Tag No.: K0025
Based on observations the facility failed to provide the required 30 minute fire resistance rating for smoke barrier walls in accordance with 19.3.7.3, 19.1.6.3, 19.1.6.4.
Finding include:
While inspecting smoke barrier walls on November 13, 2012 at 10:45 a.m., the maintenance supervisor and the surveyor observed small penetrations in 4 of the 4 smoke barrier walls on the 1st and 2nd floor.
This condition has the potential to affect about 50% of the residents and staff. The administrator and maintenance director were notified during the survey and in the exit conference.
Tag No.: K0062
Based on observation and record review, the facility failed to properly test and maintained the automatic sprinkler system contrary to NFPA 13, NFPA 25. This condition affected 100% of the residents and staff as all smoke compartments were affected.
Findings include:
While inspecting the sprinkler system on November 13, 2012 at 11:45 a.m., the surveyor and maintenance supervisor found that the sprinkler head, located in the south stairwell on the second floor, was blocked by a light.
The maintenance supervisor and the administrator were notified during an exit conference.
Tag No.: K0025
Based on observations the facility failed to provide the required 30 minute fire resistance rating for smoke barrier walls in accordance with 19.3.7.3, 19.1.6.3, 19.1.6.4.
Finding include:
While inspecting smoke barrier walls on November 13, 2012 at 10:45 a.m., the maintenance supervisor and the surveyor observed small penetrations in 4 of the 4 smoke barrier walls on the 1st and 2nd floor.
This condition has the potential to affect about 50% of the residents and staff. The administrator and maintenance director were notified during the survey and in the exit conference.
Tag No.: K0062
Based on observation and record review, the facility failed to properly test and maintained the automatic sprinkler system contrary to NFPA 13, NFPA 25. This condition affected 100% of the residents and staff as all smoke compartments were affected.
Findings include:
While inspecting the sprinkler system on November 13, 2012 at 11:45 a.m., the surveyor and maintenance supervisor found that the sprinkler head, located in the south stairwell on the second floor, was blocked by a light.
The maintenance supervisor and the administrator were notified during an exit conference.