9407 CUMBERLAND ROAD

NEW KENT, VA 23124

No Description Available

Tag No.: K0025

Based upon observations, the fire rated smoke barrier walls have penetrations and/or openings that are not fire stopped and could allow smoke to pass from one side of the smoke barrier to the other side.

Findings include

On November 15,2011 at 10:27 AM, it is observed that the smoke wall separating the lobby from the acute care area has unprotected penetrations.

No Description Available

Tag No.: K0029

Based upon observations, fire separations of hazardous areas are not properly maintained.

Findings include

On November 15,2011 at 10:14 AM, it is observed that the fire curtain separating the washer dryer room from the nurses station has not had an annual test.

No Description Available

Tag No.: K0047

Based upon observations, the exit sign are not being properly maintained.

Findings include

On November 15,2011 at 11:06 AM, it is observed the the exit sign on Side A is missing the cover.

No Description Available

Tag No.: K0062

Based upon observations, the sprinkler system and its components are not being properly maintained.

Findings include

On November 15, 2011 at 10:28 AM, it is observed that the sprinkler head in the pharmacy closet has combustibles stored within 18 inches of the sprinkler.

On November 15,2011 at 10:28 AM, it is observed that the sprinkler head in the pharmacy closet is not flush with the ceiling.

No Description Available

Tag No.: K0147

Based upon observations, there is electrical equipment that is not properly maintained.

Findings include

On November 15,2011 at 10:59 AM, it is observed that there is a electrical junction box without a cover in the sprinkler riser room.