HospitalInspections.org

Bringing transparency to federal inspections

4000 SPENCER HWY

PASADENA, TX 77504

Health Care Facilities Code - Other

Tag No.: K0900

The inspector observed, while reviewing documents that the facility failed to provide letters indicating preferred customers status in case of emergency situation for water and fuel source.
NFPA 99: 11-5.3.2

Electrical Systems - Maintenance and Testing

Tag No.: K0914

The inspector observed, while reviewing documents that the facility failed to provide a grounding report .


The inspector observed, while reviewing documents that the facility failed to provide a Line Isolation Monitors testing reports.