Bringing transparency to federal inspections
Tag No.: K0038
Based upon observation and interview, the facility failed to maintain the the exit corridors open and accessible at all times in one location in the facility.
Findings include:
Observation on May 24, 2010 at 1:30 pm revealed there were work stations set-up in the exit corridor near the Main Nurses station with chairs at the computer on wheels.
Interview with facility representatives on May 25, 2010 confirmed the condition exists.
Tag No.: K0147
Based upon observation and interview, it was determined the electrical wiring and/or equipment does not comply with NFPA 70, the National Electrical Code in one location in the facility.
Findings include:
Observation on May 24, 2010 at 11:45 am revealed that the Hydrocolator in the temporary OT/PT room was not protected by a GFCI plug.
Interview with facility representatives on May 25, 2010 confirmed the condition exists.