HospitalInspections.org

Bringing transparency to federal inspections

850 W BARAGA AVE

MARQUETTE, MI 49855

No Description Available

Tag No.: K0011

Based on observation it was determined that the facility did not maintain the required minimum 2-hour fire resistance rating of the separation wall to the adjacent non-conforming building in accordance with the LSC, sections 1.1.4.1, 19.1.1.4.2. This deficient practice could potentially affect all patients, staff and visitors in the event of a fire not being properly contained away from this portion of the facility.

Findings include:
1. On 1/6/11 at approximately 12:03pm, the 90-minute separation doors from the 1968 Building failed to self-close and latch. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0012

Based on observation it was determined that the facility failed to maintain the construction type in accordance with the LSC, sections 19.1.6.2, 19.1.6.3, 19.1.6.4, 19.3.5.1, 4.6.6, 4.6.7, 4.6.9, 4.6.10. This deficient practice could potentially affect all patients, staff and visitors in the event of a structural failure during a fire.

Findings include:
1. On 1/5/11 at approximately 1:27pm, a portion of the steel structure located above the ceiling at the RCN Building connection was observed to be missing the required fireproofing material to maintain the required rating. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0018

Based on observation the facility failed to provide corridor doors that would close, latch and resist the passage of smoke in accordance with the LSC section 19.3.6.3. . This deficient practice could potentially affect patients, staff and visitors in the affected areas by not confining smoke and fire away from the corridor.

Findings include:
1. On 1/6/11 at approximately 9:16am, Room 588 was observed to have a towel hanging over the door that prevented the door from latching. This condition was noted with the Facilities Director and Maintenance Director present.
2. On 1/6/11 at approximately 9:28am, Room 567 was observed to have a towel hanging over the door that prevented the door from latching. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0020

Based on observation the facility failed to provide 1-hour fire resistive separation for the vertical openings in accordance with the LSC section 19.3.1.1. This deficient practice could potentially affect patients, staff and visitors that utilize the identified stair by not properly containing fire and smoke away from the exit.

Findings include:
1. On 1/6/11 at approximately 10:13am, the door and frame to the 3rd Floor West Stairwell were observed to have holes from hardware that had been removed. This condition was noted with the Facilities Director and Maintenance Director present.
2. On 1/6/11 at approximately 11:08am, the entrance door to Billing/Admitting failed to self-close and latch. This door is in the required 1-hour atrium separation. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0021

Based on observation the facility failed to provide for doors hold open devices in accordance with the LSC section 19.2.2.2.6. This deficient practice could potentially affect patients, staff and visitors in the affected smoke compartment in the event of a fire not being properly contained within a hazardous area.

Findings include:
1. On 1/5/11 at approximately 10:57am, the OR Storage Room door was observed to be equipped with a hold-open device tied to the building fire alarm system. No smoke detection for activation of the door release was installed in the area. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0027

Based on observation the facility failed to provide for the smoke barrier doors to be self-closing or automatic closing in accordance with the LSC section 19.2.2.2.6. This deficient practice could potentially affect patients, staff and visitors on the affected floor in the event of smoke not being properly contained to the compartment of origin.

Findings include:
1. On 1/6/11 at approximately 10:44am, the smoke barrier door in the 2nd Floor Birthing Center failed to close to a maximum gap of 1/8 of an inch. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0029

Based on observation the facility failed to provide for the protection of hazardous areas in accordance with the LSC section 18.3.2.1. This deficient practice could potentially affect patients, staff and visitors in the affected areas in the event of a fire not being properly contained to the hazardous area.

Findings include:
1. On 1/5/11 at approximately 10:28am, the ED Soiled Linen Room door failed to self-close and latch. This condition was noted with the Facilities Director and Maintenance Director present.
2. On 1/5/11 at approximately 10:33am, the ED West Hall Storage Room door failed to self-close and latch. This condition was noted with the Facilities Director and Maintenance Director present.
3. On 1/5/11 at approximately 10:52am, the Ground Floor Storage Room 101 door was observed to not be equipped with a coordinator for the door leafs. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0038

Based on observation the facility failed to provide approved exit access in accordance with the LSC section 18.2.1. This deficient practice could potentially affect staff by delaying egress due to reduced stairway width.

Findings include:
1. On 1/5/11 at approximately 10:20am, the 4th Floor Stairwell was observed to have items stored within the egress stair enclosure. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0039

Based on observation the facility failed to provide exit access in accordance with the LSC section 19.2.3.3. This deficient practice could potentially affect patients, staff and visitors by delaying egress due to reduced corridor width.

Findings include:
1. On 1/5/11 at approximately 12:43pm, the documentation station door failed to self-close upon testing. This failure caused the corridor width to be reduced below the designed 8-foot width. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0046

Based on review of records, the facility failed to test emergency lighting in accordance with the LSC section 19.2.9.1.
This deficient practice could potentially affect patients and staff in the operating rooms in the event of a power failure.

Findings include:
1. On 1/5/11 between 8:30am and 10:15am during records review, no documentation of the required 90-minute annual test of the battery-operated emergency lights serving the operating rooms was provided. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0056

Based on observation the facility failed to provide a sprinkler system in accordance with the LSC section 19.3.5. This deficient practice could potentially affect patients, staff and visitors by allowing a fire to grow uncontrolled due to a lack of sprinkler coverage.

Findings include:
1. On 1/5/11 at approximately 1:52pm, the 3rd Floor CS Electrical Room was observed to have no sprinkler head protecting the room. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0062

Based on observation the facility failed to ensure that the automatic sprinkler system is maintained in accordance with the LSC sections 19.7.6, 4.6.12, 9.7.5. This deficient practice could potentially affect patients, staff and visitors in the affected areas in the event of a fire not being properly controlled by the sprinkler system.

Findings include:
1. On 1/5/11 at approximately 11:49am, the 7th Floor North Clean Utility Room was observed to have storage that was within 18 inches of the sprinkler head and obstructing the sprinkler pattern development. This condition was noted with the Facilities Director and Maintenance Director present.
2. On 1/5/11 at approximately 12:39pm, the 6th Floor Elevator Tower Communications Room was observed to have a ceiling tile missing. No sprinkler protection is provided above the ceiling. This condition was noted with the Facilities Director and Maintenance Director present.
3. On 1/5/11 at approximately 12:55pm, the 5th Floor Elevator Tower Communications Room was observed to have a ceiling tile missing. No sprinkler protection is provided above the ceiling. This condition was noted with the Facilities Director and Maintenance Director present.
4. On 1/5/111 at approximately 1:45pm, the 3rd Floor Lab Storage Room was observed to have storage that was within 18 inches of the sprinkler head and obstructing the sprinkler pattern development. This condition was noted with the Facilities Director and Maintenance Director present.
5. On 1/5/11 at approximately 2:11pm, the 1st Floor Elevator Tower Storage Room was observed to have an IV pole hanging from the sprinkler pipe. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0067

Based on review of records the facility failed to maintain building services in accordance with the LSC sections 19.5.2.1, 9.2, and 19.6.2.2. This deficient practice could potentially affect all patients, staff and visitor in the event of a fire not being properly contained to the compartment of origin.

Findings include:
1. On 1/5/11 between 8:30am and 10:15am during records review, a portion of the fire dampers for the building as identified in Attachment 1 had not received the required 4-year testing. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0076

Based on observation the facility failed to provide protection of medical gasses in accordance with NFPA 99. This deficient practice could potentially affect staff in the affected area in the event of a cylinder falling over.

Findings include:
1. On 1/6/11 at approximately 9:45am, the 4th Floor Cath Lab Soiled Utility Room had a oxygen cylinder that was not secured in the upright position. This condition was noted with the Facilities Director and Maintenance Supervisor present.

No Description Available

Tag No.: K0144

Based on review of records the facility failed to provide documentation that generators are maintained in accordance with NFPA 99. This deficient practice could potentially affect all patients, staff and visitors in the event of a power failure.

Findings include:
1. On 1/5/11 between 8:30am and 10:15am during records review, the facility failed to provide documentation of the monthly load test for the generator for October 2010. This condition was noted with the Facilities Director and Maintenance Director present.

No Description Available

Tag No.: K0147

Based on observation the facility failed to maintain the electrical system in accordance with the LSC section 9.1.2. This deficient practice could potentially affect patients, staff and visitors in the affected areas in the event of an electrical failure.

Findings include:
1. On 1/5/11 at approximately 12:53pm, the electrical junction boxes above the ceiling in the 6th Floor East Corridor were observed to be missing the cover plates. This condition was noted with the Facilities Director and Maintenance Director present.
2. On 1/5/11 at approximately 1:06pm, an electrical junction box in the 4th Floor Electrical Room was observed to be missing the cover plate. This condition was noted with the Facilities Director and Maintenance Director present.