HospitalInspections.org

Bringing transparency to federal inspections

777 HEMLOCK STREET

MACON, GA 31201

Building Construction Type and Height

Tag No.: K0161

K-161
Based on observation and interview with facility staff, the facility failed to ensure materials used to maintain building construction type requirements are poorly maintained. In the event of a fire in the effected areas all residents and staff may be affected.

Reference: NFPA 101 2012 Ed. Sec.19.1.6.1 thru 19.6.7

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed spray on fireproofing used to maintain the structual framing rating is missing in the 3rd floor mechanical room.

Staff member M confirmed the findings at the time of discovery.

Egress Doors

Tag No.: K0222

K 222
Based on observation and interview with facility staff, the facility failed to ensure 1 of several doors in the building is provided with only one lock or latch.

Reference: NFPA 101 2012 Ed. Sec 19.2.2.2.4

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed the 3rd floor toilet room on the South hallway has multiple locks and latches.

Staff member M confirmed the findings at the time of discovery.

Aisle, Corridor, or Ramp Width

Tag No.: K0232

K 232
Based on observation and interview with facility staff, the facility failed to ensure corridors are not being used for combustible storage. In the event of a fire in the affected area, all clients and staff may be affected.

Reference: NFPA 101 2012 Ed. Sec. 19.2.3.4

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed a combustible wooden storage crate being stored in the radiology corridor.
Staff member M confirmed the findings at the time of discovery.

Exit Signage

Tag No.: K0293

K 293
Based on observation and interview with facility staff, the facility failed to ensure exits on one of 5 floors are properly marked. Staff and clients in the affected area may be affected.

Reference: NFPA 101 2012 Ed. Sec. 7.10, 19.2.10.1

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed an exit sign is missing in the 1st floor administration area and the exit is not marked.

Staff member M confirmed the findings at the time of discovery.

Vertical Openings - Enclosure

Tag No.: K0311

K 311
Based on observation and interview with facility staff, the facility failed to ensure 1 of 2 vertical openings were properly maintained. In the event of a fire in the affected area all clients and staff may be affected.

Reference: NFPA 101 2012 Ed. Sec. 19.3.1.1 thru 19.3.1.6

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed openings in the one hour elevator shaft that was intended for a second door were filled in with gypsum and the joint between th gypsum and the block walls were not sealed with approved fire stopping.

Staff member M confirmed the findings at the time of discovery.

Fire Alarm System - Installation

Tag No.: K0341

K 341
Based on observation and interview with facility staff, the facility failed to ensure proper fire alarm visual notification is provided. In the event of a fire all hearing impaired staff and clients may be affected.

Reference: NFPA 101 2012 Ed. Sec. 9.6, 19.3.4.1

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed fire alarm strobes were set at the incorrect candela or not spaced correctly in the following areas:
(a) The wall mounted strobe in the corridor is set at 110 cd
(b) There was no strobe provided in the men ' s locker room on the second floor.
(c) There was no strobe provided in the second floor recovery room.
(d) There was no strobe provided in the contaminated instrument elevator lobby .
(e) There was no strobe provided in the doctors dictation room on the second floor.
(f) There was no strobe provided in the anesthesia office.
(g) Proper spacing of strobes is not maintained in the ASC lobby and consultation space.

Staff member M confirmed the findings at the time of discovery.

Sprinkler System - Installation

Tag No.: K0351

Based on observation and interview with facility staff, the facility failed to ensure all areas of the building have complete sprinkler coverage. In the event of a fire in these areas, all clients and staff may be affected.

Reference: NFPA 101 2012 Ed. Sec. 9.7.1.1, 19.3.5.3, 19.3.5.5

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed the following areas that were not completely covered with sprinkler protection:
(a) Sprinkler coverage was obstructed by a 5 foot HVAC duct in the basement boiler room.
(b) Two sprinkler heads were removed and branch lines plugged in the basement boiler room.
(c) A pendant sprinkler head was concealed above a light fixture lens outside room M-282
(d) Sprinklers were spaced more than 7 feet 6 inches apart at the storage alcove on the back hall of NNICU
(e) The outside trash collection area is covered by a canopy and is being used for storage and the area is not provided with sprinkler protection.
(f) The freezer in the main kitchen is not provided with sprinkler protection.

Staff member M confirmed the findings at the time of discovery.

K 351
Based on observation and interview with facility staff, the facility failed to ensure all areas of the building have complete sprinkler coverage. In the event of a fire in these areas, all clients and staff may be affected.

Reference: NFPA 101 2012 Ed. Sec. 9.7.1.1, 19.3.5.3, 19.3.5.5

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed the following areas that were not completely covered with sprinkler protection:
(a) Sprinkler coverage was obstructed by a 5 foot HVAC duct in the basement boiler room.
(b) Two sprinkler heads were removed and branch lines plugged in the basement boiler room.
(c) A pendant sprinkler head was concealed above a light fixture lens outside room M-282
(d) Sprinklers were spaced more than 7 feet 6 inches apart at the storage alcove on the back hall of NNICU
(e) The outside trash collection area is covered by a canopy and is being used for storage and the area is not provided with sprinkler protection.
(f) The freezer in the main kitchen is not provided with sprinkler protection.

Staff member M confirmed the findings at the time of discovery.

Sprinkler System - Maintenance and Testing

Tag No.: K0353

K 353
Based on observation and interview with facility staff, the facility failed to ensure proper testing and maintenance of sprinklers has been conducted. Staffing may be affected by a fire in the affected area.

Reference: NFPA 101 2012 Ed. Sec. 9.7.6 NFPA 25 2011 Ed.

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed sprinkler heads in the basement boiler room are over 50 years old.

Staff member M confirmed the findings at the time of discovery

Subdivision of Building Spaces - Smoke Barrie

Tag No.: K0372

K 372
Based on observation and interview with facility staff, the facility failed to ensure the smoke barrier on one of five floors is properly maintained. In the event of a fire on that floor, the clients and staff of that floor may be affected.

Reference: NFPA 101 2012 Ed. Sec. 8.6.7.1 (1), 19.3.7.3

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed the smoke barrier adjacent to the center stairs on the 3rd floor has penetrations that are not properly fire stopped.

Staff member M confirmed the findings at the time of discovery.

HVAC

Tag No.: K0521

K 521
Based on observation and interview with facility staff, the facility failed to ensure gas fired appliances and rooms containing gas fired appliances are properly ventilated.

Reference: NFPA 101 2012 Ed. Sec. 9.2, 19.5.2.1

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed there were not high and low vents for combustion and ventilation air in the EVS laundry room. Observation also revealed the dryer vents in the EVS room are leaking above the acoustical ceiling and the joints in the metal dryer ducts are secured together using sheet metal screws.

Staff member M confirmed the findings at the time of discovery.

Electrical Systems - Other

Tag No.: K0911

K-911
Based on observation and interview with facility staff, the facility failed to ensure electrical systems are not in accordance with NFPA 99.

Reference: NFPA 70 2011 Ed.

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed the circuit breakers in the electrical panel boxes were not identified.

Staff member M confirmed the findings at the time of discovery.

Electrical Equipment - Power Cords and Extens

Tag No.: K0920

K 920
Based on observation and interview with facility staff, the facility failed to ensure power strips were properly installed in the administration area of one of nine floors. Improper installation of these devices may affect the staff and clients in that area.

Reference: NFPA 70 2011 Ed. 590.3 (D)

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed the power strips were resting on the floor of the 3rd floor administration area.

Staff member M confirmed the findings at the time of discovery.

Gas Equipment - Cylinder and Container Storag

Tag No.: K0923

K 923
Based on observation and interview with facility staff, the facility failed to ensure oxygen cylinders are properly secured on 3 of 9 floors. In the event of the cylinders falling all residents and clients may be affected.

Reference: NFPA 99 2012 Ed. Sec. 11.3.3.3

Findings Include:
On 12/12/2016 between 10:30 a.m. and 5:30 p.m. observation revealed oxygen cylinders in the hall next to the elevators on the 7th, 8th, and 9th floors are not secured.

Staff member M confirmed the findings at the time of discovery.