HospitalInspections.org

Bringing transparency to federal inspections

220 HOSPITAL DRIVE

JACKSON, AL 36545

No Description Available

Tag No.: K0078

The facility failed to maintain the Anesthetizing Locations per code. Findings include:
During the survey, the following are examples of what was observed:

OR 1 - use general anesthesia and/or electrical life support - the following was observed:

a. No smoke venting system

1999 NFPA 99, 5-4.1.2 Supply and exhaust systems for windowless anesthetizing locations shall be arranged to automatically vent smoke and products of combustion.
1999 NFPA 99, 5-4.1.3 Ventilating systems for anesthetizing locations shall be provided that automatically (a) prevent recirculation of smoke originating within the surgical suite and (b) prevent the circulation of smoke entering the system intake, without in either case interfering with the exhaust function of the system.
1999 NFPA 99, 5-4.1.4 The electric supply to the ventilating system shall be served by the equipment system of the essential electrical system specified in Chapter 3, "Electrical Systems."
1999 NFPA 99, 5-6.1.1 Ventilating and humidifying equipment for anesthetizing locations shall be kept in operable condition and be continually operating during surgical procedures (see A-5-4.1).