Bringing transparency to federal inspections
Tag No.: K0011
Based on observation and interview, it was determined the facility failed to maintain one common wall, affecting one of two floors.
Findings include:
1. Observation on July 10, 2014, at 8:58 a.m. revealed an unsealed conduit penetration of the common wall, within first floor Medical Records Room.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the unsealed penetration.
Tag No.: K0012
Based on observation and interview, it was determined the facility failed to maintain the two- hour fire resistant ceiling assembly in five locations, affecting two of four floors.
Findings include:
1. Observation on July 9, 2014, between 9:30 a.m. and 1:26 p.m. revealed the following ceiling assembly deficiencies:
a. 9:30 a.m., the large ceiling access panel within the basement-level Bed Repair Room, compromised the fire resistive integrity of the floor slab assembly;
b. 12:15 p.m., a portion of the fire rated ceiling assembly was lacking, within first floor Room 1439;
c. 1:17 p.m., recessed lighting fixtures within the first floor Medical Records lacked bonnet protection;
d. 1:21 p.m., ceiling diffusers within the first floor Medical Records lacked fire dampers;
e. 1:30 p.m., two non-rated access panels within the first floor Medical Records.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the building construction deficiencies.
Tag No.: K0017
Based on observation and interview, it was determined the facility failed to maintain corridor walls in one location, affecting one of four floors.
Findings include:
1. Observation on July 9, 2014, at 9:22 a.m. revealed a corridor wall penetration closest to the Lighbulb Room.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the penetration.
Tag No.: K0018
Based on observation and interview, it was determined the facility failed to maintain one corridor door, on one of four floors.
Findings include:
1. Observation on July 9, 2014, at 8:20 a.m. revealed the door to basement-level, Room 0832 was held open by unapproved means.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the door was held open.
Tag No.: K0020
Based on observation and interview, it was determined the facility failed to maintain two vertical openings, affecting two of four floors.
Findings include:
1. Observation on July 9, 2014, between 9:20 a.m. and 1:31 p.m. revealed the following unsealed penetrations:
a. 9:20 a.m., two vertical penetrations of the floor slab assembly were noted within the basement-level exit access corridor closest to the Lightbulb Room.
b. 1:30 p.m., a horizontal penetration of the large shaft enclosure closest to the first floor, Main Entrance.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the unsealed penetrations.
Tag No.: K0025
Based on observation and interview, it was determined the facility failed to maintain one smoke barrier separation wall, affecting one of four floors.
Findings include:
1. Observation on July 9, 2014, at 10:46 a.m. revealed an unsealed penetration of the smoke barrier wall within first floor Room 1439, above the suspended ceiling assembly.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the unsealed penetration.
Tag No.: K0027
Based on observation and interview, it was determined the facility failed to maintain one smoke barrier door, affecting one of four floors.
Findings include:
1. Observation on July 9, 2014, at 12:02 p.m. revealed the smoke barrier door to first floor Room 1439, lacked a self closing device.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the door lacked a self-closing device.
Tag No.: K0029
Based on observation and interview, it was determined the facility failed to maintain three hazardous area enclosures, affecting one of four floors.
Findings include:
1. Observation on July 9, 2014, between 8:27 a.m. and 9:44 a.m. revealed the following doors to hazardous areas would not close due to contact with the floor:
a. 8:27 a.m., basement-level, Mechanical Room 0839;
b. 8:29 a.m., basement-level, Form Storage Room 0840;
c. 9:44 a.m., basement-level, Mechanical Room 0311.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the doors would not close.
Tag No.: K0038
Based on observation and interview, it was determined the facility failed to maintain exit access in one location, affecting one of four floors.
Findings include:
1. Observation on July 10, 2014, at 10:12 a.m. revealed the third floor, Third Medical, exit access corridor system was used as a large storage area.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the storage in the corridor.
Tag No.: K0047
Based on observation and interview, it was determined the facility failed to maintain illuminated exit signage in one location, on one of four floors.
Findings include:
1. Observation on July 9, 2014, at 8:06 a.m. revealed the facility lacked an exit sign, in the exit access corridor system, in the vicinity of the freight elevator.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the area lacked illuminated exit signage.
Tag No.: K0064
Based on observation and interview, it was determined the facility failed to properly install one portable fire extinguisher, on one of four floors.
Findings include:
1. Observation on July 9, 2014, at 10:44 a.m. revealed the fire extinguisher located within the basement-level Electric Shop was installed in excess of sixty inches from the handle to the finished floor.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the fire extinguisher was mounted to high.
Tag No.: K0077
Based on observation and interview, it was determined the facility failed to maintain the piped-in medical gas system in one location, on one of four floors of the building.
Findings include:
1. Observation on July 9, 2014, at 9:44 a.m. revealed medical gas piping, within the basement-level Bed Repair Room, lacked shut-off valves at the base of the risers.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the lack of shut-off valves.
Tag No.: K0211
Based on observation and interview, it was determined the facility failed to properly install alcohol-based hand rub (ABHR) stations in multiple locations, affecting three of four floors.
Findings include:
1. Observation on July 09, 2014, between 8:55 a.m. and 2:01 p.m. revealed ABHR dispensers were positioned over a source of ignition throughout this component.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the ABHR dispensers were positioned over sources of ignition.
Tag No.: K0011
Based on observation and interview, it was determined the facility failed to maintain one common wall, affecting one of two floors.
Findings include:
1. Observation on July 10, 2014, at 8:58 a.m. revealed an unsealed conduit penetration of the common wall, within first floor Medical Records Room.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the unsealed penetration.
Tag No.: K0012
Based on observation and interview, it was determined the facility failed to maintain the two- hour fire resistant ceiling assembly in five locations, affecting two of four floors.
Findings include:
1. Observation on July 9, 2014, between 9:30 a.m. and 1:26 p.m. revealed the following ceiling assembly deficiencies:
a. 9:30 a.m., the large ceiling access panel within the basement-level Bed Repair Room, compromised the fire resistive integrity of the floor slab assembly;
b. 12:15 p.m., a portion of the fire rated ceiling assembly was lacking, within first floor Room 1439;
c. 1:17 p.m., recessed lighting fixtures within the first floor Medical Records lacked bonnet protection;
d. 1:21 p.m., ceiling diffusers within the first floor Medical Records lacked fire dampers;
e. 1:30 p.m., two non-rated access panels within the first floor Medical Records.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the building construction deficiencies.
Tag No.: K0017
Based on observation and interview, it was determined the facility failed to maintain corridor walls in one location, affecting one of four floors.
Findings include:
1. Observation on July 9, 2014, at 9:22 a.m. revealed a corridor wall penetration closest to the Lighbulb Room.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the penetration.
Tag No.: K0018
Based on observation and interview, it was determined the facility failed to maintain one corridor door, on one of four floors.
Findings include:
1. Observation on July 9, 2014, at 8:20 a.m. revealed the door to basement-level, Room 0832 was held open by unapproved means.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the door was held open.
Tag No.: K0020
Based on observation and interview, it was determined the facility failed to maintain two vertical openings, affecting two of four floors.
Findings include:
1. Observation on July 9, 2014, between 9:20 a.m. and 1:31 p.m. revealed the following unsealed penetrations:
a. 9:20 a.m., two vertical penetrations of the floor slab assembly were noted within the basement-level exit access corridor closest to the Lightbulb Room.
b. 1:30 p.m., a horizontal penetration of the large shaft enclosure closest to the first floor, Main Entrance.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the unsealed penetrations.
Tag No.: K0025
Based on observation and interview, it was determined the facility failed to maintain one smoke barrier separation wall, affecting one of four floors.
Findings include:
1. Observation on July 9, 2014, at 10:46 a.m. revealed an unsealed penetration of the smoke barrier wall within first floor Room 1439, above the suspended ceiling assembly.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the unsealed penetration.
Tag No.: K0027
Based on observation and interview, it was determined the facility failed to maintain one smoke barrier door, affecting one of four floors.
Findings include:
1. Observation on July 9, 2014, at 12:02 p.m. revealed the smoke barrier door to first floor Room 1439, lacked a self closing device.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the door lacked a self-closing device.
Tag No.: K0029
Based on observation and interview, it was determined the facility failed to maintain three hazardous area enclosures, affecting one of four floors.
Findings include:
1. Observation on July 9, 2014, between 8:27 a.m. and 9:44 a.m. revealed the following doors to hazardous areas would not close due to contact with the floor:
a. 8:27 a.m., basement-level, Mechanical Room 0839;
b. 8:29 a.m., basement-level, Form Storage Room 0840;
c. 9:44 a.m., basement-level, Mechanical Room 0311.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the doors would not close.
Tag No.: K0038
Based on observation and interview, it was determined the facility failed to maintain exit access in one location, affecting one of four floors.
Findings include:
1. Observation on July 10, 2014, at 10:12 a.m. revealed the third floor, Third Medical, exit access corridor system was used as a large storage area.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the storage in the corridor.
Tag No.: K0047
Based on observation and interview, it was determined the facility failed to maintain illuminated exit signage in one location, on one of four floors.
Findings include:
1. Observation on July 9, 2014, at 8:06 a.m. revealed the facility lacked an exit sign, in the exit access corridor system, in the vicinity of the freight elevator.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the area lacked illuminated exit signage.
Tag No.: K0064
Based on observation and interview, it was determined the facility failed to properly install one portable fire extinguisher, on one of four floors.
Findings include:
1. Observation on July 9, 2014, at 10:44 a.m. revealed the fire extinguisher located within the basement-level Electric Shop was installed in excess of sixty inches from the handle to the finished floor.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the fire extinguisher was mounted to high.
Tag No.: K0077
Based on observation and interview, it was determined the facility failed to maintain the piped-in medical gas system in one location, on one of four floors of the building.
Findings include:
1. Observation on July 9, 2014, at 9:44 a.m. revealed medical gas piping, within the basement-level Bed Repair Room, lacked shut-off valves at the base of the risers.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the lack of shut-off valves.
Tag No.: K0211
Based on observation and interview, it was determined the facility failed to properly install alcohol-based hand rub (ABHR) stations in multiple locations, affecting three of four floors.
Findings include:
1. Observation on July 09, 2014, between 8:55 a.m. and 2:01 p.m. revealed ABHR dispensers were positioned over a source of ignition throughout this component.
Exit interview on July 10, 2014, between 12:20 p.m. and 12:40 p.m. with the Facilities Manager confirmed the ABHR dispensers were positioned over sources of ignition.