HospitalInspections.org

Bringing transparency to federal inspections

2767 OLIVE HIGHWAY

OROVILLE, CA 95966

No Description Available

Tag No.: K0012

Based on observation, the facility failed to maintain the integrity of the building construction. This was evidenced by unsealed penetrations in the walls and ceilings. This affected two of two floors in the Main Hospital and could potentially result in the spread of fire and smoke to other areas of the facility.

Findings:

During a tour of the facility with Staff on 8/3/15, the walls and ceilings were observed.

Main Hospital

1. At 9:30 a.m., there were three approximately 1/4 inch penetrations in the north wall next to fire extinguisher 54 in the Lift Equipment Room.

2. At 9:35 a.m., in the South Mechanical Room wall, there was an approximately 1/4 inch penetration around a one inch pipe, an approximately 1/4 inch penetration around a 1/2 inch pipe, and an approximately 1/4 inch penetration around a cord in the wall.

3. At 9:50 a.m., in the Maternity Ward Storage Room, there was an approximately eight foot by eight foot area of the southwest wall that was missing the sheet rock. There was also an approximately eight foot by two foot area of the ceiling that was missing the sheet rock.

4. At 10:10 a.m., a data outlet plate cover was shifted to one side exposing an approximately 1/4 inch penetration in the wall below a desk in the Neurology Lab.

5. At 10:31 a.m., a sprinkler head was missing an escutcheon ring exposing an approximately 1/2 inch penetration in the ceiling in Janitor Closet 9.

6. At 11:20 a.m., a sprinkler head was missing an escutcheon ring exposing an approximately 1/4 inch penetration around the pipe in the X-ray Office.

7. At 11:33 a.m., a sprinkler escutcheon ring was not flush to the ceiling exposing an approximately 1/4 inch penetration in the Emergency Registration Office.

8. At 11:40 a.m., a sprinkler escutcheon ring was shifted to one side exposing an approximately 1/4 inch penetration in the ceiling in the Respiratory Break Room.

9. At 11:51 a.m., a sprinkler head was missing an escutcheon ring exposing an approximately 1/2 inch penetration in the ceiling in the Kitchen Serving Line.

10. At 12:57 p.m., a sprinkler head was missing an escutcheon ring exposing an approximately 1/4 inch penetration in Room 604 of Ambulatory Care Service (ACS).

No Description Available

Tag No.: K0018

Based on observation, the facility failed to maintain its corridor doors. This was evidenced by four doors that were obstructed and one door that failed to latch. This affected two of two floors in the Main Hospital and could potentially result in the inability to contain a fire to a room.

NFPA 101, 2000
19.3.6.3.7 Door frames shall be labeled, shall be of steel construction, or shall be other materials in compliance with the provisions of 8.2.3.2.1

8.2.3.2.1 Doors assemblies in fire barriers shall be of an approved type with the appropriate fire protection rating for the location in which they are installed and shall comply with the following: (a) Fire doors shall be installed in accordance with NFPA 80, Standard for Fire Doors and Fire Windows.

NFPA 80, 1999
Door opening and the surrounding area shall be kept clear of anything that could obstruct or interfere with the free operation of the door.

Findings:

During a tour of the facility with Staff on 8/3/15, the corridor doors were observed.

Main Hospital

1. At 9:54 a.m., the roll down fire door at the Obstetrics and Gynecology (OB) Nurse's Station was obstructed from closing by a tissue box, a box of face masks, and a hole puncher.

2. At 10:23 a.m., the self-closing door to the State Office was held open by a rubber wedge.

3. At 11:07 a.m., the rolling down fire door in the Laboratory was obstructed by a tissue box, a brochure box, a bell, and a black basket.

4. At 11:16 a.m., the self-closing door to Micro Laboratory was held open by a piece of cardboard.

5. At 1 p.m., the self-closing door to the Unit 3 Overflow failed to latch.

No Description Available

Tag No.: K0022

Based on observation, the facility failed to mark access to exits. This was evidenced by the failure to provide visible exit signs at exit locations. This affected two of two floors in the Main Hospital, and had the potential to delay evacuation in the event of an emergency.

Findings:

During a tour of the facility with Staff on 8/3/15, the exit locations were observed.

Main Hospital

1. At 10:05 a.m., there was no exit sign above the exit door in the Obstetrics and Gynecology (OB) waiting room. There was a sign on the door identifying it as an emergency exit.

2. At 11 a.m., there was no exit sign above the exit stairway door on the second floor near the Dover elevator.

3. At 11:34 a.m., there was no exit sign above the Emergency Room (ER) waiting area door.

4. At 11:35 a.m., there was no exit sign above the ER patient registration door.

No Description Available

Tag No.: K0027

Based on observation, the facility failed to maintain the fire doors. This was evidenced by items that were stored in front of the fire doors. This affected two of two floors in the Main Hospital, and could result in a delay in egress in the event of an emergency.

NFPA 101, 2000
19.3.6.3.7 Door frames shall bed labeled, shall be of steel constructions, or shall be of other materials in compliance with the provision of 8.2.3.2.1
8.2.3.2.1 Door assemblies in fire barrier shall be of an approved type with the appropriate fire protection rating for the location in which they are installed and shall comply with the following: (A) the fire doors shall be installed in accordance with NFPA 80, Standard for Fire Doors and Fire Window. Fire doors shall be of a design that has been tested to meet the conditions of acceptance of NFPA 252, Standard Methods of Fire Test of Door Assemblies.

NFPA 80, 1999
2-4.1.4* All closing mechanisms shall be adjusted to overcome the resistance of the latch mechanism so that positive latching is achieved on each door operation.
15-1 This chapter covers the care and maintenance of fire doors and fire windows.
15-2.3 Prevention of Door Blockage.
15-2.3.1 Door openings and the surrounding areas shall be kept clear of anything that could obstruct or interfere with the free operation of the door.
15-2.3.3 Blocking or wedging of doors in the open position shall be prohibited.

Findings:

During a tour of the facility with Staff, the fire doors were observed.

Main Hospital

1. On 8/3/15, at 9:26 a.m., the right leaf fire door 4-22 on the first floor was obstructed by a large, tall yellow bin. The yellow bin was stationed within one inch of the door handle when the door was closed.

2. On 8/3/15, at 10:26 a.m., the right leaf fire door 1-13 on the first floor was obstructed by a north cart. The north cart was stationed within one inch of the door handle when the door was closed.

3. On 8/4/15, at 9:22 a.m., the left leaf of fire door 26-11 on the second floor near Dover corridor failed to latch .

4. On 8/4/15, at 9:32 a.m., the right leaf of fire door 7-20 on the second floor failed to latch.

No Description Available

Tag No.: K0029

.
Outpatient Services Building 2-2809 Olive Highway

3. On 8/5/15, at 10 a.m., the door to the Biohazard Room in Suite 230 was not equipped with a self-closing device.

No Description Available

Tag No.: K0029

Based on observation, the facility failed to protect its hazardous areas. This was evidenced by doors to hazardous area enclosures that were not equipped with self-closing devices and by one door that failed to latch. This affected one of two floors at the Main Hospital and one of three floors at Outpatient Services Building 2. This could potentially result in the spread of fire and/or smoke to other areas of the facility.

NFPA 101, 2000
19.3.2.1 states that any hazardous areas shall have smoke-resisting doors that are self-closing or automatic-closing. Hazardous areas shall include, but shall not be restricted to, the following:
(1) Boiler and fuel-fired heater rooms
(2) Central/bulk laundries larger than 100 ft2 (9.3 m2)
(3) Paint shops
(4) Repair shops
(5) Soiled linen rooms
(6) Trash collection rooms
(7) Rooms or spaces larger than 50 ft2 (4.6 m2), including repair shops, used for storage of combustible supplies and equipment in quantities deemed hazardous by the authority having jurisdiction
(8) Laboratories employing flammable or combustible materials in quantities less than those that would be considered a severe hazard.

39.3.2.1 Hazardous areas including, but not limited to, areas used for general storage, boiler or furnace rooms, and maintenance shops that include woodworking and painting areas shall be protected in accordance with section 8.4

8.4.1.3 Doors in barriers required to have a fire resistance rating shall have a 3/4 hour fire protection rating and shall be self closing or automatic closing in accordance with 7.2.1.8.

Findings:

During a tour of the facility with Staff, the hazardous areas were observed.

Main Hospital

1. On 8/3/15, at 10:36 a.m., the door to the Soiled Linen Room near Room 205 failed to latch.

2. On 8/3/15, at 11:50 a.m., the Kitchen Dry Storage Room contained approximately three dozen cardboard boxes and paper packaging. The room was 225 square feet in size and the door was not equipped with a self-closing device.

No Description Available

Tag No.: K0038

Based on observation, the facility failed to maintain the emergency exit doors. This was evidenced by items that were stored in front of the emergency exit doors. This affected two of two floors in the Main Hospital and could result in a delayed egress in the event of an emergency.

Findings:

During a tour of the facility with Staff on 8/3/15, the emergency exit doors were observed.

Main Hospital

1. At 9:20 a.m., there was an exit sign above the emergency exit door in the Linen Storage Room on the first floor. The door was completely obstructed by a laundry cart, a large box, two step stools, and a walker.

2. At 11:31 a.m., the exit door that was adjacent to 14T in the Emergency Department was obstructed by a bed that was stationed within one inch of the left leaf push handle.

No Description Available

Tag No.: K0046

.
Outpatient Services Building 2-2809 Olive Highway

2. On 8/5/15, at 1:20 p.m., there was one emergency light observed in Suite 110. No documentation was provided indicating that the 30 second monthly or 90 minute annual tests had been performed in the past 12 months. During an interview at 1:30 p.m., the Assistant Director of Plant Operations confirmed the finding.

No Description Available

Tag No.: K0046

Based on observation, document review, and interview, the facility failed to maintain its battery back-up emergency lights. This was evidenced by incomplete testing for the 90 minutes test annually in the Main Hospital, and failure to test one emergency light for 30 seconds monthly and 90 minutes annually in the Outpatient Services Building 2. This could result in a delay in evacuation in the event of a power outage.

NFPA 101, 2000
19.2.9 Emergency Lighting
Emergency lighting shall be provided in accordance with section 7.9

39.2.9.1 Emergency lighting shall be provided in accordance with section 7.9 in any building where any one of the following conditions exists (1) the building is two or more stories in height above the level of exit discharge. (2) the occupancy is subject to 100 or more occupants above or below the level of exit discharge. (3) the occupancy is subject to 1000 or more total occupants.

7.9.3 Periodic Testing of Emergency Lighting Equipment. A functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds. A annual test shall be be conducted on every required battery-powered emergency lighting system for not less than 1 1/2 hours. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.

Findings:

During tour, document review, and interview with staff, the emergency lights were observed and documents were requested.

Main Hospital

1. On 8/4/15, at 1:45 p.m., the facility was observed with emergency lights throughout the building. The document titled, "Emergency Lights," was incomplete. The log indicated that eight of 31 emergency lights had not been tested in the past 12 months. There was no annual testing in the Dietary Serving Line, Dietary North Wall, RT Blood Gas Lab, Medical Records, Medical Records Transcription Room, Phlebotomy Supervisor's Office Room 888, HIS Computer Room, and HIS UPS Room.
During an interview at 2 p.m., the Assistant Director of Plant Operations confirmed the findings.

No Description Available

Tag No.: K0047

.
Outpatient Services Building 2-2809 Olive Highway

2. On 8/5/15, at 1:20 p.m., the facility was observed with exit signs with battery back up throughout the building. A review of the exit sign logs indicated no 90 minutes annual tests had been performed in the past 12 months. During an interview at 1:22 p.m., the Assistant Director of Plant Operations stated that the facility was not aware of the requirement for the 90 minutes annual test for the exit signs.

No Description Available

Tag No.: K0047

Based on observation, document review and interview, the facility failed to maintain its emergency exit signs. This was evidenced by a lack of documentation for annual testing of its battery-powered emergency exit signs. This affected two of two floors in the Main Hospital and three of three floors in Outpatient Services Building 2. Failure to maintain and test emergency exit signs could potentially result in delayed evacuation and/or injury in the event of a loss of power.

NFPA 101, 2000
19.2.10.1 Means of egress shall have signs in accordance with Section 7.10.

39.2.10 Marking of Means of Egress. Means of egress shall have signs in accordance with Section 7.10.

7.10.9.2 Testing. Exit signs connected to or provided with a battery-operated emergency illumination source, where required in 7.10.4, shall be tested and maintained in accordance with 7.9.3
7.9.3 Periodic Testing of Emergency Lighting Equipment. A functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds. An annual test shall be conducted on every required battery-powered emergency lighting system for not less than 11/2 hours. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.

Findings:

During tour, document review, and interview with Staff, the emergency exit signs were observed and documents were requested.

Main Hospital

1. On 8/4/15, at 10:50 a.m., the facility was observed with exit signs with battery back up throughout the building. A review of the exit sign logs indicated that no 90 minutes annual tests had been performed in the past 12 months. During an interview at 11 a.m., the Assistant Director of Plant Operations confirmed the findings.

No Description Available

Tag No.: K0050

.
Outpatient Services Building 2-2809 Olive Highway

2. On 8/6/15, at 9:10 a.m., three of five suites (Suite 110, 120, 230) failed to provide documentation for fire drills in the past 12 months. During an interview at 9:15 a.m., the Assistant Director of Plant Operations confirmed that there had been no drills.

3. On 8/6/15, at 1:20 p.m., in suit 120, one of four staff members did not know how to use a portable fire extinguisher.

Outpatient Building 3-2450 Oro Dam Blvd.

4. On 8/5/15, at 1:25 p.m., there was no fire drill documentation provided for the past 12 months. During an interview at 1:30 p.m., the Assistant Director Plant Operation confirmed that there had been no drills.

No Description Available

Tag No.: K0050

Based on document review and interview, the facility failed to train all staff in fire safety procedures. This was evidenced by staff that did not know the meaning of the Acronym R.A.C.E., where the nearest fire alarm pull station was, or how to use a fire extinguisher. This was also evidenced by the failure to conduct fire drills at Outpatient Services Building 3 and in three of five suites in the Outpatient Services Building 2. This could potentially result in staff members being untrained and unaware of their roles and responsibilities during a fire.

NFPA 101, 2000
39.7.1 Drills. In any business occupancy building occupied by more than 500 persons or more that 100 persons above or below the street level, employees and supervisory personnel shall be periodically instructed in accordance with section 4.7 and shall hold drills periodically where practicable.

39.7.2 Designated employees of business occupancies shall be periodically instructed in the use of portable fire extinguishers.

Findings:

During document review and interview with Staff, the fire drill documents were requested and interviews were performed.

Main Hospital

1. On 8/6/15, between 9:30 a.m. and 10 a.m., three of five staff members were interviewed in Dietary, Cardiopulmonary, Emergency Services, and Registration/Admitting Departments. One Staff in Dietary and one Staff in Cardiopulmonary did not know what RACE stood for for, and one Staff in Registration/Admitting did not know where the nearest fire alarm pull station was.

No Description Available

Tag No.: K0051

Based on observation and interview, the facility failed to maintain fire alarm system components. This was evidenced by one fire alarm chime that failed to emit an audible sound. This affected one of two floors at the Main Hospital and could potentially result in a delayed notification of fire.

NFPA 101, 2000
19.3.4.1 General. Health care occupancies shall be provided with a fire alarm system in accordance with section 9.6

39.3.4.1 General. A fire alarm system in accordance with section 9.6 shall be provided in any business occupancy where any one of the following condition exists: (1) the building is two or more stories in height above the level of exit discharge. (2) the occupancy is subject to 100 or more occupants above or below the level of exit discharge. (3) The occupancy is subject to 1000 or more total occupants.

9.6.1.4 A fire alarm system required for life safety shall be installed, tested, and maintained in accordance with the applicable requirements of NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm Code, unless an existing installation, which shall be permitted to be continued in use, subject to the approval of the authority having jurisdiction.
9.6.3.8 Audible alarm notification appliances shall be of such character and so distributed as to be effectively heard above the average ambient sound level occurring under normal conditions of the occupancy.

Findings:

During a tour of the facility with Staff on 8/4/15, the fire alarm system was observed and Staff was interviewed.

Main Hospital

At 9:59 a.m., chime/strobe N13-4 in the Laboratory failed to chime during testing. During an interview at 10 a.m., the Assistant Director of Plant Operations confirmed that the device did not chime but made a clicking sound.

No Description Available

Tag No.: K0052

.
Outpatient Services Building 2-2809 Olive Highway

3. On 8/5/15, at 1:20 p.m., the document titled, "Quarterly Fire Inspection Reports 2015," was incomplete. In the third quarter on 7/21/15, the document indicated that there was no access to two smoke detectors in the North and South Electrical Rooms on the second floor. The report also indicated that a duct detector on the third floor was not tested. Plant Operation Staff 1 confirmed a South Electrical Room duct detector on the third floor was not tested.

No Description Available

Tag No.: K0052

Based on document review and interview, the facility failed to maintain the fire alarm system. This was evidenced by incomplete testing records for the annual fire alarm inspection report . This affected two of two floors at the Main Hospital and two of three floors at Outpatient Services Building 2. This could result in a delay in notification in the event of a fire.

NFPA 101, 2000
19.3.4.1 General. Health care occupancies shall be provided with a fire alarm system in accordance with section 9.6
19.3.6.3.7 Door frames shall be labeled, shall be of steel construction, or shall be other materials in compliance with the provisions of 8.2.3.2.1

8.2.3.2.1 Doors assemblies in fire barriers shall be if an approved type with the appropriate fire protection rating for the location in which they are installed and shall comply with the following: (a) Fire doors shall be installed in accordance with NFPA 80, Standard for Fire Doors and Fire Windows.

39.3.4.1 General. A fire alarm system in accordance with section 9.6 shall be provided in any business occupancy where any one of the following condition exists: (1) the building is two or more stories in height above the level of exit discharge. (2) the occupancy is subject to 100 or more occupants above or below the level of exit discharge. (3) The occupancy is subject to 1000 or more total occupants.

9.6.1.4 A fire alarm system required for life safety shall be installed, tested, and maintained in accordance with the applicable requirements of NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm Code, unless an existing installation, which shall be permitted to be continued in use, subject to the approval of the authority having jurisdiction.

NFPA 72, 1999
1-6.3 Records. A complete, unalterable record of the tests and operations of each system shall be kept until the next test and for 1 year thereafter. The record shall be available for examination and, if required, reported to the authority having jurisdiction. Archiving of records by any means shall be permitted if hard copies of the records can be provided promptly when requested.
Exception: If off-premises monitoring is provided, records of all signals,
tests, and operations recorded at the supervising station shall be
maintained for not less than 1 year.

7-5.2.2 A permanent record of all inspections, testing, and maintenance shall be provided that includes the following information regarding tests and all the applicable information requested in Figure 7-5.2.2.
(1) Date
(2) Test frequency
(3) Name of property
(4) Address
(5) Name of person performing inspection, maintenance, tests, or combination thereof, and affiliation, business address, and telephone number
(6) Name, address, and representative of approving agency(ies)
(7) Designation of the detector(s) tested, for example, " Tests performed in accordance with Section __________. "
(8) Functional test of detectors
(9) *Functional test of required sequence of operations
(10) Check of all smoke detectors
(11) Loop resistance for all fixed-temperature, line-type heat detectors
(12) Other tests as required by equipment manufacturers
(13) Other tests as required by the authority having jurisdiction
(14) Signatures of tester and approved authority representative
(15)Disposition of problems identified during test (for example, owner notified, problem corrected/successfully retested, device abandoned in place)

NFPA 80, 1999
15-2.4.3 All horizontal or vertical sliding and rolling fire doors shall be inspected and tested annually to check for proper operation and full closure. Resetting of the release mechanism shall be done in accordance with the manufacturer ' s instructions. A written record shall be maintained and shall be made available to the authority having jurisdiction.

Findings:

During document review and interview with Staff, the annual fire alarm inspection reports were reviewed.

Main Hospital

1. On 8/4/15, at 10:50 a.m., the document titled, "Alarm and Detection Report," dated 11/5/14, was incomplete. The report indicated three of 40 duct detectors were not tested. On page 8 of 8 of the report, it indicated that the duct detector in Medical Equipment Room was blocked from access and that the duct detector could not be reached. During an interview at 11 a.m., Plant Operation Staff 2 stated that three duct detectors in the Intensive Care Unit (ICU) were not tested.

2. On 8/4/15, at 10:51 a.m., the facility was observed with three roll down fire doors in the Obstetrics and Gynecology (OB), Private Branch Exchange (PBX), and the Laboratory. No records were provided indicating that the rolling fire doors were tested annually for proper operation. During an interview at 11 a.m., the Assistant Director of Plant Operations confirmed the finding.

No Description Available

Tag No.: K0054

Based on document review and interview, the facility failed to maintain its smoke detectors. This was evidenced by incomplete documentation for smoke detector sensitivity testing and by the failure to have the smoke detectors tested for sensitivity by a certified and trained person. This affected two of two floors in the Main Hospital and could result in delayed notification of a fire due to a malfunctioning or dirty smoke detector.

NFPA 101, 2000
19.3.4.1 General. Health care occupancies shall be provided with a fire alarm system in accordance with section 9.6
9.6.1.4 A fire alarm system required for life safety shall be installed, tested, and maintained in accordance with the applicable requirements of NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm Code, unless an existing installation, which shall be permitted to be continued in use, subject to the approval of the authority having jurisdiction.

NFPA 72, 1999
7-1.2.2 Service personnel shall be qualified and experienced in the inspection, testing, and maintenance of fire alarm systems. Examples of qualified personnel shall be permitted to include, but shall not be limited to, individuals with the following qualifications:
(1) Factory trained and certified
(2) National Institute for Certification in Engineering Technologies
fire alarm certified
(3) International Municipal Signal Association fire alarm
certified
(4) Certified by a state or local authority
(5) Trained and qualified personnel employed by an organization
listed by a national testing laboratory for the servicing
of fire alarm systems.

7-3.2.1 Detector sensitivity shall be checked within 1 year after installation and every alternate year thereafter. After the second required calibration test, if sensitivity tests indicate that the detector has remained within its listed and marked sensitivity range (or 4 percent obscuration light gray smoke, if not marked), the length of time between calibration tests shall be permitted to be extended to a maximum of 5 years. If the frequency is extended, records of detector-caused nuisance alarms and subsequent trends of these alarms shall be maintained. In zones or in areas where nuisance alarms show any increase over the previous year, calibration tests shall be performed.
To ensure that each smoke detector is within its listed and marked sensitivity range, it shall be tested using any of the following methods:
(1) Calibrated test method
(2) Manufacturer's calibrated sensitivity test instrument
(3) Listed control equipment arranged for the purpose
(4) Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit where its sensitivity is outside its listed sensitivity range
(5) Other calibrated sensitivity test methods approved by the authority having jurisdiction
Detectors found to have a sensitivity outside the listed and marked sensitivity range shall be cleaned and recalibrated or be replaced.
Exception No. 1: Detectors listed as field adjustable shall be permitted to be either adjusted within the listed and marked sensitivity range and cleaned and recalibrated, or they shall be replaced.
Exception No. 2: This requirement shall not apply to single station detectors referenced in 7-3.3 and table 7-2.2.
The detector sensitivity shall not be tested or measured using any device that administers an unmeasured concentration of smoke or other aerosol into the detector.

Findings:

During document review and interview with Staff on 8/4/15, the smoke detector sensitivity records were reviewed.

Main Hospital

1. At 1:26 p.m., the facility had approximately 166 smoke detectors. A review of the smoke detector sensitivity log indicated 11 of 166 smoke detectors were not tested for sensitivity. During an interview at 1:32 p.m., the Director of Plant Operations stated that some areas were not accessible.

2. At 1:32 p.m., a review of the smoke detector sensitivity log indicated that the facility performed in-house smoke detector sensitivity testing. During an interview at 1:35 p.m., Director of Plant Operations stated that Plant Operation Staff 2 was trained but not certified.

No Description Available

Tag No.: K0061

Based on observation, testing, and interview, the facility failed to ensure that the automatic sprinkler system had control valves that were supervised. This was evidenced by three sprinkler system backflow preventer-valve assemblies that were not supervised. This affected two of two floors in the Main Hospital and could potentially result in staff being unaware of a loss of sprinkler protection if the automatic sprinkler system water were shut off.

NFPA 101, 2000
19.3.5.2 Where this code permits exceptions for fully sprinklered buildings or smoke compartments, the sprinkler system shall meet the following criteria: (1) it shall be in accordance with section 9.7. (2) it shall be electrically connected to the fire alarm system. (3) it shall be fully supervised. Exception: in Type I and Type II construction, where approved by the authority having jurisdiction, alternative protection measures shall be permitted to be substituted for sprinkler protection in specified areas where the authority having jurisdiction has prohibited sprinklers, without causing a building to be classified as nonsprinklered.

9.7.2.1* Supervisory Signals. Where supervised automatic sprinkler systems are required by another section of this Code, supervisory attachments shall be installed and monitored for integrity in accordance with NFPA 72, National Fire Alarm Code, and a distinctive supervisory signal shall be provided to indicate a condition that would impair the satisfactory operation of the sprinkler system. Monitoring shall include, but shall not be limited to, monitoring of control valves, fire pump power supplies and running conditions, water tank levels and temperatures, tank pressure, and air pressure on dry-pipe valves. Supervisory signals shall sound and shall be displayed either at a location within the protected building that is constantly attended by qualified personnel or at an approved, remotely located receiving facility.
9.7.2.2. Alarm Signal Transmission. Where supervision of the automatic sprinkler systems is provided in accordance with another provision of this code, waterflow alarms shall be transmitted to an approved, proprietary alarm receiving facility, a remote station, a central station, or the fire department. Such connection shall be in accordance with 9.6.1.4.

Findings:

During a tour of the facility, testing, and interview with Staff 8/5/15, the automatic sprinkler system backflow shut off valves were observed and tested.

Main Hospital

1. At 9:01 a.m., the southwest sprinkler system backflow shut-off valve assembly was chained and locked in an open position. The valves were closed and there was no tamper alarm and/or supervisory signal that was initiated at the fire alarm control panel (FACP) room/Private Branch Exchange (PBX) office, or at an off site monitoring station. The control valve assembly was not equipped with a tamper switch. During an interview at 9:05 a.m., the Assistant Director of Plant Operations and Plant Operation Staff 1 confirmed that no signals were received at the FACP or PBX.

2. At 9:11 a.m., the northwest sprinkler system backflow shut-off valve assembly was chained and locked in an open position. The valves were closed and there was no tamper alarm and/or supervisory signal that was initiated at the FACP Room, the PBX office, or at an off site monitoring station. The control valve assembly did not have a tamper switch on it. During an interview at 9:12 a.m., the Assistant Director of Plant Operations and Plant Operation Staff 1 confirmed that there were no signals received at the FACP or PBX.

3. At 9:15 a.m., the northeast sprinkler system backflow shut-off valve assembly was chained and locked in an open position. The valves were closed and there was no tamper alarm and/or supervisory signal that was initiated at the FACP room, the PBX office, or at an off site monitoring station. The control valve assembly did not have a tamper switch on it. During an interview at 9:17 a.m., Assistant Director of Plant Operations and Plant Operation Staff 1 confirmed that there were no signals received at the FACP or PBX.

No Description Available

Tag No.: K0062

.
Outpatient Services Building 2-2809 Olive Highway

6. On 8/5/15 at 9:46 a.m., a corridor sprinkler was observed with a green liquid substance on the deflector plate in Suite 110.

7. On 8/5/15 at 9:47 a.m., a sprinkler head in the Supply Closet in Suite 120 had a box that was within 12 inches of the deflector.

8. On 8/5/15 at 10:06 a.m., the Inspector Test Valve (ITV) on the first floor took longer than 90 seconds to alarm. The ITV took one minute and forty seconds to activate the fire alarm system. Plant Operations Staff 2 confirmed.

9. On 8/5/15 at 1:25 p.m., the facility was missing two quarterly sprinkler inspection tests for the third and fourth quarter of 2014. Assistant Director of Plant Operations and Plant Operation Staff 2 confirmed the findings.

Outpatient Building 3-2450 Oro Dam Blvd.

10. On 8/5/15, at 10:42 a.m., the spare sprinkler box that was located between the two Sprinkler Risers was missing the special sprinkler head wrench.

11. On 8/5/15, at 10:50 a.m., one of two Post Indicator Valves (PIV) was observed without a wrench to operate the valve and without a lock to prevent tampering. The valve was supervised and functioned properly when tested.

No Description Available

Tag No.: K0062

Based on observation, document review, and interview, the facility failed to maintain the automatic sprinkler system and its components. This was evidenced by foreign material on sprinkler heads, less than 18 inches of clearance below the sprinkler deflector, a missing sprinkler wrench, two missing fire department connection (FDC) caps, missing quarterly sprinkler testing and inspections, an unlocked post indicator valve with a missing wrench, and three annual backflow inspection tests that had failed. This affected two of two floors at the Main Hospital, three of three floors at the Outpatient Services Building 2, and one of one floor at the Outpatient Services Building 3. This could result in the sprinkler system failing to function as designed and a delay in notification in the event of a fire.

NFPA 101, 2000
19.7.6 Maintenance and Testing (see 4.6.12)
4.6.12 Maintenance and Testing. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provision of this code, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with applicable NFPA requirements or as directed by the authority having jurisdiction.

39.1.5.2 For purpose of the design of an automatic sprinkler system, a business occupancy shall be classified as a light hazardous occupancy in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.
39.3.4.1 General. A fire alarm system in accordance with section 9.6 shall be provided in any business occupancy where any one of the following condition exists: (1) the building is two or more stories in height above the level of exit discharge. (2) the occupancy is subject to 100 or more occupants above or below the level of exit discharge. (3) The occupancy is subject to 1000 or more total occupants.

9.6.1.4 A fire alarm system required for life safety shall be installed, tested, and maintained in accordance with the applicable requirements of NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm Code, unless an existing installation, which shall be permitted to be continued in use, subject to the approval of the authority having jurisdiction.

NFPA 13, 1999
3-2.9.2 A special sprinkler wrench shall also be provided and kept in the cabinet to be used in the removal and installation of sprinklers
5-5.6 The clearance between the deflector and the top of storage shall be
18 in. (457 mm) or greater.
12-1 General. A sprinkler system installed in accordance with this standard shall be properly inspected, tested, and maintained in accordance with NFPA 25, Standard for the inspection, testing, and maintenance of water-based fire protection systems, to provide at least the same level of performance and protection as designed.

NFPA 25, 1998
9-3.3.2* The valve inspection shall verify that the valves are in the following condition:
(a) In the normal open or closed position
(b) *Properly sealed, locked, or supervised
(c) Accessible
(d) Provided with appropriate wrenches
(e) Free from external leaks
(f) Provided with appropriate identification

Chapter 2 Sprinkler Systems, 2-1 General. This chapter provides the minimum requirements for the routine inspection, testing, and maintenance of sprinkler systems. Table 2-1 shall be used to determined the minimum required frequencies for inspections, testing, and maintenance. Exception: Valves and fire department connections shall be inspected, tested, and maintained in accordance with Chapter 9.
1-8*. Records of inspections, tests, and maintenance of the system and its components shall be made available to the authority having jurisdiction upon request. Typical records include, but are not limited to, valve inspections; flow, drain, and pump tests; and trip tests of dry pipe, deluge, and pre-action valves.
1-8.1 Records shall indicate the procedure performed (e.g., inspection, test, or maintenance), the organization that performed the work, the results, and the date.
2-2.1.1*. Sprinklers shall be inspected from the floor level annually. Sprinklers shall be free of corrosion, foreign materials, paint, and physical damage and shall be installed in the proper orientation (e.g., upright, pendant, or sidewall). Any sprinkler shall be replaced that is painted, corroded, damaged, loaded, or in the improper orientation.
2-2.2 Sprinkler pipe and fittings shall be inspected annually from the floor level. Pipe and fittings shall be in good condition and free of mechanical damage, leakage, corrosion, and misalignment. Sprinkler piping shall not be subjected to external loads by materials either resting on the pipe or hung from the pipe.
2-2.6 Alarm Devices. Alarm devices shall be inspected quarterly to verify that they are free of physical damage.
2-3.3* Alarm Devices. 2 Waterflow alarm devices including,but not limited to, mechanical water motor gongs, vane-type waterflow devices, and pressure switches that provide audible or visual signals shall be tested quarterly.
9-6.2.1 All backflow preventers installed in fire protection system piping shall be tested annually in accordance with the following:
(a) a forward flow test shall be conducted at the system demand, including hose stream demand, where hydrants or inside hose stations are located downstream of the backflow preventer.
(b) a backflow performance test, as required by the authority having jurisdiction, shall be conducted at the completion of the forward flow test.
9-7.1 Fire department connections shall be inspected quarterly. The inspection shall verify the following:
(a) The fire department connections are visible and accessible.
(b) Couplings or swivels are not damaged and rotate smoothly.
(c) Plugs or caps are in place and undamaged.
(d) Gaskets are in place and in good condition.
(e) Identification signs are in place.
(f) The check valve is not leaking.
(g) The automatic drain valve is in place and operating properly.

NFPA 72, 1999
2-6.2 Initiation of the alarm signal shall occur within 90 sec of waterflow at the alarm-initiating device when flow occurs that is equal to or greater than that from a single sprinkler of the smallest orifice size installed in the systems. Movement of water due to waste, surges, or variable pressure shall not be indicated.
3-8.3.2.5.2 The integrity of each fire suppression system actuating device and its circuit shall be supervised in accordance with 1-5.8.1 and with other applicable NFPA standards.


Findings:
During a tour of the facility, document review, and interview with Staff, the automatic sprinkler system and components were observed and tested, and documents were requested.
Main Hospital
1. On 8/3/15, at 9:28 a.m., a sprinkler in the Rehab Office Storage had a black lunch cooler that was located within 10 inches of the deflector plate.
2. On 8/3/15, at 9:53 a.m., a sprinkler in the Maternity Workroom had a surgical glove box that was within 12 inches of the deflector plate.
3. On 8/3/15, at 11:46 a.m., two sprinkler heads in the Kitchen Dishwashing area were observed with a dark, thick greaselike buildup.
4. On 8/4/15, at 11:30 a.m., the facility had five Inspector Test Valves (ITV) throughout the building. Testing was performed in house. The Inspector's Test Valves were located in the Laboratory, in X-ray, in the Canopy-Admitting, Unit 1-2, and Mechanical Room 3. A review of the quarterly testing records indicated that seven quarterly inspections were not performed for the ITV valves in a 12 month period. The Laboratory flow test was missing for the third quarter of 2014, the X-ray flow test was missing for the fourth quarter of 2014, the Canopy-Admitting flow test was missing for the second quarter of 2015 and fourth quarter of 2014, Unit 1-2 was missing for the first quarter of 2015 and third quarter of 2014, and Mechanical Room 3 was missing for the second quarter of 2015. During an interview at 12 p.m., Plant Operations Staff 2 confirmed the findings.
5. On 8/5/15, at 12:55 p.m., the facility had three sprinkler system OS&Y double back flow valves assemblies. A review of the inspection reports dated 6/9/15, indicated that a total of six back flow valves failed. They were located in Southwest, Northeast, and Northwest areas of the facility. During an interview at 1 p.m., the Assistant Director of Plant Operation and Director of Plant Operation confirmed the findings.

No Description Available

Tag No.: K0064

Based on observation, the facility failed to maintain its portable fire extinguishers. This was evidenced by fire extinguishers that were recessed into the wall that were obscured from view and by fire extinguishers that were obstructed from access. This affected two of two floors in the Main Hospital and could result in a delay in access to the fire extinguisher in the event of a fire.

NFPA 101, 2000
19.3.5.6 Portable Fire Extinguishers shall be provided in all health care occupancies in accordance with 9.7.4.1
9.7.4 Manual Extinguishing Equipment
9.7.4.1 Where required by the provision of another section of this code, portable fire extinguishers shall be installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguisher.

21.3.5.2 Portable fire extinguishers shall be provided in ambulatory health care facilities in accordance with 9.7.4.1
9.7.4.1 Where required by the provision of another section of this code, portable fire extinguishers shall be installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.

NFPA 10, 1998
1-6.6* Fire extinguishers shall not be obstructed or obscured from view. Exception: In large rooms, and in certain locations where visual obstruction cannot be completely avoided, means all be provided to indicate the location.

1-6.12 Fire extinguishers mounted in cabinets or wall recesses shall be placed so that the fire extinguisher operating instructions face outward. The location of such fire extinguishers shall be marked conspicuously. (See 1 6.6.)

Findings:

During a tour of the facility with Staff on 8/3/15, the portable fire extinguishers were observed.

Main Hospital

1. At 9:25 a.m., recessed cabinet fire extinguisher number 46 on the first floor by the Linen Storage Room was obscured from view. There was no sign marking its location.

2. At 9:25 a.m., cabinet fire extinguisher 54 on the first floor in the South Mechanical Room was obstructed from access by a vacuum pump and other large equipment. The items were stationed within one inch of the fire extinguisher.

3. At 10:10 a.m., recessed cabinet fire extinguisher number 41 on the first floor by Elevator Door 4-16 was obscured from view. There was no sign marking its location.

4. At 10:16 a.m., recessed cabinet fire extinguisher number 43 on the first floor by Room 114 was obstructed by four wheelchairs that prevented direct access to the extinguisher.

5. At 10:20 a.m., recessed cabinet fire extinguisher number 44 on the first floor in Unit 1 was obscured from view and was also obstructed from access by a metal rolling ladder that was stationed within one inch in front of it. There was no sign marking its location.

6. At 10:21 a.m., recessed cabinet fire extinguisher number 45 on the first floor in Unit 1 was obscured from view. There was no sign marking its location.

7. At 10:24 a.m., recessed cabinet fire extinguisher number 42 on the first floor in Unit 1 was obscured from view. There was no sign marking its location. The fire extinguisher was also obstructed from access by a janitor's cart that was stationed within one inch of the front of it.

8. At 10:30 a.m., recessed cabinet fire extinguisher number 47 on the second floor behind elevator fire door 7-17 was obscured from view. There was no sign marking its location.

9. At 10:31 a.m., recessed cabinet fire extinguisher number 55 on the second floor in Unit 2 was obscured from view. There was no sign marking its location.

10. At 10:35 a.m., recessed cabinet fire extinguisher number 53 on the second floor in Unit 2 was obscured from view. There was no sign marking its location.

11. At 10:37 a.m., recessed cabinet fire extinguisher number 52 on the second floor in Unit 2 was obscured from view. There was no sign marking its location.

12. At 10:40 a.m., recessed cabinet fire extinguisher number 51 on the second floor in the Intensive Care Unit (ICU) was obscured from view. There was no sign marking its location.

13. At 10:41 a.m., recessed cabinet fire extinguisher number 50 on the second floor in ICU was obscured from view. There was no sign marking its location.

14. At 10:46 a.m., recessed cabinet fire extinguisher number 49 on the second floor in Surgery was obscured from view. There was no sign marking its location.

15. At 10:51 a.m., recessed cabinet fire extinguisher number 48 on the second floor in the Surgery was obscured from view. There was no sign marking its location.

16. At 11:02 a.m., recessed cabinet fire extinguisher number 79 on the second floor in the Lab was obstructed from access by a trash bin that was stationed within one inch of it. There was no sign marking its location.

17. At 11:40 a.m., recessed cabinet fire extinguisher number 12 on the second floor in the Emergency Department (ER) was obscured from view. There was no sign marking its location.

18. At 12:55 p.m., recessed cabinet fire extinguisher number 3 on the second floor in the Ambulatory Care Service (ACS) was obscured from view and was also obstructed by a tall IV pole that was stationed in front of it. There was no sign marking its location.

No Description Available

Tag No.: K0076

Based on observation, the facility failed to maintain its compressed gas cylinders. This was evidenced by an unsecured cylinder. This affected one of two floors in the Main Hospital and could result in an increased risk or acceleration of a fire.

4-3.1.1.1 Cylinder and Container Management. Cylinders in service and in storage shall be individually secured and located to prevent falling or being knocked over.
4-3.5.2.1 (27) Freestanding cylinders shall be properly chained or supported in a proper cylinder stand or cart.

Findings:

During a tour of the facility with Staff on 8/3/15, the non-flammable gas was observed.

Main Hospital

1. At 11:45 a.m., a carbon dioxide cylinder was observed freestanding on the floor in the Kitchen Dry Storage.

No Description Available

Tag No.: K0077

Based on observation, the facility failed to maintain access to its medical gas shut off valves. This was evidenced by equipment placed in front of emergency oxygen shut off valves. This affected one of two floors in the Main Hospital and could delay personnel from shutting off oxygen during an emergency.

NFPA 101, 2000
19.3.2.4 Medical Gas.
Medical gas storage and administration areas shall be protected in accordance with NFPA 99, Standard for Health Care Facilities.

NFPA 99,1999
4-3.1.2.3 Gas Shutoff Valves, Shutoff valves accessible to other than authorized personnel shall be installed in valve boxes with frangible or removable windows large enough to permit manual operation of valves.
Exception: Shutoff valves for use in certain areas, such as psychiatric or pediatric, shall be permitted to be secured to prevent inappropriate access.
(i) Shutoff Valves (Manual). Manual shutoff valves in boxes shall be installed where they are visible and accessible at all times. The boxes shall not be installed behind normally open or normally closed doors, or otherwise hidden from plain view.

Findings:

During a tour of the facility with Staff 8/3/15, the piped-in medical gas shut off valves were observed.

Main Hospital

1. At 10:50 a.m., the shut off valve near Operation Room (OR) 2 in the Surgery Unit was obstructed by a cart, two instrument holders, a tall supply cart, and a stints cart. The items impeded access to the shut off valve.

2. At 10:55 a.m., the shut off valve by OR 1 in the Surgery Unit was obstructed by a metal supply cart.

3. At 11:37 a.m., the shut off valve in the Emergency Department (ER) was obstructed by a x-ray machine that was stationed within one inch of the front of it.

4. At 11:41 a.m., the shut off valve in the Respirator Care Workroom had a tool box that was stationed within one inch of the front of it.

No Description Available

Tag No.: K0078

Based on document review and interview, the facility failed to maintain and
provide a written policy for the relative humidity (RH). This was evidenced by failure to following the policy for the RH and failure to document the RH level. This affected one of two floors in the Main Hospital and could result in an increased risk of fire.

Findings:

During document review and interview, the RH policy was requested and reviewed.

Main Hospital

1. On 8/4/15, at 1:35 p.m., the Surgery Unit had five operating rooms. (OR). The relative humidity (RH) policy indicated that the RH would be maintained at 55%-65%." A review of the RH log indicated that in the last six month period (January-July 2015), the RH level went as low as 18% and as high at 76%. During an interview on 8/5/15 at 1:26 p.m., the Surgery Administrative Staff stated that Plant Operations personnel made the adjustments to the RH when needed. Staff further stated there was no log recording the adjustments that have been made. During an interview at 1:30 p.m., Director of Plant Operations stated that they do not make adjustments to the RH levels.

2. On 8/6/15, at 9:10 a.m., the Ambulatory Care Services Unit (ACS) had five Endoscopy Rooms (rooms 601, 603, 604, 606, and 607) and one eye laser procedure room. The ACS Unit failed to provide a written policy or maintain a log for RH levels. During an interview at 9:20 a.m., Director of Plant Operations stated they did not have a policy or a log for the RH.

No Description Available

Tag No.: K0104

Based on observation, the facility failed to maintain its smoke barrier walls free from penetrations. This was evidenced by penetrations in four walls. This affected two of two floors in the Main Hospital and could result in the spread of fire and/or smoke.

NFPA 101, 2000
19.3.7.3 Any required smoke barrier shall be constructed in accordance with section 8.3 and shall have a fire resistance rating of not less than 1/2 hours.

8.3.6.1: Pipes, conduits, ducts, cables, wires, air ducts, pneumatic tube and ducts, and similar building service equipment that pass through floors and smoke barriers shall be protected as follows:
(1) The space between the penetrating item and the smoke barrier shall meet one following conditions:
(a) It shall be filled with a material that is capable of maintaining the smoke resistance of the smoke barrier.
(b) It shall be protected by an approved device that is designed of the specific purpose.
(2) Where the penetrating item uses a sleeve to penetrate the smoke barrier, the sleeve shall be solidly set in the smoke barrier, and the space between the item and the sleeve shall meet one of the following conditions:(a) It shall be filled with a material that is capable of maintaining the smoke resistance of the smoke barrier

Findings:

During a tour of the facility with Staff on 8/3/15, the smoke barrier walls were observed.

Main Hospital

1. At 1:26 p.m., there was an approximately four inch by four inch penetration with wires traveling through the smoke barrier wall in Unit 1 near fire door 2-14.

2. At 1:27 p.m., there was an approximately four inch by four inch penetration with wires traveling through the smoke barrier wall in the Unit 1 Conference Room by fire door 2-12.

3. At 1:40 p.m., there was an approximately three inch penetration with wires traveling through the wall in the west smoke barrier wall by Dietary.

4. At 1:43 p.m., there was an approximately two inch penetration with wires traveling through the wall in the east smoke barrier wall by Dietary.

No Description Available

Tag No.: K0144

Based on document review and interview, the facility failed to test its diesel generators. This was evidenced by missing documentation for three monthly full load tests in the past 12 months. This affected two of two smoke compartments and could potentially result in a generator failure during an emergency.

NFPA 101, 2000
19.7.6 Maintenance and Testing (see 4.6.12)
4.6.12 Maintenance and Testing. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provision of this code, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with applicable NFPA requirements or as directed by the authority having jurisdiction.

NFPA 110, 1999
6-4.1* Level 1 and Level 2 EPSSs, including all appurtenant components, shall be inspected weekly and shall be exercised under load at least monthly.

Findings:

During document review and interview with Staff on 8/4/15, the generator records were requested.

1. At 11:30 a.m., the facility had two emergency diesel-powered generators. The north generator was rated for 250 kilowatts (KW) and the south generator was rated 200 KW. The north 250KW generator supplies emergency back-up power to Unit 3, Obstetrics and Gynecology (OB), Ambulance, Dietary, Emergency Department, X-ray, and Pharmacy. The south 200KW generator supplies emergency back-up power to Surgery, the Intensive Care Unit (ICU), and Unit 2 and Unit 1. The generator log titled, "Weekly Operational Test Exercise Log", did not indicate that a full load test was done in January 2015 and November 2014 for the north generator. There was no documentation provided indicating that the full load test was done for the south generator in August 2014. During an interview at 12 p.m., Assistant Director of Plant Operations confirmed the findings.

No Description Available

Tag No.: K0147

.
Outpatient Services Building 2-2809 Olive Highway

27. On 8/5/15, at 9:50 a.m., in Suite 150 Infusion Room, there were three IV pumps and a patient monitor plugged into a power strip at Station A, two IV pumps were plugged into a power strip at Station B, two IV pumps and a patient monitor were plugged into a power strip at Station C, two IV poles were plugged into a power strip at Station D, and four IV pumps and a patient monitor were plugged into a power strip at Station E.

28. On 8/5/15, at 9:56 a.m., a computer charger was plugged into a extension card in the Suite 230 Break Room.

No Description Available

Tag No.: K0147

Based on observation, the facility failed to maintain its electrical wiring and connections. This was evidenced by the use of extension cords, power strips chained together, power strips suspended above the floor, obstructed electrical panels, and power strips being used for medical devices and high power equipment. This affected two of two floors at the Main Hospital and one of three floors at Outpatient Services Building 2. This could could potentially result in an electrical fire.

NFPA 101, 2000
19.5.1 Utilities. Utilities shall comply with the provisions of section 9.1
39.5.1 Utilities. Utilities shall comply with the provisions of section 9.1

9.1.2 Electric. Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code, unless existing installations, which shall be permitted to be continued in service, subject to approval by the authority having jurisdiction.

NFPA 70, 1999
110-12 Mechanical Execution of Work. Electrical equipment shall be installed in a neat and workmanlike manner.
(c) Integrity of Electrical Equipment and Connections. Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues. There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment such as parts that are broken; bent; cut; or deteriorated by corrosion, chemical action, or overheating.

110-26 Spaces About Electrical Equipment. Sufficient access and working space shall be provided and maintained about all electrical equipment to permit ready and safe operation and maintenance of such equipment. Enclosures housing electrical apparatus that are controlled by lock and key shall be considered accessible to qualified persons.
(1) Depth of Working Space. The depth of the working space in the direction of access to live parts shall not be less than indicated in Table 110-26(a). Distances shall be measured from the live parts if such are exposed or from the enclosure front or opening if such are enclosed.
(2) Width of Working Space. The width of the working space in front of the electric equipment shall be the width of the equipment or 30 in.
(762 mm), whichever is greater.

210-23 In no case shall the load exceed the branch-circuit ampere rating. An individual branch circuit shall be permitted to supply any load for which it is rated. A branch circuit supplying two or more outlets or receptacles shall supply only the loads specified according to its size as specified in (a) through (d) and as summarized in Section 210-24. A 15 or 20-ampere branch circuit shall be permitted to supply lighting units or other utilization, or a combination of both. The rating of any one cord and plug-connected utilization equipment shall not exceed 80 percent of the branch-circuit ampere rating. The total rating of utilization equipment fastened in place, other than lighting fixtures, shall not exceed 50 percent of the branch circuit ampere rating where lighting units, cord and plug-connected utilization equipment not fastened in place, or both, are also supplied.

400-8 Unless specifically permitted in Section 400-7, flexible cord and cables shall not be used for the following:
(1) As a substitute for the fixed wiring of a structure
(2) Where run through holes in walls, structural ceilings, suspended ceilings, dropped ceilings, or floors.
(3) Where run through doorways, windows, or similar openings
(4) Where attached to building surfaces
(5) Where concealed behind building walls, structural ceilings, suspended ceilings, dropped ceilings, or floors
(6) Where installed in raceways, except as otherwise permitted in this Code.

400-10. Flexible cords and cables shall be connected to devices and to fittings so that tension will not be transmitted to joints or terminals.

Findings:

During a tour of the facility with Staff, the electrical wiring and connections were observed.

1. On 8/3/15, at 9:21 a.m., in the Linen Storage on the first floor, there were three different areas that had power strips chained together. Two were near the the radio cabinet, and one was in the office.

2. On 8/3/15, at 9:28 a.m., a power strip was connected to a wall outlet adapter in the Rehabilitation Office below a desk.

3. On 8/3/15, at 9:29 a.m., in Rehabilitation at desk 3, a yellow extension cord was plugged into a three plugged adapter that had two pieces of computer equipment plugged in to it.

4. On 8/3/15, at 9:30 a.m., a red extension cord was plugged into a power strip that was connected to a floor scrubbing machine, in the South Mechanical Room.

5. On 8/3/15, at 9:36 a.m., in the Main Mechanical Room South, an orange extension cord was plugged into a lift, a bed was plugged into an orange extension cord that was connected to a power strip that was suspended off the floor, and a wall outlet was plugged into a wall outlet junction box.

6. On 8/3/15, at 9:40 a.m., an outlet adapter was plugged into an outlet in the Chiller area.

7. On 8/3/15, at 9:50 a.m., two power strips were suspended off the floor in the Pharmacy Office.

8. On 8/3/15, at 9:51 a.m., a refrigerator was plugged into a power strip in the Maternity Nursery work room.

9. On 8/3/15, at 10:05 a.m., a corridor camera was plugged into a blue extension cord in the Health Information Service (HIS) Operation Room.

10. On 8/3/15, at 10:10 a.m., in the Neurology Laboratory, a six plug wall adapter was connected to an orange extension card that was plugged into a power strip. Also, a six plug adapter was connected to a power strip that was plugged into another power strip.

11. On 8/3/15, at 10:15 a.m., in Unit 1, a power strip was mounted on a crash cart and a defibrillator machine was connected to it .

12. On 8/3/15, at 10:27 a.m., in the Unit 1 Conference Room, a refrigerator and microwave were plugged into a power strip that was suspended off the floor.

13. On 8/3/15, at 10:30 a.m., a red extension cord was plugged into a outlet in the Cardiopulmonary Office.

14. On 8/3/15, at 10:31 a.m., in Unit 2, a power strip was mounted on a crash cart and a defibrillator machine was connected to it.

15. On 8/3/15, at 10:45 a.m., in Surgery, electrical panel L2B Sect. 2 was obstructed by a supply cart that was stationed within one inch of it.

16. On 8/3/15, at 10:47 a.m., a power strip was connected to another power strip in the Surgery corridor.

17. On 8/3/15, at 11:10 a.m., electrical panel 9L was obstructed by two drop ceiling tiles and a box that was stationed within one inch of it in the Laboratory Electrical room.

18. On 8/3/15, at 11:13 a.m., a refrigerator was plugged into a red extension cord in the Main Laboratory.

19. On 8/3/15, at 11:15 a.m., three electronic items were plugged into a three plug adapter in the Micro Laboratory.

20. On 8/3/15, at 11:20 a.m., a data plate was loose and was hanging from the junction box in the X-ray Tech room.

21. On 8/3/15, at 11:21 a.m., in the Emergency Room (ER) Manager's Office, a microwave was plugged into a extension cord that was connected to a power strip. There was also a refrigerator that was plugged into a power strip.

22. On 8/3/15, at 11:22 a.m., electrical panel S was obstructed by a tall privacy curtain that was stationed within one inch of it in Emergency Room Biohazard Room.

24. On 8/3/15, at 11:30 a.m., a power strip was suspended off the floor with two items plugged into it in the ER by QRQ room.

25. On 8/3/15, at 11:41 a.m., a patient scanner and a patient monitor were plugged into a power strip in the ER room by the Staff Lounge.

26. On 8/3/15, at 11:55 a.m., in the Cafeteria, a coffee machine was plugged into a power strip and a refrigerator was plugged into a power strip.

Means of Egress - General

Tag No.: K0211

Based on observation, the facility failed to maintain the installation of its alcohol based hand rub dispensers (ABHR). This was evidenced by the mounting of an ABHR dispenser over or adjacent to an ignition source. This affected two of two floors in the Main Hospital. This could result in the ignition of fire.

Findings:

During a tour of the facility with Staff on 8/3/15, the alcohol based hand rub dispensers were observed.

Main Hospital

1. At 11:43 a.m., the ABHR dispenser in the Cardiology Treadmill Office was mounted 10 inches directly above a light switch.

2. At 12:58 p.m., the ABHR dispenser in Room 604 of the Ambulatory Care Service Unit (ACS) was mounted 10 inches directly above a light switch.

3. At 1:01 p.m., the ABHR dispenser in Unit 3 Overflow Storage was mounted 10 inches directly above a light switch.

LIFE SAFETY CODE STANDARD

Tag No.: K0012

Based on observation, the facility failed to maintain the integrity of the building construction. This was evidenced by unsealed penetrations in the walls and ceilings. This affected two of two floors in the Main Hospital and could potentially result in the spread of fire and smoke to other areas of the facility.

Findings:

During a tour of the facility with Staff on 8/3/15, the walls and ceilings were observed.

Main Hospital

1. At 9:30 a.m., there were three approximately 1/4 inch penetrations in the north wall next to fire extinguisher 54 in the Lift Equipment Room.

2. At 9:35 a.m., in the South Mechanical Room wall, there was an approximately 1/4 inch penetration around a one inch pipe, an approximately 1/4 inch penetration around a 1/2 inch pipe, and an approximately 1/4 inch penetration around a cord in the wall.

3. At 9:50 a.m., in the Maternity Ward Storage Room, there was an approximately eight foot by eight foot area of the southwest wall that was missing the sheet rock. There was also an approximately eight foot by two foot area of the ceiling that was missing the sheet rock.

4. At 10:10 a.m., a data outlet plate cover was shifted to one side exposing an approximately 1/4 inch penetration in the wall below a desk in the Neurology Lab.

5. At 10:31 a.m., a sprinkler head was missing an escutcheon ring exposing an approximately 1/2 inch penetration in the ceiling in Janitor Closet 9.

6. At 11:20 a.m., a sprinkler head was missing an escutcheon ring exposing an approximately 1/4 inch penetration around the pipe in the X-ray Office.

7. At 11:33 a.m., a sprinkler escutcheon ring was not flush to the ceiling exposing an approximately 1/4 inch penetration in the Emergency Registration Office.

8. At 11:40 a.m., a sprinkler escutcheon ring was shifted to one side exposing an approximately 1/4 inch penetration in the ceiling in the Respiratory Break Room.

9. At 11:51 a.m., a sprinkler head was missing an escutcheon ring exposing an approximately 1/2 inch penetration in the ceiling in the Kitchen Serving Line.

10. At 12:57 p.m., a sprinkler head was missing an escutcheon ring exposing an approximately 1/4 inch penetration in Room 604 of Ambulatory Care Service (ACS).

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observation, the facility failed to maintain its corridor doors. This was evidenced by four doors that were obstructed and one door that failed to latch. This affected two of two floors in the Main Hospital and could potentially result in the inability to contain a fire to a room.

NFPA 101, 2000
19.3.6.3.7 Door frames shall be labeled, shall be of steel construction, or shall be other materials in compliance with the provisions of 8.2.3.2.1

8.2.3.2.1 Doors assemblies in fire barriers shall be of an approved type with the appropriate fire protection rating for the location in which they are installed and shall comply with the following: (a) Fire doors shall be installed in accordance with NFPA 80, Standard for Fire Doors and Fire Windows.

NFPA 80, 1999
Door opening and the surrounding area shall be kept clear of anything that could obstruct or interfere with the free operation of the door.

Findings:

During a tour of the facility with Staff on 8/3/15, the corridor doors were observed.

Main Hospital

1. At 9:54 a.m., the roll down fire door at the Obstetrics and Gynecology (OB) Nurse's Station was obstructed from closing by a tissue box, a box of face masks, and a hole puncher.

2. At 10:23 a.m., the self-closing door to the State Office was held open by a rubber wedge.

3. At 11:07 a.m., the rolling down fire door in the Laboratory was obstructed by a tissue box, a brochure box, a bell, and a black basket.

4. At 11:16 a.m., the self-closing door to Micro Laboratory was held open by a piece of cardboard.

5. At 1 p.m., the self-closing door to the Unit 3 Overflow failed to latch.

LIFE SAFETY CODE STANDARD

Tag No.: K0022

Based on observation, the facility failed to mark access to exits. This was evidenced by the failure to provide visible exit signs at exit locations. This affected two of two floors in the Main Hospital, and had the potential to delay evacuation in the event of an emergency.

Findings:

During a tour of the facility with Staff on 8/3/15, the exit locations were observed.

Main Hospital

1. At 10:05 a.m., there was no exit sign above the exit door in the Obstetrics and Gynecology (OB) waiting room. There was a sign on the door identifying it as an emergency exit.

2. At 11 a.m., there was no exit sign above the exit stairway door on the second floor near the Dover elevator.

3. At 11:34 a.m., there was no exit sign above the Emergency Room (ER) waiting area door.

4. At 11:35 a.m., there was no exit sign above the ER patient registration door.

LIFE SAFETY CODE STANDARD

Tag No.: K0027

Based on observation, the facility failed to maintain the fire doors. This was evidenced by items that were stored in front of the fire doors. This affected two of two floors in the Main Hospital, and could result in a delay in egress in the event of an emergency.

NFPA 101, 2000
19.3.6.3.7 Door frames shall bed labeled, shall be of steel constructions, or shall be of other materials in compliance with the provision of 8.2.3.2.1
8.2.3.2.1 Door assemblies in fire barrier shall be of an approved type with the appropriate fire protection rating for the location in which they are installed and shall comply with the following: (A) the fire doors shall be installed in accordance with NFPA 80, Standard for Fire Doors and Fire Window. Fire doors shall be of a design that has been tested to meet the conditions of acceptance of NFPA 252, Standard Methods of Fire Test of Door Assemblies.

NFPA 80, 1999
2-4.1.4* All closing mechanisms shall be adjusted to overcome the resistance of the latch mechanism so that positive latching is achieved on each door operation.
15-1 This chapter covers the care and maintenance of fire doors and fire windows.
15-2.3 Prevention of Door Blockage.
15-2.3.1 Door openings and the surrounding areas shall be kept clear of anything that could obstruct or interfere with the free operation of the door.
15-2.3.3 Blocking or wedging of doors in the open position shall be prohibited.

Findings:

During a tour of the facility with Staff, the fire doors were observed.

Main Hospital

1. On 8/3/15, at 9:26 a.m., the right leaf fire door 4-22 on the first floor was obstructed by a large, tall yellow bin. The yellow bin was stationed within one inch of the door handle when the door was closed.

2. On 8/3/15, at 10:26 a.m., the right leaf fire door 1-13 on the first floor was obstructed by a north cart. The north cart was stationed within one inch of the door handle when the door was closed.

3. On 8/4/15, at 9:22 a.m., the left leaf of fire door 26-11 on the second floor near Dover corridor failed to latch .

4. On 8/4/15, at 9:32 a.m., the right leaf of fire door 7-20 on the second floor failed to latch.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

.
Outpatient Services Building 2-2809 Olive Highway

3. On 8/5/15, at 10 a.m., the door to the Biohazard Room in Suite 230 was not equipped with a self-closing device.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on observation, the facility failed to protect its hazardous areas. This was evidenced by doors to hazardous area enclosures that were not equipped with self-closing devices and by one door that failed to latch. This affected one of two floors at the Main Hospital and one of three floors at Outpatient Services Building 2. This could potentially result in the spread of fire and/or smoke to other areas of the facility.

NFPA 101, 2000
19.3.2.1 states that any hazardous areas shall have smoke-resisting doors that are self-closing or automatic-closing. Hazardous areas shall include, but shall not be restricted to, the following:
(1) Boiler and fuel-fired heater rooms
(2) Central/bulk laundries larger than 100 ft2 (9.3 m2)
(3) Paint shops
(4) Repair shops
(5) Soiled linen rooms
(6) Trash collection rooms
(7) Rooms or spaces larger than 50 ft2 (4.6 m2), including repair shops, used for storage of combustible supplies and equipment in quantities deemed hazardous by the authority having jurisdiction
(8) Laboratories employing flammable or combustible materials in quantities less than those that would be considered a severe hazard.

39.3.2.1 Hazardous areas including, but not limited to, areas used for general storage, boiler or furnace rooms, and maintenance shops that include woodworking and painting areas shall be protected in accordance with section 8.4

8.4.1.3 Doors in barriers required to have a fire resistance rating shall have a 3/4 hour fire protection rating and shall be self closing or automatic closing in accordance with 7.2.1.8.

Findings:

During a tour of the facility with Staff, the hazardous areas were observed.

Main Hospital

1. On 8/3/15, at 10:36 a.m., the door to the Soiled Linen Room near Room 205 failed to latch.

2. On 8/3/15, at 11:50 a.m., the Kitchen Dry Storage Room contained approximately three dozen cardboard boxes and paper packaging. The room was 225 square feet in size and the door was not equipped with a self-closing device.

LIFE SAFETY CODE STANDARD

Tag No.: K0038

Based on observation, the facility failed to maintain the emergency exit doors. This was evidenced by items that were stored in front of the emergency exit doors. This affected two of two floors in the Main Hospital and could result in a delayed egress in the event of an emergency.

Findings:

During a tour of the facility with Staff on 8/3/15, the emergency exit doors were observed.

Main Hospital

1. At 9:20 a.m., there was an exit sign above the emergency exit door in the Linen Storage Room on the first floor. The door was completely obstructed by a laundry cart, a large box, two step stools, and a walker.

2. At 11:31 a.m., the exit door that was adjacent to 14T in the Emergency Department was obstructed by a bed that was stationed within one inch of the left leaf push handle.

LIFE SAFETY CODE STANDARD

Tag No.: K0046

.
Outpatient Services Building 2-2809 Olive Highway

2. On 8/5/15, at 1:20 p.m., there was one emergency light observed in Suite 110. No documentation was provided indicating that the 30 second monthly or 90 minute annual tests had been performed in the past 12 months. During an interview at 1:30 p.m., the Assistant Director of Plant Operations confirmed the finding.

LIFE SAFETY CODE STANDARD

Tag No.: K0046

Based on observation, document review, and interview, the facility failed to maintain its battery back-up emergency lights. This was evidenced by incomplete testing for the 90 minutes test annually in the Main Hospital, and failure to test one emergency light for 30 seconds monthly and 90 minutes annually in the Outpatient Services Building 2. This could result in a delay in evacuation in the event of a power outage.

NFPA 101, 2000
19.2.9 Emergency Lighting
Emergency lighting shall be provided in accordance with section 7.9

39.2.9.1 Emergency lighting shall be provided in accordance with section 7.9 in any building where any one of the following conditions exists (1) the building is two or more stories in height above the level of exit discharge. (2) the occupancy is subject to 100 or more occupants above or below the level of exit discharge. (3) the occupancy is subject to 1000 or more total occupants.

7.9.3 Periodic Testing of Emergency Lighting Equipment. A functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds. A annual test shall be be conducted on every required battery-powered emergency lighting system for not less than 1 1/2 hours. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.

Findings:

During tour, document review, and interview with staff, the emergency lights were observed and documents were requested.

Main Hospital

1. On 8/4/15, at 1:45 p.m., the facility was observed with emergency lights throughout the building. The document titled, "Emergency Lights," was incomplete. The log indicated that eight of 31 emergency lights had not been tested in the past 12 months. There was no annual testing in the Dietary Serving Line, Dietary North Wall, RT Blood Gas Lab, Medical Records, Medical Records Transcription Room, Phlebotomy Supervisor's Office Room 888, HIS Computer Room, and HIS UPS Room.
During an interview at 2 p.m., the Assistant Director of Plant Operations confirmed the findings.

LIFE SAFETY CODE STANDARD

Tag No.: K0047

.
Outpatient Services Building 2-2809 Olive Highway

2. On 8/5/15, at 1:20 p.m., the facility was observed with exit signs with battery back up throughout the building. A review of the exit sign logs indicated no 90 minutes annual tests had been performed in the past 12 months. During an interview at 1:22 p.m., the Assistant Director of Plant Operations stated that the facility was not aware of the requirement for the 90 minutes annual test for the exit signs.

LIFE SAFETY CODE STANDARD

Tag No.: K0047

Based on observation, document review and interview, the facility failed to maintain its emergency exit signs. This was evidenced by a lack of documentation for annual testing of its battery-powered emergency exit signs. This affected two of two floors in the Main Hospital and three of three floors in Outpatient Services Building 2. Failure to maintain and test emergency exit signs could potentially result in delayed evacuation and/or injury in the event of a loss of power.

NFPA 101, 2000
19.2.10.1 Means of egress shall have signs in accordance with Section 7.10.

39.2.10 Marking of Means of Egress. Means of egress shall have signs in accordance with Section 7.10.

7.10.9.2 Testing. Exit signs connected to or provided with a battery-operated emergency illumination source, where required in 7.10.4, shall be tested and maintained in accordance with 7.9.3
7.9.3 Periodic Testing of Emergency Lighting Equipment. A functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds. An annual test shall be conducted on every required battery-powered emergency lighting system for not less than 11/2 hours. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.

Findings:

During tour, document review, and interview with Staff, the emergency exit signs were observed and documents were requested.

Main Hospital

1. On 8/4/15, at 10:50 a.m., the facility was observed with exit signs with battery back up throughout the building. A review of the exit sign logs indicated that no 90 minutes annual tests had been performed in the past 12 months. During an interview at 11 a.m., the Assistant Director of Plant Operations confirmed the findings.

LIFE SAFETY CODE STANDARD

Tag No.: K0050

.
Outpatient Services Building 2-2809 Olive Highway

2. On 8/6/15, at 9:10 a.m., three of five suites (Suite 110, 120, 230) failed to provide documentation for fire drills in the past 12 months. During an interview at 9:15 a.m., the Assistant Director of Plant Operations confirmed that there had been no drills.

3. On 8/6/15, at 1:20 p.m., in suit 120, one of four staff members did not know how to use a portable fire extinguisher.

Outpatient Building 3-2450 Oro Dam Blvd.

4. On 8/5/15, at 1:25 p.m., there was no fire drill documentation provided for the past 12 months. During an interview at 1:30 p.m., the Assistant Director Plant Operation confirmed that there had been no drills.

LIFE SAFETY CODE STANDARD

Tag No.: K0050

Based on document review and interview, the facility failed to train all staff in fire safety procedures. This was evidenced by staff that did not know the meaning of the Acronym R.A.C.E., where the nearest fire alarm pull station was, or how to use a fire extinguisher. This was also evidenced by the failure to conduct fire drills at Outpatient Services Building 3 and in three of five suites in the Outpatient Services Building 2. This could potentially result in staff members being untrained and unaware of their roles and responsibilities during a fire.

NFPA 101, 2000
39.7.1 Drills. In any business occupancy building occupied by more than 500 persons or more that 100 persons above or below the street level, employees and supervisory personnel shall be periodically instructed in accordance with section 4.7 and shall hold drills periodically where practicable.

39.7.2 Designated employees of business occupancies shall be periodically instructed in the use of portable fire extinguishers.

Findings:

During document review and interview with Staff, the fire drill documents were requested and interviews were performed.

Main Hospital

1. On 8/6/15, between 9:30 a.m. and 10 a.m., three of five staff members were interviewed in Dietary, Cardiopulmonary, Emergency Services, and Registration/Admitting Departments. One Staff in Dietary and one Staff in Cardiopulmonary did not know what RACE stood for for, and one Staff in Registration/Admitting did not know where the nearest fire alarm pull station was.

LIFE SAFETY CODE STANDARD

Tag No.: K0051

Based on observation and interview, the facility failed to maintain fire alarm system components. This was evidenced by one fire alarm chime that failed to emit an audible sound. This affected one of two floors at the Main Hospital and could potentially result in a delayed notification of fire.

NFPA 101, 2000
19.3.4.1 General. Health care occupancies shall be provided with a fire alarm system in accordance with section 9.6

39.3.4.1 General. A fire alarm system in accordance with section 9.6 shall be provided in any business occupancy where any one of the following condition exists: (1) the building is two or more stories in height above the level of exit discharge. (2) the occupancy is subject to 100 or more occupants above or below the level of exit discharge. (3) The occupancy is subject to 1000 or more total occupants.

9.6.1.4 A fire alarm system required for life safety shall be installed, tested, and maintained in accordance with the applicable requirements of NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm Code, unless an existing installation, which shall be permitted to be continued in use, subject to the approval of the authority having jurisdiction.
9.6.3.8 Audible alarm notification appliances shall be of such character and so distributed as to be effectively heard above the average ambient sound level occurring under normal conditions of the occupancy.

Findings:

During a tour of the facility with Staff on 8/4/15, the fire alarm system was observed and Staff was interviewed.

Main Hospital

At 9:59 a.m., chime/strobe N13-4 in the Laboratory failed to chime during testing. During an interview at 10 a.m., the Assistant Director of Plant Operations confirmed that the device did not chime but made a clicking sound.

LIFE SAFETY CODE STANDARD

Tag No.: K0052

.
Outpatient Services Building 2-2809 Olive Highway

3. On 8/5/15, at 1:20 p.m., the document titled, "Quarterly Fire Inspection Reports 2015," was incomplete. In the third quarter on 7/21/15, the document indicated that there was no access to two smoke detectors in the North and South Electrical Rooms on the second floor. The report also indicated that a duct detector on the third floor was not tested. Plant Operation Staff 1 confirmed a South Electrical Room duct detector on the third floor was not tested.

LIFE SAFETY CODE STANDARD

Tag No.: K0052

Based on document review and interview, the facility failed to maintain the fire alarm system. This was evidenced by incomplete testing records for the annual fire alarm inspection report . This affected two of two floors at the Main Hospital and two of three floors at Outpatient Services Building 2. This could result in a delay in notification in the event of a fire.

NFPA 101, 2000
19.3.4.1 General. Health care occupancies shall be provided with a fire alarm system in accordance with section 9.6
19.3.6.3.7 Door frames shall be labeled, shall be of steel construction, or shall be other materials in compliance with the provisions of 8.2.3.2.1

8.2.3.2.1 Doors assemblies in fire barriers shall be if an approved type with the appropriate fire protection rating for the location in which they are installed and shall comply with the following: (a) Fire doors shall be installed in accordance with NFPA 80, Standard for Fire Doors and Fire Windows.

39.3.4.1 General. A fire alarm system in accordance with section 9.6 shall be provided in any business occupancy where any one of the following condition exists: (1) the building is two or more stories in height above the level of exit discharge. (2) the occupancy is subject to 100 or more occupants above or below the level of exit discharge. (3) The occupancy is subject to 1000 or more total occupants.

9.6.1.4 A fire alarm system required for life safety shall be installed, tested, and maintained in accordance with the applicable requirements of NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm Code, unless an existing installation, which shall be permitted to be continued in use, subject to the approval of the authority having jurisdiction.

NFPA 72, 1999
1-6.3 Records. A complete, unalterable record of the tests and operations of each system shall be kept until the next test and for 1 year thereafter. The record shall be available for examination and, if required, reported to the authority having jurisdiction. Archiving of records by any means shall be permitted if hard copies of the records can be provided promptly when requested.
Exception: If off-premises monitoring is provided, records of all signals,
tests, and operations recorded at the supervising station shall be
maintained for not less than 1 year.

7-5.2.2 A permanent record of all inspections, testing, and maintenance shall be provided that includes the following information regarding tests and all the applicable information requested in Figure 7-5.2.2.
(1) Date
(2) Test frequency
(3) Name of property
(4) Address
(5) Name of person performing inspection, maintenance, tests, or combination thereof, and affiliation, business address, and telephone number
(6) Name, address, and representative of approving agency(ies)
(7) Designation of the detector(s) tested, for example, " Tests performed in accordance with Section __________. "
(8) Functional test of detectors
(9) *Functional test of required sequence of operations
(10) Check of all smoke detectors
(11) Loop resistance for all fixed-temperature, line-type heat detectors
(12) Other tests as required by equipment manufacturers
(13) Other tests as required by the authority having jurisdiction
(14) Signatures of tester and approved authority representative
(15)Disposition of problems identified during test (for example, owner notified, problem corrected/successfully retested, device abandoned in place)

NFPA 80, 1999
15-2.4.3 All horizontal or vertical sliding and rolling fire doors shall be inspected and tested annually to check for proper operation and full closure. Resetting of the release mechanism shall be done in accordance with the manufacturer ' s instructions. A written record shall be maintained and shall be made available to the authority having jurisdiction.

Findings:

During document review and interview with Staff, the annual fire alarm inspection reports were reviewed.

Main Hospital

1. On 8/4/15, at 10:50 a.m., the document titled, "Alarm and Detection Report," dated 11/5/14, was incomplete. The report indicated three of 40 duct detectors were not tested. On page 8 of 8 of the report, it indicated that the duct detector in Medical Equipment Room was blocked from access and that the duct detector could not be reached. During an interview at 11 a.m., Plant Operation Staff 2 stated that three duct detectors in the Intensive Care Unit (ICU) were not tested.

2. On 8/4/15, at 10:51 a.m., the facility was observed with three roll down fire doors in the Obstetrics and Gynecology (OB), Private Branch Exchange (PBX), and the Laboratory. No records were provided indicating that the rolling fire doors were tested annually for proper operation. During an interview at 11 a.m., the Assistant Director of Plant Operations confirmed the finding.

LIFE SAFETY CODE STANDARD

Tag No.: K0054

Based on document review and interview, the facility failed to maintain its smoke detectors. This was evidenced by incomplete documentation for smoke detector sensitivity testing and by the failure to have the smoke detectors tested for sensitivity by a certified and trained person. This affected two of two floors in the Main Hospital and could result in delayed notification of a fire due to a malfunctioning or dirty smoke detector.

NFPA 101, 2000
19.3.4.1 General. Health care occupancies shall be provided with a fire alarm system in accordance with section 9.6
9.6.1.4 A fire alarm system required for life safety shall be installed, tested, and maintained in accordance with the applicable requirements of NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm Code, unless an existing installation, which shall be permitted to be continued in use, subject to the approval of the authority having jurisdiction.

NFPA 72, 1999
7-1.2.2 Service personnel shall be qualified and experienced in the inspection, testing, and maintenance of fire alarm systems. Examples of qualified personnel shall be permitted to include, but shall not be limited to, individuals with the following qualifications:
(1) Factory trained and certified
(2) National Institute for Certification in Engineering Technologies
fire alarm certified
(3) International Municipal Signal Association fire alarm
certified
(4) Certified by a state or local authority
(5) Trained and qualified personnel employed by an organization
listed by a national testing laboratory for the servicing
of fire alarm systems.

7-3.2.1 Detector sensitivity shall be checked within 1 year after installation and every alternate year thereafter. After the second required calibration test, if sensitivity tests indicate that the detector has remained within its listed and marked sensitivity range (or 4 percent obscuration light gray smoke, if not marked), the length of time between calibration tests shall be permitted to be extended to a maximum of 5 years. If the frequency is extended, records of detector-caused nuisance alarms and subsequent trends of these alarms shall be maintained. In zones or in areas where nuisance alarms show any increase over the previous year, calibration tests shall be performed.
To ensure that each smoke detector is within its listed and marked sensitivity range, it shall be tested using any of the following methods:
(1) Calibrated test method
(2) Manufacturer's calibrated sensitivity test instrument
(3) Listed control equipment arranged for the purpose
(4) Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit where its sensitivity is outside its listed sensitivity range
(5) Other calibrated sensitivity test methods approved by the authority having jurisdiction
Detectors found to have a sensitivity outside the listed and marked sensitivity range shall be cleaned and recalibrated or be replaced.
Exception No. 1: Detectors listed as field adjustable shall be permitted to be either adjusted within the listed and marked sensitivity range and cleaned and recalibrated, or they shall be replaced.
Exception No. 2: This requirement shall not apply to single station detectors referenced in 7-3.3 and table 7-2.2.
The detector sensitivity shall not be tested or measured using any device that administers an unmeasured concentration of smoke or other aerosol into the detector.

Findings:

During document review and interview with Staff on 8/4/15, the smoke detector sensitivity records were reviewed.

Main Hospital

1. At 1:26 p.m., the facility had approximately 166 smoke detectors. A review of the smoke detector sensitivity log indicated 11 of 166 smoke detectors were not tested for sensitivity. During an interview at 1:32 p.m., the Director of Plant Operations stated that some areas were not accessible.

2. At 1:32 p.m., a review of the smoke detector sensitivity log indicated that the facility performed in-house smoke detector sensitivity testing. During an interview at 1:35 p.m., Director of Plant Operations stated that Plant Operation Staff 2 was trained but not certified.

LIFE SAFETY CODE STANDARD

Tag No.: K0061

Based on observation, testing, and interview, the facility failed to ensure that the automatic sprinkler system had control valves that were supervised. This was evidenced by three sprinkler system backflow preventer-valve assemblies that were not supervised. This affected two of two floors in the Main Hospital and could potentially result in staff being unaware of a loss of sprinkler protection if the automatic sprinkler system water were shut off.

NFPA 101, 2000
19.3.5.2 Where this code permits exceptions for fully sprinklered buildings or smoke compartments, the sprinkler system shall meet the following criteria: (1) it shall be in accordance with section 9.7. (2) it shall be electrically connected to the fire alarm system. (3) it shall be fully supervised. Exception: in Type I and Type II construction, where approved by the authority having jurisdiction, alternative protection measures shall be permitted to be substituted for sprinkler protection in specified areas where the authority having jurisdiction has prohibited sprinklers, without causing a building to be classified as nonsprinklered.

9.7.2.1* Supervisory Signals. Where supervised automatic sprinkler systems are required by another section of this Code, supervisory attachments shall be installed and monitored for integrity in accordance with NFPA 72, National Fire Alarm Code, and a distinctive supervisory signal shall be provided to indicate a condition that would impair the satisfactory operation of the sprinkler system. Monitoring shall include, but shall not be limited to, monitoring of control valves, fire pump power supplies and running conditions, water tank levels and temperatures, tank pressure, and air pressure on dry-pipe valves. Supervisory signals shall sound and shall be displayed either at a location within the protected building that is constantly attended by qualified personnel or at an approved, remotely located receiving facility.
9.7.2.2. Alarm Signal Transmission. Where supervision of the automatic sprinkler systems is provided in accordance with another provision of this code, waterflow alarms shall be transmitted to an approved, proprietary alarm receiving facility, a remote station, a central station, or the fire department. Such connection shall be in accordance with 9.6.1.4.

Findings:

During a tour of the facility, testing, and interview with Staff 8/5/15, the automatic sprinkler system backflow shut off valves were observed and tested.

Main Hospital

1. At 9:01 a.m., the southwest sprinkler system backflow shut-off valve assembly was chained and locked in an open position. The valves were closed and there was no tamper alarm and/or supervisory signal that was initiated at the fire alarm control panel (FACP) room/Private Branch Exchange (PBX) office, or at an off site monitoring station. The control valve assembly was not equipped with a tamper switch. During an interview at 9:05 a.m., the Assistant Director of Plant Operations and Plant Operation Staff 1 confirmed that no signals were received at the FACP or PBX.

2. At 9:11 a.m., the northwest sprinkler system backflow shut-off valve assembly was chained and locked in an open position. The valves were closed and there was no tamper alarm and/or supervisory signal that was initiated at the FACP Room, the PBX office, or at an off site monitoring station. The control valve assembly did not have a tamper switch on it. During an interview at 9:12 a.m., the Assistant Director of Plant Operations and Plant Operation Staff 1 confirmed that there were no signals received at the FACP or PBX.

3. At 9:15 a.m., the northeast sprinkler system backflow shut-off valve assembly was chained and locked in an open position. The valves were closed and there was no tamper alarm and/or supervisory signal that was initiated at the FACP room, the PBX office, or at an off site monitoring station. The control valve assembly did not have a tamper switch on it. During an interview at 9:17 a.m., Assistant Director of Plant Operations and Plant Operation Staff 1 confirmed that there were no signals received at the FACP or PBX.

LIFE SAFETY CODE STANDARD

Tag No.: K0062

.
Outpatient Services Building 2-2809 Olive Highway

6. On 8/5/15 at 9:46 a.m., a corridor sprinkler was observed with a green liquid substance on the deflector plate in Suite 110.

7. On 8/5/15 at 9:47 a.m., a sprinkler head in the Supply Closet in Suite 120 had a box that was within 12 inches of the deflector.

8. On 8/5/15 at 10:06 a.m., the Inspector Test Valve (ITV) on the first floor took longer than 90 seconds to alarm. The ITV took one minute and forty seconds to activate the fire alarm system. Plant Operations Staff 2 confirmed.

9. On 8/5/15 at 1:25 p.m., the facility was missing two quarterly sprinkler inspection tests for the third and fourth quarter of 2014. Assistant Director of Plant Operations and Plant Operation Staff 2 confirmed the findings.

Outpatient Building 3-2450 Oro Dam Blvd.

10. On 8/5/15, at 10:42 a.m., the spare sprinkler box that was located between the two Sprinkler Risers was missing the special sprinkler head wrench.

11. On 8/5/15, at 10:50 a.m., one of two Post Indicator Valves (PIV) was observed without a wrench to operate the valve and without a lock to prevent tampering. The valve was supervised and functioned properly when tested.

LIFE SAFETY CODE STANDARD

Tag No.: K0062

Based on observation, document review, and interview, the facility failed to maintain the automatic sprinkler system and its components. This was evidenced by foreign material on sprinkler heads, less than 18 inches of clearance below the sprinkler deflector, a missing sprinkler wrench, two missing fire department connection (FDC) caps, missing quarterly sprinkler testing and inspections, an unlocked post indicator valve with a missing wrench, and three annual backflow inspection tests that had failed. This affected two of two floors at the Main Hospital, three of three floors at the Outpatient Services Building 2, and one of one floor at the Outpatient Services Building 3. This could result in the sprinkler system failing to function as designed and a delay in notification in the event of a fire.

NFPA 101, 2000
19.7.6 Maintenance and Testing (see 4.6.12)
4.6.12 Maintenance and Testing. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provision of this code, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with applicable NFPA requirements or as directed by the authority having jurisdiction.

39.1.5.2 For purpose of the design of an automatic sprinkler system, a business occupancy shall be classified as a light hazardous occupancy in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.
39.3.4.1 General. A fire alarm system in accordance with section 9.6 shall be provided in any business occupancy where any one of the following condition exists: (1) the building is two or more stories in height above the level of exit discharge. (2) the occupancy is subject to 100 or more occupants above or below the level of exit discharge. (3) The occupancy is subject to 1000 or more total occupants.

9.6.1.4 A fire alarm system required for life safety shall be installed, tested, and maintained in accordance with the applicable requirements of NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm Code, unless an existing installation, which shall be permitted to be continued in use, subject to the approval of the authority having jurisdiction.

NFPA 13, 1999
3-2.9.2 A special sprinkler wrench shall also be provided and kept in the cabinet to be used in the removal and installation of sprinklers
5-5.6 The clearance between the deflector and the top of storage shall be
18 in. (457 mm) or greater.
12-1 General. A sprinkler system installed in accordance with this standard shall be properly inspected, tested, and maintained in accordance with NFPA 25, Standard for the inspection, testing, and maintenance of water-based fire protection systems, to provide at least the same level of performance and protection as designed.

NFPA 25, 1998
9-3.3.2* The valve inspection shall verify that the valves are in the following condition:
(a) In the normal open or closed position
(b) *Properly sealed, locked, or supervised
(c) Accessible
(d) Provided with appropriate wrenches
(e) Free from external leaks
(f) Provided with appropriate identification

Chapter 2 Sprinkler Systems, 2-1 General. This chapter provides the minimum requirements for the routine inspection, testing, and maintenance of sprinkler systems. Table 2-1 shall be used to determined the minimum required frequencies for inspections, testing, and maintenance. Exception: Valves and fire department connections shall be inspected, tested, and maintained in accordance with Chapter 9.
1-8*. Records of inspections, tests, and maintenance of the system and its components shall be made available to the authority having jurisdiction upon request. Typical records include, but are not limited to, valve inspections; flow, drain, and pump tests; and trip tests of dry pipe, deluge, and pre-action valves.
1-8.1 Records shall indicate the procedure performed (e.g., inspection, test, or maintenance), the organization that performed the work, the results, and the date.
2-2.1.1*. Sprinklers shall be inspected from the floor level annually. Sprinklers shall be free of corrosion, foreign materials, paint, and physical damage and shall be installed in the proper orientation (e.g., upright, pendant, or sidewall). Any sprinkler shall be replaced that is painted, corroded, damaged, loaded, or in the improper orientation.
2-2.2 Sprinkler pipe and fittings shall be inspected annually from the floor level. Pipe and fittings shall be in good condition and free of mechanical damage, leakage, corrosion, and misalignment. Sprinkler piping shall not be subjected to external loads by materials either resting on the pipe or hung from the pipe.
2-2.6 Alarm Devices. Alarm devices shall be inspected quarterly to verify that they are free of physical damage.
2-3.3* Alarm Devices. 2 Waterflow alarm devices including,but not limited to, mechanical water motor gongs, vane-type waterflow devices, and pressure switches that provide audible or visual signals shall be tested quarterly.
9-6.2.1 All backflow preventers installed in fire protection system piping shall be tested annually in accordance with the following:
(a) a forward flow test shall be conducted at the system demand, including hose stream demand, where hydrants or inside hose stations are located downstream of the backflow preventer.
(b) a backflow performance test, as required by the authority having jurisdiction, shall be conducted at the completion of the forward flow test.
9-7.1 Fire department connections shall be inspected quarterly. The inspection shall verify the following:
(a) The fire department connections are visible and accessible.
(b) Couplings or swivels are not damaged and rotate smoothly.
(c) Plugs or caps are in place and undamaged.
(d) Gaskets are in place and in good condition.
(e) Identification signs are in place.
(f) The check valve is not leaking.
(g) The automatic drain valve is in place and operating properly.

NFPA 72, 1999
2-6.2 Initiation of the alarm signal shall occur within 90 sec of waterflow at the alarm-initiating device when flow occurs that is equal to or greater than that from a single sprinkler of the smallest orifice size installed in the systems. Movement of water due to waste, surges, or variable pressure shall not be indicated.
3-8.3.2.5.2 The integrity of each fire suppression system actuating device and its circuit shall be supervised in accordance with 1-5.8.1 and with other applicable NFPA standards.


Findings:
During a tour of the facility, document review, and interview with Staff, the automatic sprinkler system and components were observed and tested, and documents were requested.
Main Hospital
1. On 8/3/15, at 9:28 a.m., a sprinkler in the Rehab Office Storage had a black lunch cooler that was located within 10 inches of the deflector plate.
2. On 8/3/15, at 9:53 a.m., a sprinkler in the Maternity Workroom had a surgical glove box that was within 12 inches of the deflector plate.
3. On 8/3/15, at 11:46 a.m., two sprinkler heads in the Kitchen Dishwashing area were observed with a dark, thick greaselike buildup.
4. On 8/4/15, at 11:30 a.m., the facility had five Inspector Test Valves (ITV) throughout the building. Testing was performed in house. The Inspector's Test Valves were located in the Laboratory, in X-ray, in the Canopy-Admitting, Unit 1-2, and Mechanical Room 3. A review of the quarterly testing records indicated that seven quarterly inspections were not performed for the ITV valves in a 12 month period. The Laboratory flow test was missing for the third quarter of 2014, the X-ray flow test was missing for the fourth quarter of 2014, the Canopy-Admitting flow test was missing for the second quarter of 2015 and fourth quarter of 2014, Unit 1-2 was missing for the first quarter of 2015 and third quarter of 2014, and Mechanical Room 3 was missing for the second quarter of 2015. During an interview at 12 p.m., Plant Operations Staff 2 confirmed the findings.
5. On 8/5/15, at 12:55 p.m., the facility had three sprinkler system OS&Y double back flow valves assemblies. A review of the inspection reports dated 6/9/15, indicated that a total of six back flow valves failed. They were located in Southwest, Northeast, and Northwest areas of the facility. During an interview at 1 p.m., the Assistant Director of Plant Operation and Director of Plant Operation confirmed the findings.

LIFE SAFETY CODE STANDARD

Tag No.: K0064

Based on observation, the facility failed to maintain its portable fire extinguishers. This was evidenced by fire extinguishers that were recessed into the wall that were obscured from view and by fire extinguishers that were obstructed from access. This affected two of two floors in the Main Hospital and could result in a delay in access to the fire extinguisher in the event of a fire.

NFPA 101, 2000
19.3.5.6 Portable Fire Extinguishers shall be provided in all health care occupancies in accordance with 9.7.4.1
9.7.4 Manual Extinguishing Equipment
9.7.4.1 Where required by the provision of another section of this code, portable fire extinguishers shall be installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguisher.

21.3.5.2 Portable fire extinguishers shall be provided in ambulatory health care facilities in accordance with 9.7.4.1
9.7.4.1 Where required by the provision of another section of this code, portable fire extinguishers shall be installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.

NFPA 10, 1998
1-6.6* Fire extinguishers shall not be obstructed or obscured from view. Exception: In large rooms, and in certain locations where visual obstruction cannot be completely avoided, means all be provided to indicate the location.

1-6.12 Fire extinguishers mounted in cabinets or wall recesses shall be placed so that the fire extinguisher operating instructions face outward. The location of such fire extinguishers shall be marked conspicuously. (See 1 6.6.)

Findings:

During a tour of the facility with Staff on 8/3/15, the portable fire extinguishers were observed.

Main Hospital

1. At 9:25 a.m., recessed cabinet fire extinguisher number 46 on the first floor by the Linen Storage Room was obscured from view. There was no sign marking its location.

2. At 9:25 a.m., cabinet fire extinguisher 54 on the first floor in the South Mechanical Room was obstructed from access by a vacuum pump and other large equipment. The items were stationed within one inch of the fire extinguisher.

3. At 10:10 a.m., recessed cabinet fire extinguisher number 41 on the first floor by Elevator Door 4-16 was obscured from view. There was no sign marking its location.

4. At 10:16 a.m., recessed cabinet fire extinguisher number 43 on the first floor by Room 114 was obstructed by four wheelchairs that prevented direct access to the extinguisher.

5. At 10:20 a.m., recessed cabinet fire extinguisher number 44 on the first floor in Unit 1 was obscured from view and was also obstructed from access by a metal rolling ladder that was stationed within one inch in front of it. There was no sign marking its location.

6. At 10:21 a.m., recessed cabinet fire extinguisher number 45 on the first floor in Unit 1 was obscured from view. There was no sign marking its location.

7. At 10:24 a.m., recessed cabinet fire extinguisher number 42 on the first floor in Unit 1 was obscured from view. There was no sign marking its location. The fire extinguisher was also obstructed from access by a janitor's cart that was stationed within one inch of the front of it.

8. At 10:30 a.m., recessed cabinet fire extinguisher number 47 on the second floor behind elevator fire door 7-17 was obscured from view. There was no sign marking its location.

9. At 10:31 a.m., recessed cabinet fire extinguisher number 55 on the second floor in Unit 2 was obscured from view. There was no sign marking its location.

10. At 10:35 a.m., recessed cabinet fire extinguisher number 53 on the second floor in Unit 2 was obscured from view. There was no sign marking its location.

11. At 10:37 a.m., recessed cabinet fire extinguisher number 52 on the second floor in Unit 2 was obscured from view. There was no sign marking its location.

12. At 10:40 a.m., recessed cabinet fire extinguisher number 51 on the second floor in the Intensive Care Unit (ICU) was obscured from view. There was no sign marking its location.

13. At 10:41 a.m., recessed cabinet fire extinguisher number 50 on the second floor in ICU was obscured from view. There was no sign marking its location.

14. At 10:46 a.m., recessed cabinet fire extinguisher number 49 on the second floor in Surgery was obscured from view. There was no sign marking its location.

15. At 10:51 a.m., recessed cabinet fire extinguisher number 48 on the second floor in the Surgery was obscured from view. There was no sign marking its location.

16. At 11:02 a.m., recessed cabinet fire extinguisher number 79 on the second floor in the Lab was obstructed from access by a trash bin that was stationed within one inch of it. There was no sign marking its location.

17. At 11:40 a.m., recessed cabinet fire extinguisher number 12 on the second floor in the Emergency Department (ER) was obscured from view. There was no sign marking its location.

18. At 12:55 p.m., recessed cabinet fire extinguisher number 3 on the second floor in the Ambulatory Care Service (ACS) was obscured from view and was also obstructed by a tall IV pole that was stationed in front of it. There was no sign marking its location.

LIFE SAFETY CODE STANDARD

Tag No.: K0076

Based on observation, the facility failed to maintain its compressed gas cylinders. This was evidenced by an unsecured cylinder. This affected one of two floors in the Main Hospital and could result in an increased risk or acceleration of a fire.

4-3.1.1.1 Cylinder and Container Management. Cylinders in service and in storage shall be individually secured and located to prevent falling or being knocked over.
4-3.5.2.1 (27) Freestanding cylinders shall be properly chained or supported in a proper cylinder stand or cart.

Findings:

During a tour of the facility with Staff on 8/3/15, the non-flammable gas was observed.

Main Hospital

1. At 11:45 a.m., a carbon dioxide cylinder was observed freestanding on the floor in the Kitchen Dry Storage.

LIFE SAFETY CODE STANDARD

Tag No.: K0077

Based on observation, the facility failed to maintain access to its medical gas shut off valves. This was evidenced by equipment placed in front of emergency oxygen shut off valves. This affected one of two floors in the Main Hospital and could delay personnel from shutting off oxygen during an emergency.

NFPA 101, 2000
19.3.2.4 Medical Gas.
Medical gas storage and administration areas shall be protected in accordance with NFPA 99, Standard for Health Care Facilities.

NFPA 99,1999
4-3.1.2.3 Gas Shutoff Valves, Shutoff valves accessible to other than authorized personnel shall be installed in valve boxes with frangible or removable windows large enough to permit manual operation of valves.
Exception: Shutoff valves for use in certain areas, such as psychiatric or pediatric, shall be permitted to be secured to prevent inappropriate access.
(i) Shutoff Valves (Manual). Manual shutoff valves in boxes shall be installed where they are visible and accessible at all times. The boxes shall not be installed behind normally open or normally closed doors, or otherwise hidden from plain view.

Findings:

During a tour of the facility with Staff 8/3/15, the piped-in medical gas shut off valves were observed.

Main Hospital

1. At 10:50 a.m., the shut off valve near Operation Room (OR) 2 in the Surgery Unit was obstructed by a cart, two instrument holders, a tall supply cart, and a stints cart. The items impeded access to the shut off valve.

2. At 10:55 a.m., the shut off valve by OR 1 in the Surgery Unit was obstructed by a metal supply cart.

3. At 11:37 a.m., the shut off valve in the Emergency Department (ER) was obstructed by a x-ray machine that was stationed within one inch of the front of it.

4. At 11:41 a.m., the shut off valve in the Respirator Care Workroom had a tool box that was stationed within one inch of the front of it.

LIFE SAFETY CODE STANDARD

Tag No.: K0078

Based on document review and interview, the facility failed to maintain and
provide a written policy for the relative humidity (RH). This was evidenced by failure to following the policy for the RH and failure to document the RH level. This affected one of two floors in the Main Hospital and could result in an increased risk of fire.

Findings:

During document review and interview, the RH policy was requested and reviewed.

Main Hospital

1. On 8/4/15, at 1:35 p.m., the Surgery Unit had five operating rooms. (OR). The relative humidity (RH) policy indicated that the RH would be maintained at 55%-65%." A review of the RH log indicated that in the last six month period (January-July 2015), the RH level went as low as 18% and as high at 76%. During an interview on 8/5/15 at 1:26 p.m., the Surgery Administrative Staff stated that Plant Operations personnel made the adjustments to the RH when needed. Staff further stated there was no log recording the adjustments that have been made. During an interview at 1:30 p.m., Director of Plant Operations stated that they do not make adjustments to the RH levels.

2. On 8/6/15, at 9:10 a.m., the Ambulatory Care Services Unit (ACS) had five Endoscopy Rooms (rooms 601, 603, 604, 606, and 607) and one eye laser procedure room. The ACS Unit failed to provide a written policy or maintain a log for RH levels. During an interview at 9:20 a.m., Director of Plant Operations stated they did not have a policy or a log for the RH.

LIFE SAFETY CODE STANDARD

Tag No.: K0104

Based on observation, the facility failed to maintain its smoke barrier walls free from penetrations. This was evidenced by penetrations in four walls. This affected two of two floors in the Main Hospital and could result in the spread of fire and/or smoke.

NFPA 101, 2000
19.3.7.3 Any required smoke barrier shall be constructed in accordance with section 8.3 and shall have a fire resistance rating of not less than 1/2 hours.

8.3.6.1: Pipes, conduits, ducts, cables, wires, air ducts, pneumatic tube and ducts, and similar building service equipment that pass through floors and smoke barriers shall be protected as follows:
(1) The space between the penetrating item and the smoke barrier shall meet one following conditions:
(a) It shall be filled with a material that is capable of maintaining the smoke resistance of the smoke barrier.
(b) It shall be protected by an approved device that is designed of the specific purpose.
(2) Where the penetrating item uses a sleeve to penetrate the smoke barrier, the sleeve shall be solidly set in the smoke barrier, and the space between the item and the sleeve shall meet one of the following conditions:(a) It shall be filled with a material that is capable of maintaining the smoke resistance of the smoke barrier

Findings:

During a tour of the facility with Staff on 8/3/15, the smoke barrier walls were observed.

Main Hospital

1. At 1:26 p.m., there was an approximately four inch by four inch penetration with wires traveling through the smoke barrier wall in Unit 1 near fire door 2-14.

2. At 1:27 p.m., there was an approximately four inch by four inch penetration with wires traveling through the smoke barrier wall in the Unit 1 Conference Room by fire door 2-12.

3. At 1:40 p.m., there was an approximately three inch penetration with wires traveling through the wall in the west smoke barrier wall by Dietary.

4. At 1:43 p.m., there was an approximately two inch penetration with wires traveling through the wall in the east smoke barrier wall by Dietary.

LIFE SAFETY CODE STANDARD

Tag No.: K0144

Based on document review and interview, the facility failed to test its diesel generators. This was evidenced by missing documentation for three monthly full load tests in the past 12 months. This affected two of two smoke compartments and could potentially result in a generator failure during an emergency.

NFPA 101, 2000
19.7.6 Maintenance and Testing (see 4.6.12)
4.6.12 Maintenance and Testing. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provision of this code, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with applicable NFPA requirements or as directed by the authority having jurisdiction.

NFPA 110, 1999
6-4.1* Level 1 and Level 2 EPSSs, including all appurtenant components, shall be inspected weekly and shall be exercised under load at least monthly.

Findings:

During document review and interview with Staff on 8/4/15, the generator records were requested.

1. At 11:30 a.m., the facility had two emergency diesel-powered generators. The north generator was rated for 250 kilowatts (KW) and the south generator was rated 200 KW. The north 250KW generator supplies emergency back-up power to Unit 3, Obstetrics and Gynecology (OB), Ambulance, Dietary, Emergency Department, X-ray, and Pharmacy. The south 200KW generator supplies emergency back-up power to Surgery, the Intensive Care Unit (ICU), and Unit 2 and Unit 1. The generator log titled, "Weekly Operational Test Exercise Log", did not indicate that a full load test was done in January 2015 and November 2014 for the north generator. There was no documentation provided indicating that the full load test was done for the south generator in August 2014. During an interview at 12 p.m., Assistant Director of Plant Operations confirmed the findings.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

.
Outpatient Services Building 2-2809 Olive Highway

27. On 8/5/15, at 9:50 a.m., in Suite 150 Infusion Room, there were three IV pumps and a patient monitor plugged into a power strip at Station A, two IV pumps were plugged into a power strip at Station B, two IV pumps and a patient monitor were plugged into a power strip at Station C, two IV poles were plugged into a power strip at Station D, and four IV pumps and a patient monitor were plugged into a power strip at Station E.

28. On 8/5/15, at 9:56 a.m., a computer charger was plugged into a extension card in the Suite 230 Break Room.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation, the facility failed to maintain its electrical wiring and connections. This was evidenced by the use of extension cords, power strips chained together, power strips suspended above the floor, obstructed electrical panels, and power strips being used for medical devices and high power equipment. This affected two of two floors at the Main Hospital and one of three floors at Outpatient Services Building 2. This could could potentially result in an electrical fire.

NFPA 101, 2000
19.5.1 Utilities. Utilities shall comply with the provisions of section 9.1
39.5.1 Utilities. Utilities shall comply with the provisions of section 9.1

9.1.2 Electric. Electrical wiring and equipment shall be in accordance with NFPA 70, National Electrical Code, unless existing installations, which shall be permitted to be continued in service, subject to approval by the authority having jurisdiction.

NFPA 70, 1999
110-12 Mechanical Execution of Work. Electrical equipment shall be installed in a neat and workmanlike manner.
(c) Integrity of Electrical Equipment and Connections. Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues. There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment such as parts that are broken; bent; cut; or deteriorated by corrosion, chemical action, or overheating.

110-26 Spaces About Electrical Equipment. Sufficient access and working space shall be provided and maintained about all electrical equipment to permit ready and safe operation and maintenance of such equipment. Enclosures housing electrical apparatus that are controlled by lock and key shall be considered accessible to qualified persons.
(1) Depth of Working Space. The depth of the working space in the direction of access to live parts shall not be less than indicated in Table 110-26(a). Distances shall be measured from the live parts if such are exposed or from the enclosure front or opening if such are enclosed.
(2) Width of Working Space. The width of the working space in front of the electric equipment shall be the width of the equipment or 30 in.
(762 mm), whichever is greater.

210-23 In no case shall the load exceed the branch-circuit ampere rating. An individual branch circuit shall be permitted to supply any load for which it is rated. A branch circuit supplying two or more outlets or receptacles shall supply only the loads specified according to its size as specified in (a) through (d) and as summarized in Section 210-24. A 15 or 20-ampere branch circuit shall be permitted to supply lighting units or other utilization, or a combination of both. The rating of any one cord and plug-connected utilization equipment shall not exceed 80 percent of the branch-circuit ampere rating. The total rating of utilization equipment fastened in place, other than lighting fixtures, shall not exceed 50 percent of the branch circuit ampere rating where lighting units, cord and plug-connected utilization equipment not fastened in place, or both, are also supplied.

400-8 Unless specifically permitted in Section 400-7, flexible cord and cables shall not be used for the following:
(1) As a substitute for the fixed wiring of a structure
(2) Where run through holes in walls, structural ceilings, suspended ceilings, dropped ceilings, or floors.
(3) Where run through doorways, windows, or similar openings
(4) Where attached to building surfaces
(5) Where concealed behind building walls, structural ceilings, suspended ceilings, dropped ceilings, or floors
(6) Where installed in raceways, except as otherwise permitted in this Code.

400-10. Flexible cords and cables shall be connected to devices and to fittings so that tension will not be transmitted to joints or terminals.

Findings:

During a tour of the facility with Staff, the electrical wiring and connections were observed.

1. On 8/3/15, at 9:21 a.m., in the Linen Storage on the first floor, there were three different areas that had power strips chained together. Two were near the the radio cabinet, and one was in the office.

2. On 8/3/15, at 9:28 a.m., a power strip was connected to a wall outlet adapter in the Rehabilitation Office below a desk.

3. On 8/3/15, at 9:29 a.m., in Rehabilitation at desk 3, a yellow extension cord was plugged into a three plugged adapter that had two pieces of computer equipment plugged in to it.

4. On 8/3/15, at 9:30 a.m., a red extension cord was plugged into a power strip that was connected to a floor scrubbing machine, in the South Mechanical Room.

5. On 8/3/15, at 9:36 a.m., in the Main Mechanical Room South, an orange extension cord was plugged into a lift, a bed was plugged into an orange extension cord that was connected to a power strip that was suspended off the floor, and a wall outlet was plugged into a wall outlet junction box.

6. On 8/3/15, at 9:40 a.m., an outlet adapter was plugged into an outlet in the Chiller area.

7. On 8/3/15, at 9:50 a.m., two power strips were suspended off the floor in the Pharmacy Office.

8. On 8/3/15, at 9:51 a.m., a refrigerator was plugged into a power strip in the Maternity Nursery work room.

9. On 8/3/15, at 10:05 a.m., a corridor camera was plugged into a blue extension cord in the Health Information Service (HIS) Operation Room.

10. On 8/3/15, at 10:10 a.m., in the Neurology Laboratory, a six plug wall adapter was connected to an orange extension card that was plugged into a power strip. Also, a six plug adapter was connected to a power strip that was plugged into another power strip.

11. On 8/3/15, at 10:15 a.m., in Unit 1, a power strip was mounted on a crash cart and a defibrillator machine was connected to it .

12. On 8/3/15, at 10:27 a.m., in the Unit 1 Conference Room, a refrigerator and microwave were plugged into a power strip that was suspended off the floor.

13. On 8/3/15, at 10:30 a.m., a red extension cord was plugged into a outlet in the Cardiopulmonary Office.

14. On 8/3/15, at 10:31 a.m., in Unit 2, a power strip was mounted on a crash cart and a defibrillator machine was connected to it.

15. On 8/3/15, at 10:45 a.m., in Surgery, electrical panel L2B Sect. 2 was obstructed by a supply cart that was stationed within one inch of it.

16. On 8/3/15, at 10:47 a.m., a power strip was connected to another power strip in the Surgery corridor.

17. On 8/3/15, at 11:10 a.m., electrical panel 9L was obstructed by two drop ceiling tiles and a box that was stationed within one inch of it in the Laboratory Electrical room.

18. On 8/3/15, at 11:13 a.m., a refrigerator was plugged into a red extension cord in the Main Laboratory.

19. On 8/3/15, at 11:15 a.m., three electronic items were plugged into a three plug adapter in the Micro Laboratory.

20. On 8/3/15, at 11:20 a.m., a data plate was loose and was hanging from the junction box in the X-ray Tech room.

21. On 8/3/15, at 11:21 a.m., in the Emergency Room (ER) Manager's Office, a microwave was plugged into a extension cord that was connected to a power strip. There was also a refrigerator that was plugged into a power strip.

22. On 8/3/15, at 11:22 a.m., electrical panel S was obstructed by a tall privacy curtain that was stationed within one inch of it in Emergency Room Biohazard Room.

24. On 8/3/15, at 11:30 a.m., a power strip was suspended off the floor with two items plugged into it in the ER by QRQ room.

25. On 8/3/15, at 11:41 a.m., a patient scanner and a patient monitor were plugged into a power strip in the ER room by the Staff Lounge.

26. On 8/3/15, at 11:55 a.m., in the Cafeteria, a coffee machine was plugged into a power strip and a refrigerator was plugged into a power strip.