, 2019, at 12:45 p.m., revealed, in Fifth Floor, soiled utility room, had an unsealed penetration of the rear wall on both sides.
Interview at the exit conference with the Chief Operating Officer on November 7, 2019, at 11:30 a.m., confirmed the unsealed penetration.
************************************
Based on observation, document review and interview during an onsite Revisit conducted on November 2, 2020, at 8:15 a.m., revealed the following:
Item 2. Not Complete. The Fifth Floor, soiled utility room, there was an unsealed penetration of the rear rated shaft wall. The facility was unable to provide verification at the time of survey the penetrations were sealed utilizing a through penetration fire stop system.
Interview at the exit conference with the Administrator on November 2, 2020, at 11:50 a.m., confirmed the facility could not provide the verification information.
All other deficiencies noted under this tag were corrected.
Tag No.: K0344
Based on an observation and interview, it was determined the facility failed to ensure fire alarm control functions were maintained, affecting three of four elevators.
Findings include:
1. Observation on November 6, 2019, at 11:45 a.m., revealed, during the fire-alarm test, the following elevators did not recall: E025, E027, and E028.
Interview at the exit conference with the Chief Operating Officer on November 7, 2019, at 11:30 a.m., confirmed the elevators failed to recall during the fire-alarm test.
************************************
Based on observation and interview during an onsite Revisit conducted on November 2, 2020, at 8:15 a.m., revealed the following:
Item 1. Not Complete. An elevator recall test could not be performed for elevators E025, E027, and E028 due to the elevators being out of service during the revisit.
Interview at the exit conference with the Administrator on November 2, 2020, at 11:50 a.m., confirmed the elevator recalls could not be tested.
Tag No.: K0353
Based on an observation, document review and interview, it was determined the facility failed to maintain automatic sprinkler system components, affecting one of six floors.
Findings include:
1. Observation on November 7, 2019, at 10:20 a.m., revealed, in Fifth Floor electrical room, the spare sprinklers and wrench were not stored in a sprinkler cabinet.
Interview at the exit conference with the Chief Operating Officer on November 7, 2019, at 11:30 a.m., confirmed the sprinkler spares were not properly stored in a sprinkler cabinet.
***********************************
Based on observation and interview during an onsite Revisit conducted on November 2, 2020, at 8:15 a.m., revealed the following:
Item 1. Not Complete. inside the Fifth Floor electrical room, the spare sprinkler head box did not contain a sprinkler wrench.
Interview at the exit conference with the Administrator on November 2, 2020, at 11:50 a.m., confirmed the lack of a sprinkler wrench.
Tag No.: K0911
Based on an observation and interview, it was determined the facility failed to maintain protection of electrical wiring, affecting three of six floors.
Findings include:
1. Observation on November 7, 2019, between 9:30 a.m. and 10:00 a.m., revealed electrical panels with missing circuit breaker protective blanks in the following locations:
a. 9:30 a.m., Substation Falls 4, Panel DEP-4;
b. 9:55 a.m., Second Floor, Falls 4, Panel EGAS-2;
c. 10:00 a.m., Second Floor, Falls 4, Panel EEAS-2.
Interview at the exit conference with the Chief Operating Officer on November 7, 2019, at 11:30 a.m., confirmed electrical equipment was missing protective covers.
2. Observation on November 7, 2019, between 9:45 a.m. and 9:50 a.m., revealed junction boxes with exposed inner wiring, due to missing cover plates, in the following locations:
a. 9:45 a.m., Substation Falls 4;
b. 9:55 a.m., Falls 2, main switchgear room, above panels.
Interview at the exit conference with the Chief Operating Officer on November 7, 2019, at 11:30 a.m., confirmed the missing cover plates.
************************************
Based on observation and interview during an onsite Revisit conducted on November 2, 2020, at 8:15 a.m., revealed the following:
Item 2a and 2b. Not Complete. There were junction boxes with exposed inner wiring, due to missing cover plates, in the following locations:
a. 9:45 a.m., Substation Falls 4;
b. 9:55 a.m., Falls 2, main switchgear room, above panels.
Interview at the exit conference with the Administrator on November 2, 2020, at 11:50 a.m., confirmed the unprotected electrical wiring in the above named locations.
All remaining deficiencies listed under this tag were corrected.