HospitalInspections.org

Bringing transparency to federal inspections

3637 OLD VINEYARD ROAD

WINSTON SALEM, NC 27104

No Description Available

Tag No.: K0025

By observation on 11/2/09 and onward smoke barriers were non-compliant, specific findings include penetrations in the following areas:
(A) Above ceiling to laundry
(B) Across from laundry at room 111
(C) Above the cross corridor smoke doors

This is a recited item:
By observation on 1/22/2010 and onward smoke barriers were non-compliant, specific findings include penetrations in the following areas:
(A) Above ceiling to laundry

No Description Available

Tag No.: K0025

By observation on 11/2/09 and onward smoke barriers were non-compliant, specific findings include penetrations in the following areas:
(A) The smoke wall of Phoenix and Perserverance
(B) Around the window to Pharmacy
(C) The ceiling to the main electrical room and the exterior dietary hot water heater room.

This is a recited item:
By observation on 1/22/2010 and onward smoke barriers were non-compliant, specific findings include penetrations in the following areas:
(A) Smoke wall to adjacent compartment in dayroom above the ceiling.

No Description Available

Tag No.: K0067

By observation on 11/2/09 and onward the following HVAC regulations were non-compliant, specific findings include improper air balance between the corridor and the three bedrooms and conference room in the girls adolescent area. Currently the air flow to the roof based HVAC unit is believed by staff to return warm air from the adjacent area beyond the cross corridor smoke doors causing the unit to not cycle on and provide warm air to the bedrooms and conference area when needed.

This is Waivered Item that will expire on 2/19/2010

No Description Available

Tag No.: K0076

By observation on 1/22/2010 the following was noted:
1) In the room located across from room 111 and nurse station (Phoenix) By observation, oxygen cylinders were not properly chained or supported in a proper cylinder stand or cart. [NFPA 99 4-3.5.2.1b(27)]

LIFE SAFETY CODE STANDARD

Tag No.: K0067

By observation on 11/2/09 and onward the following HVAC regulations were non-compliant, specific findings include improper air balance between the corridor and the three bedrooms and conference room in the girls adolescent area. Currently the air flow to the roof based HVAC unit is believed by staff to return warm air from the adjacent area beyond the cross corridor smoke doors causing the unit to not cycle on and provide warm air to the bedrooms and conference area when needed.

This is Waivered Item that will expire on 2/19/2010