1401 WEST ASH STREET

GOLDSBORO, NC 27530

No Description Available

Tag No.: K0027

a. Based on observation on 05/10/2011 the corridor smoke door near room 254 failed to close ( dragging the floor ).

No Description Available

Tag No.: K0029

A. Based on observation on 05/10/2011 storage room #377 was not covered by a sprinkler head.

No Description Available

Tag No.: K0029

A. Based on observation on 05/10/2011 the corridor door to the linen storage room #144 failed to latch when closed.

No Description Available

Tag No.: K0045

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) Exit discharge lighting was not provided at the exit doors in the basement area.

No Description Available

Tag No.: K0050

A. Based on observation on 05/12/2011 the staff interviewed did not know the fire drill procedure and also had trouble finding the right key to activate/reset the Fire Alarm pull stations.

No Description Available

Tag No.: K0052

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) The strobe lights in building #1 on first floor east did not operate on battery back-up power when testing the fire alarm system

2) Based on observation on 05/12/2011 when the fire alarm was tested there was a strobe not working on the second floor East near room 218.

No Description Available

Tag No.: K0072

A. Based on observation on 05/11/2011 there were linen carts stored in the egress corridor on the second floor ( near room 202 )

No Description Available

Tag No.: K0147

A. Based on observation on 05/11/2011 there were incandescent light fixtures in the 1 East soiled linen room there were not protected by a cover.


26594

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) At the electrical area in the basement where the transfer switch for emergency generator is located, the area was not supplied with emergency battery backup lighting.

No Description Available

Tag No.: K0147

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:


1) At the electrical area in the basement where the transfer switch for emergency generator is located, the area was not supplied with emergency battery backup lighting.

No Description Available

Tag No.: K0147

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) At the electrical area in the basement where the transfer switch for emergency generator is located, the area was not supplied with emergency battery backup lighting.

No Description Available

Tag No.: K0147

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) At the electrical area in the basement where the transfer switch for emergency generator is located, the area was not supplied with emergency battery backup lighting.

.

LIFE SAFETY CODE STANDARD

Tag No.: K0027

a. Based on observation on 05/10/2011 the corridor smoke door near room 254 failed to close ( dragging the floor ).

LIFE SAFETY CODE STANDARD

Tag No.: K0029

A. Based on observation on 05/10/2011 storage room #377 was not covered by a sprinkler head.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

A. Based on observation on 05/10/2011 the corridor door to the linen storage room #144 failed to latch when closed.

LIFE SAFETY CODE STANDARD

Tag No.: K0045

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) Exit discharge lighting was not provided at the exit doors in the basement area.

LIFE SAFETY CODE STANDARD

Tag No.: K0050

A. Based on observation on 05/12/2011 the staff interviewed did not know the fire drill procedure and also had trouble finding the right key to activate/reset the Fire Alarm pull stations.

LIFE SAFETY CODE STANDARD

Tag No.: K0052

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) The strobe lights in building #1 on first floor east did not operate on battery back-up power when testing the fire alarm system

2) Based on observation on 05/12/2011 when the fire alarm was tested there was a strobe not working on the second floor East near room 218.

LIFE SAFETY CODE STANDARD

Tag No.: K0072

A. Based on observation on 05/11/2011 there were linen carts stored in the egress corridor on the second floor ( near room 202 )

LIFE SAFETY CODE STANDARD

Tag No.: K0147

A. Based on observation on 05/11/2011 there were incandescent light fixtures in the 1 East soiled linen room there were not protected by a cover.


26594

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) At the electrical area in the basement where the transfer switch for emergency generator is located, the area was not supplied with emergency battery backup lighting.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:


1) At the electrical area in the basement where the transfer switch for emergency generator is located, the area was not supplied with emergency battery backup lighting.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) At the electrical area in the basement where the transfer switch for emergency generator is located, the area was not supplied with emergency battery backup lighting.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation on May 12, 2011 at approximately 10:30 AM onward the following was noted:
1) At the electrical area in the basement where the transfer switch for emergency generator is located, the area was not supplied with emergency battery backup lighting.

.