Tag No.: K0321
The inspector observed, while accompanied by the Plant Director during the hours of the inspection from 8:00 am to 11:35 am on 5/3/2017 that there were the following issues. The second floor rated double doors located near room #209 was missing an astragal or the equivalent.
Tag No.: K0500
The inspector observed, while accompanied by the Plant Director during the hours of the inspection from 8:00 am to 11:35 am on 5/3/2017 that there were the following issues. The facility failed to provide documentation showing that air filters were being inspected bimonthly for pressure drops per ASHRAE 170 requirements.
Tag No.: K0751
The inspector observed, while accompanied by the Plant Director during the hours of the inspection from 8:00 am to 11:35 am on 5/3/2017 that there were the following issues. The facility failed to provide the required flame spread documentation for draperies, curtains and for loosely hanging fabrics.
Tag No.: K0911
The inspector observed, while accompanied by the Plant Director during the hours of the inspection from 8:00 am to 11:35 am on 5/3/2017 that there were the following issues. In the electrical room on the second floor was being used for storage. The facility failed to provide an adequate safe zone space around the electrical panel boxes.
Tag No.: K0914
The inspector observed, while accompanied by the Plant Director during the hours of the inspection from 8:00 am to 11:35 am on 5/3/2017 that there were the following issues. The facility failed to provide documentation showing that records are maintained for receptacles for repairs or modifications, containing date, room or area tested, and results. 6.3.4 (NFPA 99)
Tag No.: K0918
The inspector observed, while accompanied by the Plant Director during the hours of the inspection from 8:00 am to 11:35 am on 5/3/2017 that there were the following issues. The facility failed to provide documentation showing that the required emergency generator testing and maintenance was being conducted.