Tag No.: K0144

The emergency generator must be inspected weekly and exercised under load for 30 minutes monthly. NFPA 110, Standard for Emergency and Standby Power Systems.

1) Review of records determined documentation of the weekly inspections was not available.

2) Observation determined the battery for the emergency generator was maintenance free type. Review of records determined there was no documentation that the fluids were checked weekly.