Bringing transparency to federal inspections
Tag No.: K0012
Based upon observation and interview, it was determined the facility failed to maintain building construction requirements in one location on one of ten floors.
Findings include:
Observation of the sixth floor I.C.U. Waiting Room at 09:24 a.m. on March 13, 2012, revealed horizontal structural steel within to lack spray fireproofing in one location
Interview with facilities manager at 09:25 a.m. on March 13, 2012, confirmed the structural steel to lack spray fireproofing in one location.
Tag No.: K0018
Based upon observation and interview, it was determined the facility failed to maintain two corridor openings in two locations on one of ten floors.
Findings include:
1. Observation of various corridor openings between 09:15 a.m. and 09:22 a.m. on March 13, 2012, revealed the below deficiencies:
a. The sixth floor Family Room corridor entrance door lacks smoke-tight integrity when coupled with the corresponding door frame assembly. 09:15 a.m.
b. The sixth floor I.C.U. Waiting Room corridor entrance door lacks smoke-tight integrity when coupled with the corresponding door frame assembly. 09:22 a.m.
Interview with facilities manager at 09:23 a.m. on March 13, 2012, confirmed the above corridor entrance doors to lack smoke-tight integrity.
Tag No.: K0020
Based upon observation and interview, it was determined the facility failed to maintain one vertical opening in one location on one of five floors.
Findings include:
Observation of the basement-level portion of the conduit shaft enclosure at 08:22 a.m. on March 14, 2012, revealed the shaft to require a fire resistive seal around the annular spaces of miscellaneous electrical conduit.
Interview with facilities manager two at 08:23 a.m. on March 14, 2012, confirmed the vertical opening deficiency.
Tag No.: K0020
Based upon observation and interview, it was determined the facility failed to maintain one vertical opening in one location on one of nine floors.
Findings include:
Observation of the fourth floor electrical room located closest to Patient Room 425 at 09:54 a.m. on March 13, 2012, revealed a conduit penetration at the floor slab assembly.
Interview with facilities manager at 09:55 a.m. on March 13, 2012, confirmed the vertical opening deficiency.
Tag No.: K0020
Based upon observation and interview, it was determined the facility failed to maintain one vertical opening in one location on one of ten floors.
Findings include:
Observation of the sixth floor I.C.U. Waiting Room at 09:26 a.m. on March 13, 2012, revealed two large conduit penetrations located at the floor slab assembly (beyond the suspended ceiling assembly.)
Interview with facilities manager at 09:27 a.m. on March 13, 2012, confirmed the vertical penetrations.
Tag No.: K0025
Based upon observation and interview, it was determined the facility failed to maintain one smoke barrier separation wall in one location on one of nine floors.
Findings include:
Observation of the area beyond the ground floor smoke barrier separation doors (S.D.G05) at 11:12 a.m. on March 13, 2012, revealed a penetration of the smoke barrier separation wall.
Interview with facilities manager at 11:13 a.m. on March 13, 2012, confirmed the smoke barrier separation wall deficiency.
Tag No.: K0025
Based upon observation and interview, it was determined the facility failed to maintain one smoke barrier separation wall in two locations on one of ten floors.
Findings include:
Observation of the portion of the sixth floor smoke barrier separation wall located beyond SD 603 at 09:08 a.m. on March 13, 2012, revealed several penetrations of the smoke barrier wall in this location.
Interview with facilities manager at 09:09 a.m. on March 13, 2012, confirmed the penetrations of the smoke barrier wall.
Tag No.: K0029
Based upon observation and interview, it was determined the facility failed to maintain one hazardous area enclosure in one location on one of five floors.
Findings include:
Observation of the basement-level mechanical room entrance door at 08:06 a.m. on March 14, 2012, revealed the door to be held open by unapproved means.
Interview with facilities manager two at 08:07 a.m. on March 14, 2012, confirmed the door to be held open by means of a chock device.
Tag No.: K0047
Based upon observation and interview, it was determined the facility failed to install and maintain illuminated exit signage in two locations on two of nine floors.
Findings include:
1. Observation of various exit access corridor systems between 10:06 a.m. and 10:22 a.m. on March 13, 2012, revealed the below deficiencies:
a. Illuminated exit signage is lacking at the 200 smoke barrier separation doors. 10:06 a.m.
b. Illuminated exit signage is required within the ground floor S.P.D. corridor (west end.) 10:22 a.m.
Interview with facilities manager at 10:25 a.m. on March 13, 2012, confirmed the absence of illuminated exit signage in the above locations.
Tag No.: K0147
Based upon observation and interview, it was determined the facility failed to maintain electrical systems (and associated apparatus) in one location on one of nine floors.
Findings include:
Observation of the first floor Gift Shop at 10:09 a.m. on March 13, 2012, revealed a surge protector being used to power an electrical lamp.
Interview with facilities manager at 10:10 a.m. on March 13, 2012, confirmed the electrical deficiency stated above.
Tag No.: K0211
Based upon observation and interview, it was determined the facility failed to properly install alcohol-based hand rub dispensers in one location on one of ten floors.
Findings include:
Observation of the sixth floor Rehab Gym at 08:55 a.m. on March 13, 2012, revealed an adjacent electrical outlet in close proximity to the alcohol-based hand rub station.
Interview with facilities manager at 08:56 a.m. on March 13, 2012, confirmed the improper installation of the A.B.H.R. dispenser.
Tag No.: K0012
Based upon observation and interview, it was determined the facility failed to maintain building construction requirements in one location on one of ten floors.
Findings include:
Observation of the sixth floor I.C.U. Waiting Room at 09:24 a.m. on March 13, 2012, revealed horizontal structural steel within to lack spray fireproofing in one location
Interview with facilities manager at 09:25 a.m. on March 13, 2012, confirmed the structural steel to lack spray fireproofing in one location.
Tag No.: K0018
Based upon observation and interview, it was determined the facility failed to maintain two corridor openings in two locations on one of ten floors.
Findings include:
1. Observation of various corridor openings between 09:15 a.m. and 09:22 a.m. on March 13, 2012, revealed the below deficiencies:
a. The sixth floor Family Room corridor entrance door lacks smoke-tight integrity when coupled with the corresponding door frame assembly. 09:15 a.m.
b. The sixth floor I.C.U. Waiting Room corridor entrance door lacks smoke-tight integrity when coupled with the corresponding door frame assembly. 09:22 a.m.
Interview with facilities manager at 09:23 a.m. on March 13, 2012, confirmed the above corridor entrance doors to lack smoke-tight integrity.
Tag No.: K0020
Based upon observation and interview, it was determined the facility failed to maintain one vertical opening in one location on one of five floors.
Findings include:
Observation of the basement-level portion of the conduit shaft enclosure at 08:22 a.m. on March 14, 2012, revealed the shaft to require a fire resistive seal around the annular spaces of miscellaneous electrical conduit.
Interview with facilities manager two at 08:23 a.m. on March 14, 2012, confirmed the vertical opening deficiency.
Tag No.: K0020
Based upon observation and interview, it was determined the facility failed to maintain one vertical opening in one location on one of nine floors.
Findings include:
Observation of the fourth floor electrical room located closest to Patient Room 425 at 09:54 a.m. on March 13, 2012, revealed a conduit penetration at the floor slab assembly.
Interview with facilities manager at 09:55 a.m. on March 13, 2012, confirmed the vertical opening deficiency.
Tag No.: K0020
Based upon observation and interview, it was determined the facility failed to maintain one vertical opening in one location on one of ten floors.
Findings include:
Observation of the sixth floor I.C.U. Waiting Room at 09:26 a.m. on March 13, 2012, revealed two large conduit penetrations located at the floor slab assembly (beyond the suspended ceiling assembly.)
Interview with facilities manager at 09:27 a.m. on March 13, 2012, confirmed the vertical penetrations.
Tag No.: K0025
Based upon observation and interview, it was determined the facility failed to maintain one smoke barrier separation wall in one location on one of nine floors.
Findings include:
Observation of the area beyond the ground floor smoke barrier separation doors (S.D.G05) at 11:12 a.m. on March 13, 2012, revealed a penetration of the smoke barrier separation wall.
Interview with facilities manager at 11:13 a.m. on March 13, 2012, confirmed the smoke barrier separation wall deficiency.
Tag No.: K0025
Based upon observation and interview, it was determined the facility failed to maintain one smoke barrier separation wall in two locations on one of ten floors.
Findings include:
Observation of the portion of the sixth floor smoke barrier separation wall located beyond SD 603 at 09:08 a.m. on March 13, 2012, revealed several penetrations of the smoke barrier wall in this location.
Interview with facilities manager at 09:09 a.m. on March 13, 2012, confirmed the penetrations of the smoke barrier wall.
Tag No.: K0029
Based upon observation and interview, it was determined the facility failed to maintain one hazardous area enclosure in one location on one of five floors.
Findings include:
Observation of the basement-level mechanical room entrance door at 08:06 a.m. on March 14, 2012, revealed the door to be held open by unapproved means.
Interview with facilities manager two at 08:07 a.m. on March 14, 2012, confirmed the door to be held open by means of a chock device.
Tag No.: K0047
Based upon observation and interview, it was determined the facility failed to install and maintain illuminated exit signage in two locations on two of nine floors.
Findings include:
1. Observation of various exit access corridor systems between 10:06 a.m. and 10:22 a.m. on March 13, 2012, revealed the below deficiencies:
a. Illuminated exit signage is lacking at the 200 smoke barrier separation doors. 10:06 a.m.
b. Illuminated exit signage is required within the ground floor S.P.D. corridor (west end.) 10:22 a.m.
Interview with facilities manager at 10:25 a.m. on March 13, 2012, confirmed the absence of illuminated exit signage in the above locations.
Tag No.: K0147
Based upon observation and interview, it was determined the facility failed to maintain electrical systems (and associated apparatus) in one location on one of nine floors.
Findings include:
Observation of the first floor Gift Shop at 10:09 a.m. on March 13, 2012, revealed a surge protector being used to power an electrical lamp.
Interview with facilities manager at 10:10 a.m. on March 13, 2012, confirmed the electrical deficiency stated above.