Tag No.: K0047
Based on observation, it was determined that the facility failed ensure that continuous exit lighting was provided.
Findings include:
1. On 3/13/12 at 11:00 AM, in the presence of Staff #2, the exit sign was not lit in the #2 exit of the basement stair.
Tag No.: K0062
Based on observation, it was determined that the facility failed to ensure that the automatic sprinkler system was continuously maintained.
Findings include:
1. On 3/14/12 at 2:00 PM, in the presence of Staff #2, eight (8) boxes of supplies were stored within 18" of the sprinkler system in the EPS storage room.
Tag No.: K0076
Based on observation, it was determined that the facility failed to ensure that medical gas storage areas are protected.
Findings include:
1. On 3/13/12 at 10:25 AM, in the presence of Staff #2, four (4) tanks of oxygen were unsecured in the basement cylinder storage room.
2. On 3/13/12 at 10:40 AM, in the presence of Staff #2, nine (9) tanks of gas were unsecured in the tank farm.
Tag No.: K0135
Based on observation, it was determined that the facility failed to ensure that flammable liquids are stored in approved containers.
Findings include:
1. On 3/13/12 at 10:10 AM, in the presence of Staff #2, eight (8) cans of flammable paint were stored on a shelf in the non-flammable paint storage area.