525 WEST MAIN STREET

MELROSE, MN 56352

No Description Available

Tag No.: K0018

On the facility tour between 10:30 am and 2:00 PM on 07/09/2015, observations revealed the linen storage by the OR in the corridor did not positively latch.

No Description Available

Tag No.: K0052

On the facility tour between 10:30 am and 2:00 pm on 07/09/2015, observations revealed the smoke detectors in Rooms 5 through 8 were installed within 36 inches of the HVAC vent.

No Description Available

Tag No.: K0056

On the facility tour between 10:30 am and 2:00 pm on 07/09/2015, observations revealed there was no sprinkler protection in the can wash room.

No Description Available

Tag No.: K0147

On the facility tour between 10:30 AM and 2:00 PM on 07/09/2015, observations revealed the following:
1) Extension cord plugged into a power strip in the laundry room behind the washer for the laundry soap.
2) Extension Cord plugged into a power strip in the Environmental Services Office powering a Microwave.
3) In the administration office there was a refrigerator plugged into an extension cord and other items used with another extension cord with a multi-plug adapter on the end of it in the same office.