HospitalInspections.org

Bringing transparency to federal inspections

1400 E BOULDER ST

COLORADO SPRINGS, CO 80909

No Description Available

Tag No.: K0017

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey July 27 through August 19, 2010 it was determined that the facility failed to maintain the fire resistance rating of the corridor walls.

During the walk through of the facility with the Maintenance Director, the corridor wall, outside of room #1418C, contained a two inch (2") hole in the corridor wall to an adjacent room. The hole was utilized for electrical conduit during remodel of the area. 2000 Edition NFPA 101 Section 19.3.6.2.1

Note: This item was corrected during the survey.

No Description Available

Tag No.: K0018

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey July 27 through August 19, 2010 it was determined the facility failed to maintain the doors to the corridor.

During the walk through of the facility with the Maintenance Director:

1) Seven (7) patient room doors contained excessive gaps in excess of 1/2 inch between the door and the frame or the door and the stop and would not resist the passage of smoke per section 19.3.6.1.
a. #7532
b. #7512
c. #6646
d. #6620
e. #5640
f. #5649
g. #4526

2) Corridor doors would not positively latch into the frame when closed. 19.3.6.3.2
a) Nine (9) corridor doors would not latch into the frame when closed.
1. Room #7524 - door would not latch into the frame
2. Room #7504 - door would not latch into the frame
3. Room #7530 - door was tight on frame and would not latch
4. Room #7508 - door was tight in the frame and would not latch
5. Room #6540 - door would not latch into the frame
6. One (1) door on the Therapy room, located on the seventh (7th) floor, would not latch into the frame
7. Room #5642 - would not latch into the frame
8. Room #5526 - door would not shut into the frame
9. Room #4530 - door would not latch into the frame
b) Three (3) 70/30 double doors were not considered to be positive latching (due to a thumb bolt lock) on the "30 side", when in the closed position. The following doors contained slide locks on the "30 side" of the door for locking:
1. Room #465, which is located off of the corridor, contains a 70/30 door. The 30 portion of the door contains a thumb lock and does not positively latch into the frame.
2. Room #4654, which is located off of the corridor, contains a 70/30 door. The 30 portion of the door contains a thumb lock and does not positively latch into the frame.
3. Room #2621 A and B contained a double door that opened into the corridor. One (1) side of the double door contained a thumb lock and would not positively lock into the frame.

Note: All deficiencies were corrected during the survey by Maintenance Staff.

No Description Available

Tag No.: K0020

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey July 27 through August 19, 2010 it was determined the facility failed to maintain the fire resistive rating of the vertical opening.

During the walk through of the facility with the Maintenance Director, the facility contained a vertical opening, in the Central Tower, from the first floor to the second floor at section 1L-2D. This area contained an egress corridor located in the vertical opening that was unprotected. Sections 19.3.1 and 8.2.5.

No Description Available

Tag No.: K0027

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey July 27 through August 19, 2010 it was determined the facility failed to maintain the smoke barrier doors.

During the walk through of the facility with the Maintenance Director, two (2) fire barrier doors would not latch into the frame when closed;
1) #4685A smoke door, one (1) side would not latch into the frame
2) #1740A smoke door would not shut completely, this was due to an auto closure device that would not close the door

Note: All cross corridor deficiencies were corrected during the survey.

No Description Available

Tag No.: K0029

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey July 27 through August 19, 2010 it was determined the facility failed to maintain the doors to the hazardous areas.

During the walk through of the facility with the Maintenance Director, the room adjacent to room #1482A contained a high amount of combustible material. The doors contained a self-closing device, however it was disconnected from the door. Per 19.3.2.1 high hazard areas must contain a self-closing device on the door.

Note: This item was corrected during the survey.

No Description Available

Tag No.: K0033

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey conducted July 27 through August 19, 2010 it was determined the facility did not maintain the fire exit hardware on exit doors.

During the walk through of the facility with the Maintenance Director, the fire exit hardware located at seven areas (7) on exit and fire-rated doors were not UL rated as fire-rated hardware.
1) Seventh (7th) floor fire door exit
2) Two (2) sets of smoke doors, located on the seventh floor Central Tower 7C
3) Fifth floor (5th) fire exit door
4) Two sets of smoke doors, located on the fifth floor Central Tower 5C
5) Fourth floor (4th) fire exit door
6) Two sets of smoke doors, located on the fifth floor Central Tower 4C
7) Smoke door #0405, located in the basement

No Description Available

Tag No.: K0038

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey July 27 through August 19, 2010 it was determined the facility failed to arrange the exit access so that exits are readily accessible at all times.

During the walk through of the facility with the Maintenance Director, the facility failed to contain an egress path from the exit door to a public way. This area was located at the north egress (1J) which contained a small four foot by four foot (4'x4') concrete pad only. The exit discharge did not contain a hard packed surface to a public means per section 19.2.7 and 7.7.1.

No Description Available

Tag No.: K0051

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey conducted July 27 through August 19, 2010 it was determined that the facility failed to install and maintain the fire alarm system with approved components, devices or equipment in accordance with NFPA 72.

During the walk through of the facility with the Maintenance Director, the operating room suite contained a fire alarm system that included strobes and alarms in the corridors. The operating rooms contained blinds or window coverings that obscured the visual notification of the alarm devices from the corridor side. Per 19.3.4.3.1, 9.6.3 and 9.6.3.6 exception #2.

No Description Available

Tag No.: K0056

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey conducted July 27 through August 19, 2010 it was determined the facility failed to provide a complete automatic sprinkler system in accordance with NFPA 13.

During the walk through of the facility with the Maintenance Director:

1) The East Tower basement elevator room, which was located off of the egress corridor, did not contain sprinkler protection per section 19.3.6.1. The room was separated by a one-hour wall only.

2) The facility contained quick response sprinkler heads and standard response heads installed and located in the same compartment. Per 19.3.5.1, 9.7.1, and 2000 Edition NFPA 13 Section 5-3.1.5.2 "When existing light hazard systems are converted to use quick-response or residential sprinklers, all sprinklers in a compartmented space shall be changed."

a) Third floor executive office corridor contains four (4) standard response heads and all others are quick response heads
b) Three (3) quick response heads in the corridor outside room #3129 and all other heads are standard response heads
c) One (1) quick response and one (1) standard response in suite #3119
d) One (1) quick response and One (1) standard response in room #3393
e) Six (6) standard response and ten (10) quick response heads located in the same compartment of the oncology corridor

3) The facility contained one (1) painted sprinkler head in the Clinical Engineering office located on the second (2nd) floor.

4) One (1) sprinkler head, located at the smoke door #1722A, was installed within three inches (3") from the smoke door. Per NFPA 13, section 5-6.3.3 "Sprinklers shall be located a minimum of 4 in. (102 mm) from a wall."

5) The pharmacy contained a sprinkler riser with two (2) OS&Y valves that were not supervised by electronic supervision. The OS&Y valves were locked open by use of a chain and lock. The air compressor for the pre-action system on zone six (6) would cycle every forty (40) seconds, which indicated a leak on the system.

Note: Item (5) and item (4) were corrected during the survey.

No Description Available

Tag No.: K0062

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey July 27 through August 19, 2010 it was determined the facility failed to maintain the automatic sprinkler system in reliable operating condition.

During the walk through of the facility with the Maintenance Director:

1) Sprinkler gauges were outdated and documentation could not be located to indicate a calibration had occurred within the past five years (5) per NFPA 25, Chapter 5, section 5.3.2. "Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced."

a) Pre-action valve for surgery rooms 8&9, contained one (1) gauge dated 2004
b) Pre-Action valve zone 4, MRI, contained one (1) gauge dated 2003
c) Pre-Action valve zone 4, radiology, contained one (1) gauge dated 2004

2) Escutcheon plates were loose or missing from the sprinkler heads in six (6) locations;
a) Room #6630-escutcheon plate missing
b) Nurse station on fifth (5th) floor (adjacent to room #5626) - gap around escutcheon plate and ceiling
c) Fire extinguisher was not fully charged
d) In the corridor outside of room #4568, charge indicator was in the red, non-charged, area
e) North facility room #3304
f) North facility sterile processing room

Note: All items corrected during the survey

No Description Available

Tag No.: K0073

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey conducted July 27 through August 19, 2010 it was determined the facility allowed the use of flammable decorations.

During the walk through of the facility with the Maintenance Director, the facility displayed a five foot (5') tall Christmas tree in the Radiology Nursing Unit. Documentation could not be provided to indicate the tree was flame retardant.

Note: The tree was removed immediately by staff.

No Description Available

Tag No.: K0074

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation and record review during the survey conducted on July 27 through August 19, 2010 it was determined the facility failed to provide curtains that comply with NFPA 701 in all areas.

During record review and walk through of the facility with the Maintenance Director, curtains located throughout the facility did not contain tags or markings showing they met NFPA 701 requirements.
1) Blood bank office #2410B contained sheer type draperies on the window
2) Pink curtains were located in the OR overflow rooms
3) Room #1776 contained draperies that were not labeled

Note: Curtains were removed by staff during the survey.

No Description Available

Tag No.: K0077

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey July 27 through August 19, 2010 it was determined the facility failed to provide a separation between service valves as required by NFPA 99.

During the walk through of the facility with the Maintenance Director, the facility contained emergency oxygen shutoff valves in two (2) areas. These emergency valves controlled oxygen valves in two rooms that were without separation between the beds it controls and the shut off valve. Per NFPA 99 section 4-3.1.2.3(d) "Zone Valve. Station outlets shall not be supplied directly from a riser unless a manual shutoff valve located in the same story is installed between the riser and the outlet with a wall intervening between the valve and the outlet."

1) Respiratory Care area contains One (1) med gas valve not separated by a wall.

2) Hat Team Unit, room #3142, contains one (1) med gas shutoff valve.

Note: The above areas are currently office space and do contain patients; however the valves were active during the survey. The facility disconnected the valves from service during the survey.

No Description Available

Tag No.: K0078

Bldg A-1 - Memorial Hospital Central - Central Tower

Through observation during the survey July 27 through August 19, 2010 it was determined the facility failed to maintain the anesthetizing locations per NFPA 99.

During the walk through and discussions with the maintenance staff and Maintenance Director;

1) Anesthetizing operating rooms did not contain ground fault or line isolation electrical protection. Per the 2000 Edition of NFPA 99, Section 3-3.2.1.2 these locations are considered "wet" locations and must be protected by either GFCI (ground fault circuit interruption) or LIM (line isolation monitors).

a) Room #1653, located in the MSCA area, utilized as a pediatric procedure room. Per conversations with the nurse staff, inhaled anesthesia is utilized in the room during procedures.
b) 2nd floor Central tower Zone 1 Surgery A,B, and C.

2) The facility failed to provide a means by which to exhaust the windowless anesthetizing operating rooms in the event that smoke or the products of combustion are detected, as required by NFPA 99, 5-4.1.2. Per discussions with Maintenance staff, it appears the AHU (air handling unit) shuts down on ducts detector activation in some cases or the air handling system is operated by duct detection only in all cases and does not exhaust products of combustion of smoke per NFPA 99 5-4.1.2 and 5-4.1.3.

a) Room #1653, located in the MSCA area, utilized as a pediatric procedure room.
b) Cath lab
c) 2nd floor Central tower Zone 1 Surgery A,B, and C. This area is setup to shut down on activation of a duct detector only. Smoke detectors are equipped in the operating rooms, however they are not interfaced with the HVAC system.
d) Operating rooms one through five (1-5) in the Central Tower. This area is setup to shut down on activation of a duct detector only. Smoke detectors are equipped in the operating rooms, however they are not interfaced with the HVAC system.
e) Operating rooms seven through eleven (7-11) contain an AHU (air handling unit) that controls only operating rooms seven through eleven (7-11) and no other areas. Duct detection operates the exhaust fan function only. Smoke detection does not activate the exhaust function of the AHU unit.
f) Operating Room six (6) contains an AHU (air handling unit) that operates only operating room #6 and no other areas. Duct detection operates an exhaust fan - smoke detection in rooms do not activate the fan mode.

No Description Available

Tag No.: K0144

Bldg A-1 - Memorial Hospital Central - Central Tower

Through record review, observation, and testing during the survey July 27 through August 19, 2010 it was determined the facility failed to maintain the emergency generator transfer time at less than ten (10) seconds.

During the review of the facility's records, maintenance presented documentation indicating the transfer time between loss of power and generator transfer was greater than ten (10) seconds on the transfer switches for the Life Safety Branch of the emergency power system. 19.2.9.1 and 7.9.1.2.

Note: This deficiency was corrected during the survey by maintenance by adjusting the transfer switches affected to properly transfer within ten (10) seconds.