HospitalInspections.org

Bringing transparency to federal inspections

5 MOBILE INFIRMARY CIRCLE

MOBILE, AL 36607

No Description Available

Tag No.: K0078

.
Uncorrected Deficiency, Waiver Pending


* The facility failed to provide smoke venting for the ORs per code. Findings include:

During the survey, the following is an example of what was observed:

The 24 windowless ORs, per observation and interview, did not have a smoke venting system.

------------
1999 NFPA 99, 5-4.1.2 Supply and exhaust systems for windowless anesthetizing locations shall be arranged to automatically vent smoke and products of combustion.

1999 NFPA 99, 5-4.1.3 Ventilating systems for anesthetizing locations shall be provided that automatically (a) prevent recirculation of smoke originating within the surgical suite and (b) prevent the circulation of smoke entering the system intake, without in either case interfering with the exhaust function of the system.

1999 NFPA 99, 5-4.1.4 The electric supply to the ventilating system shall be served by the equipment system of the essential electrical system specified in Chapter 3, "Electrical Systems."

1999 NFPA 99, 5-6.1.1 Ventilating and humidifying equipment for anesthetizing locations shall be kept in operable condition and be continually operating during surgical procedures (see A-5-4.1).



27382