Bringing transparency to federal inspections
Tag No.: K0211
Based on observation and interview, the Facility failed to be in accordance with Chapter 7, which states, all means of egress is to be continuously maintained free of all obstructions to full use in case of emergency.
Means of Egress - General
Aisles, passageways, corridors, exit discharges, exit locations, and accesses are in accordance with Chapter 7, and the means of egress is continuously maintained free of all obstructions to full use in case of emergency, unless modified by 18/19.2.2 through 18/19.2.11.
18.2.1, 19.2.1, 7.1.10.1
FINDINGS INCLUDE:
On facility tour between 9:00 AM and 12:00 PM on 05/01/2018, observation revealed a large decorative plant being stored in the East Stairwell and numerous items were observed being stored within the Radiology Exit.
This deficient practice was verified by the Facility Maintenance Director.
Tag No.: K0914
Electrical Systems - Maintenance and Testing
Hospital-grade receptacles at patient bed locations and where deep sedation or general anesthesia is administered, are tested after initial installation, replacement or servicing. Additional testing is performed at intervals defined by documented performance data. Receptacles not listed as hospital-grade at these locations are tested at intervals not exceeding 12 months. Line isolation monitors (LIM), if installed, are tested at intervals of less than or equal to 1 month by actuating the LIM test switch per 6.3.2.6.3.6, which activates both visual and audible alarm. For LIM circuits with automated self-testing, this manual test is performed at intervals less than or equal to 12 months. LIM circuits are tested per 6.3.3.3.2 after any repair or renovation to the electric distribution system. Records are maintained of required tests and associated repairs or modifications, containing date, room or area tested, and results.
6.3.4 (NFPA 99).
FINDINGS INCLUDE:
On facility tour between 9:00 AM and 12:00 PM on 05/01/2018, it was revealed that not all of the testing procedures were being conducted during the electric receptacle testing. The electrical receptacles must receive the following inspections:
1.The physical integrity of each receptacle shall be confirmed by visual inspection.
2. The continuity of the grounding circuit in each electrical receptacle shall be verified.
3. Correct polarity of the hot and neutral connections in each electrical receptacle shall be confirmed.
4. The retention force of the grounding blade of each electrical receptacle (except locking-type receptacles) shall be not less than 115 g (4 oz).
This deficient practice was verified by the Facility Maintenance Director.
Tag No.: K0918
Based on documentation review and interview, the Facility failed to provide complete written records of Generator maintenance and testing are maintained and readily available.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked and readily identifiable. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
FINDINGS INCLUDE:
On facility tour between 9:00 AM and 12:00 PM on 05/01/2018, during documentation review, it was revealed that the transfer time between normal and emergency power was not being recorded to show that this is occurring within 10 seconds.
This deficient practice was verified by the Facility Maintenance Director.